Presentation is loading. Please wait.

Presentation is loading. Please wait.

easYgen-3000XT Series Training

Similar presentations


Presentation on theme: "easYgen-3000XT Series Training"— Presentation transcript:

1 easYgen-3000XT Series Training
Operation

2 Introduction The 320x240 pixel graphic interactive LC display provides soft keys whose functionality changes depending on application and operation.

3 Display topography Last alarm Current operation
i.e. Cranking, loading, start pause, etc. Single line diagram and operation mode

4 Symbol meaning in the single line diagram
Voltage detected Rotation field clockwise Rotation field counter clockwise Import/Export Mains power Delayed engine monitoring expired Engine speed detected

5 Status menu Advance to Next Screen Select subdirectory Screen Name

6 Status menu Setpoints

7 Status menu Synchroscope

8 Status menu Event history

9 Status menu Event history

10 Status menu Counters

11 Status menu Measured values

12 Status menu Version

13 Status menu Version

14 Status menu Online diagram visible

15 Parameter menu Press „parameter” soft key Select subdirectory
Screen Name

16 Parameter menu Screen Name Pathway to this screen

17 Parameter menu Move white cursor line up and down
Press „Enter” soft key to select parameter to be changed

18 Parameter menu Move cursor if value is numeric
Other parameters are cleared from display Old value New value Select value „+ / -” soft keys

19 Password protection Three levels of password protection enable multiple users with varying degrees of access Password protection valid for 2 hours Level 1/End user Level 2/Temporary commissioning (random number+200)*3 Level 3/Commissioning Load

20 Password protection In principle the easYgen3000 password system is kept for the easYgen3000XT, but was extended HMI/ModbusRTU/CANopen support the same numeric password system as before ToolKit and ModbusTCP support an alpha-numeric password, The device has a number of fixed accounts with associated code levels, parallel to the numeric password system There are also algorithmic alphanumeric passwords analog to the numeric algorithmic passwords Load

21 Password protection Load

22 Password protection Press „parameter” soft key Password screen

23 Password protection Individual parameters cannot be viewed or edited if the password has not been entered or has expired. Names for submenus are always displayed Load

24 Operation modes Changing the operation mode may be performed via:
a shutdown alarm class the HMI soft keys the LogicsManager Button will be illuminated after selecting one of the operating modes Load

25 Operation modes A shutdown alarm will change the operating mode to STOP Load

26 Operation modes Changing the operation mode via HMI buttons Load

27 Start / stop in manual Generator circuit breaker Mains circuit breaker
Start/Stop via push buttons Conditions for “AUTO” are ignored Start prevented if active C - F class alarm No automatic start if mains failure detected Open / close GCB External start and CB close now accepted Mains circuit breaker Manual operation of MCB only LM: Enable MCB is “true” (default DI6) Open / close MCB Load

28 Start / stop in manual Unit is trying to close the breaker
Stop command issued Start/run command issued Unit is trying to close the breaker Unit is trying to open the breaker Load

29 Start / stop in AUTO Generator: Start conditions
LM: Start in auto is “true” may be used with load dependent start/stop function LM: Start w/o load is “true” LM: Critical mode is “true” Loss of mains {GCB/MCB} (Emergency mode) Mains voltage/frequency out of operating range Mains rotation field wrong “Fail to close MCB” (if parameter is enabled) Stop conditions LM: Start conditions are “false” Alarm class C-F detected LM: Stop in auto LM: Inhibit emergency mode Mains: Close MCB: Open MCB: Mains are within accepted limits  Dependent upon breaker logic DI7 is de-energized (MCB is open)  For mains decoupling LM: Enable MCB is “true” (default DI6) Conditions for synchronization or dead bus closing are met Load

30 Start / Stop logic Diesel engine Gas engine
- Pre-glow function - Fuel or Stop solenoid activation - Crank/start circuit control Gas engine - Ignition - Gas valve External logic Fuel solenoid as a start request to external controllers - External control must take care of start sequence – no start failure Start stop logic mode OFF - The start stop sequence is completely disabled Update the template / implement the ster stop logic OFF

31 Mains data It is possible to not display mains data Load

32 Application modes Parameter name: in product spec:
There are four application modes available: Parameter name: in product spec: [GCB/MCB] [GCB/MCB open/close {2oc}] [GCB] [GCB open/close {1oc}] [GCB open] [GCB open {1o}] [none] [0-CB-Mode {0}]

33 The 4 Application Modes - [GCB/MCB]
Two breaker mode Mains/utility breaker (MCB) and generator breaker (GCB) Generator protection for shutdown and GCB open command Single or multiple genset operation GCB & MCB open close command Automatic mains failure (AMF) / emergency mode Fixed Input Fixed Output DI 8 reply GCB (B contacts) DO 6/7 GCB close / open DI 7 reply MCB (B contacts) DO 8/9 MCB close / open

34 The 4 Application Modes - [GCB]
One breaker mode Generator breaker (GCB) control Generator protection for shutdown and GCB open command Single or multiple genset operation GCB open/close command Grey= breaker status only: MCB control is external Fixed Input Fixed Output DI 8 reply GCB (B contacts) DO 6/7 GCB close / open DI 7 reply mains parallel

35 The 4 Application Modes - [GCB open]
Breaker open mode Generator breaker open only Generator protection for shutdown and GCB open command Single or multiple genset operation GCB open command (shunt trip) Fixed Input Fixed Output DI 8 reply GCB (B contact) DO 7 GCB open DI 7 reply MCB (mains parallel)

36 The 4 Application Modes - [none]
Base mode No breaker control Single or multiple genset operation Generator and engine protection All breaker control is external Fixed Input DI 8 reply GCB (B contact) DI 7 reply MCB (mains parallel)

37 FAQ Frequently Asked Questions
How can I reset the maintenance counter? How can I define the loss of mains condition in order to activate the emergency mode?

38 FAQ How can I reset the maintenance counter?
The maintenance hours counter decreases as the operation hours counter increases. The maintenance days counter decreases as the Internal calendar clock increases. When a count down timer reaches “0” an alarm is issued. The reset procedure is as follows: FAQ Step 1: Enter password (see config. manual)

39 FAQ How can I reset the maintenance counter? Step 2:
Symbol appears only if the required password is active Press “Next page”  “Counters and service” buttons to get to counters screen. Next, press the “Tool” symbol button.

40 FAQ How can I reset the maintenance counter? Step 3: Step 4:
Press enter, select YES, press enter. Now the alarm may be acknowledged in the alarm list. Select counter to reset.

41

42


Download ppt "easYgen-3000XT Series Training"

Similar presentations


Ads by Google