Single Phase Pole Mounted
Recloser Bypass Single Phase Pole Mounted © 2018 Iowa Association of Electric Cooperatives DISCLAIMER: This job hazard analysis (JHA) has been made available for informational and educational purposes only. The IAEC does not make any representation or warranty with respect to the accuracy, applicability, fitness, or completeness of the JHA. The IAEC hereby disclaims any and all liability to any party for any direct, indirect, implied, punitive, special, incidental or other consequential damages arising directly or indirectly from any use of this JHA which is provided as is.
2
OSHA Required Tailgate Discussion Topics
Hazards Associate with the job Work Procedures Involved Special Precautions Energy Source Controls PPE Required The five topics required by OSHA to discuss in the tailgate. First letter from each topic = How Well Should Everyone Plan © 2018 Iowa Association of Electric Cooperatives
3
Work Procedures Involved Hazards associated with the job
Special Precautions Energy Source Controls Personal Protective Equipment Be sure to record your emergency location and post in a location everyone on the crew knows. Have your PPE and First Aid kit available Be sure your AED is accessible. A safe job begins with a thorough inspection of… Tools Be certain all of your tools are in good shape. Equipment Make sure your trucks are all in working order take time to preflight your equipment and insure there are no surprise. Line/Structure Look over the line and structure. Are there any potential hazards? (Broken insulators, damaged wire, clearances over roads or from trees?) Be aware of your work area, be sure to cover anything you can reach touch or fall into. And anything that can reach touch or fall into you! Discuss all PPE needed for the job and wear your PPE. Be sure to inspect your equipment prior to use. Identify all voltages you are exposed to. Be sure to have all of your Arc-Flash protective gear on. Identify a dedicated observer Working in traffic exposes you to hazards that are difficult to control. Give the vehicles plenty of time to see and avoid you! Follow the manual of traffic control for your area. Slips trips and falls are some of the most common injuries, look for hazards that could cause this. Be sure to inspect and wear your fall arrest harness. Here are the five topics again with signs and bubbles to jump start tailgate discussion!! Click on the icon to bring up a text box. Click on the icon again to make the text box go away Gets the crew involved. Gives the feeling of knowing it is ok to ask questions, give suggestions, see something, say something! The next slides will get directly into the task at hand. Visual, written and audio will all be used here! There are suggestions in the notes as to what to discuss. This will get the Team involved, creating communication channels to open! © 2018 Iowa Association of Electric Cooperatives
4
Visually inspect the recloser for damage
Visually inspect the recloser for damage. Look to be sure all of the jumpers are in good shape. Visually inspect the recloser for damage. Look to be sure all of the jumpers are in good shape. © 2018 Iowa Association of Electric Cooperatives
5
Remove the bypass fuse from the hanger and move it to the bypass cutout.
© 2018 Iowa Association of Electric Cooperatives
6
Close the bypass fuse. Close the bypass fuse.
© 2018 Iowa Association of Electric Cooperatives
7
Be sure the bypass is complete.
© 2018 Iowa Association of Electric Cooperatives
8
Open the recloser handle.
© 2018 Iowa Association of Electric Cooperatives
9
Be sure you listened and heard the internal operation.
© 2018 Iowa Association of Electric Cooperatives
10
Install the jumper insulated stand-off.
© 2018 Iowa Association of Electric Cooperatives
11
Install the jumper insulated stand-off.
© 2018 Iowa Association of Electric Cooperatives
12
© 2018 Iowa Association of Electric Cooperatives
13
Remove the source side jumper and place it on the insulated stand-off.
© 2018 Iowa Association of Electric Cooperatives
14
© 2018 Iowa Association of Electric Cooperatives
15
© 2018 Iowa Association of Electric Cooperatives
16
Take the load side jumper down and place it on the system neutral.
© 2018 Iowa Association of Electric Cooperatives
17
© 2018 Iowa Association of Electric Cooperatives
18
© 2018 Iowa Association of Electric Cooperatives
19
Remove the source side jumper from the insulated stand-off and place it on the system neutral.
© 2018 Iowa Association of Electric Cooperatives
20
© 2018 Iowa Association of Electric Cooperatives
21
You can now disconnect the case ground and remove the recloser from the pole.
© 2018 Iowa Association of Electric Cooperatives
22
© 2018 Iowa Association of Electric Cooperatives
23
Install the new recloser and connect the case grounds first
Install the new recloser and connect the case grounds first. Be sure the control handle is in the open position. Install the new recloser and connect the case grounds first. Be sure the control handle is in the open position. © 2018 Iowa Association of Electric Cooperatives
24
Move the source side jumper to the insulated stand-off.
© 2018 Iowa Association of Electric Cooperatives
25
© 2018 Iowa Association of Electric Cooperatives
26
© 2018 Iowa Association of Electric Cooperatives
27
Connect the load side jumper to the load side line.
© 2018 Iowa Association of Electric Cooperatives
28
© 2018 Iowa Association of Electric Cooperatives
29
© 2018 Iowa Association of Electric Cooperatives
30
Move the source side jumper to the source line.
© 2018 Iowa Association of Electric Cooperatives
31
© 2018 Iowa Association of Electric Cooperatives
32
© 2018 Iowa Association of Electric Cooperatives
33
Remove the insulated stand-off.
© 2018 Iowa Association of Electric Cooperatives
34
© 2018 Iowa Association of Electric Cooperatives
35
Close the recloser control handle.
© 2018 Iowa Association of Electric Cooperatives
36
© 2018 Iowa Association of Electric Cooperatives
37
Open the bypass fuse. Open the bypass fuse.
© 2018 Iowa Association of Electric Cooperatives
38
© 2018 Iowa Association of Electric Cooperatives
39
Remove the fuse door. Leaving it hanging open will cause it to fill with contaminants.
© 2018 Iowa Association of Electric Cooperatives
40
Place the bypass fuse back in it’s storage location with the open end down. This will prevent it from filling with contaminants. Place the bypass fuse back in it’s storage location with the open end down. This will prevent it from filling with contaminants. © 2018 Iowa Association of Electric Cooperatives
41
The job is complete. The job is complete.