1 Portable Fire extinguisher

2 MOTIVATION Portable fire extinguishers can provide the firefighter with another tool for fire fighting. Of all the equipment used by firefighters, the portable fire extinguisher is probably the least understood. It is important that firefighters have a working knowledge of portable fire extinguishers, especially since they are perhaps the most readily available firefighting tools at the firefighter’s disposal. We live in a world regulated by codes and standards, therefore, in almost any commercial or industrial building, and a large percentage of residential structures, there are portable extinguishers. The firefighter must understand how fire extinguishers work, not only to perform better at fires, but to better educate the public as to how portable fire extinguishers play a part in fire prevention. The extinguisher is an excellent tool for combating small, incipient stage fires. With the speed that a firefighter can use an extinguisher, it is much easier and faster than using an attack line. However, only extensive training will prepare the firefighter in the appropriate use of fire extinguishers.

3

4

5 FIRE EXTINGUISHERS

6 The Fire Triangle Fuel Oxygen Heat Fuel Oxygen Heat Fuel Fuel Oxygen

7 REVIEW OF CLASSES OF FIRE
Class A -Ordinary Combustibles: Wood, Cloth, Paper, Rubber, Plastic Class B -Flammable Liquids: Gasoline, Oil, Lacquer, Paint, Mineral Spirits, and Alcohol Class C -Energized Electrical Equipment: Household Appliances, Computers, Transformers, and Overhead Transmission Lines Class D -Combustible Metals: Aluminum, Magnesium, Titanium, Zirconium, Sodium, and Potassium Class K –Combustible Cooking Media: Vegetable or Animal Oils and Fats

8

9

10 AGENTS USED IN FIRE EXTINGUISHERS
Pump tank & backpack pump (water). Stored pressure (water). AFFF (aqueous film forming foam). Halon 1211 (bromochlorodifluromethane). Halon 1301 (bromotrifluoromethane). Co2 (liquefied compressed gas). Dry Chemical (ordinary and multipurpose).

11

12

13 STORED PRESSURE VS PUMP TANK WATER
Stored pressure can be used on small Class A fires, small hot spots especially during overhaul operations, and chimney fires. The difference between the two is that the air pressurized uses air pressure or nitrogen gas to expel the water, whereas, the pump tank water is manually pumped to siphon water.

14

15 HALON EXTINGUISHERS Usually used to protect energized electrical equipment (Class C fires) found in computer server rooms, etc. The Montreal Protocol on Substances that Deplete the Ozone Layer requires a complete phaseout of the production of halogens by the year The U.S. stopped producing halogens at the end of However, these units may still be found.

16 WARNING When halon is used to extinguish a fire, it decomposes and liberates toxic components, so these agents should not be used in unventilated, confined spaces.

17

18 CARBON DIOXIDE EXTINGUISHERS
CO2 extinguishers are effective in extinguishing Class B and C fires. Carbon dioxide gas displaces available oxygen and smothers the fire. Re-ignition is a danger.

19 CARBON DIOXIDE EXTINGUISHERS
CAUTION: Never mix or contaminate dry chemicals with any other type of agent because they may chemically react and cause a dangerous rise in pressure inside the extinguisher.

20

21 DRY CHEMICAL EXTINGUISHERS
Dry chemical agents are for use on Class A-B-C fire and/or Class B-C fires. The following are commonly used dry chemicals: Sodium bicarbonate Potassium bicarbonate Urea-potassium bicarbonate Potassium chloride Monoammonium phosphate

22 TYPES OF HANDHELD DRY CHEMICAL EXTINGUISHERS
Stored-pressure –similar in design to the air-pressurized water extinguisher, and a constant pressure of about 200 psi. Cartridge-operated –employs a pressure cartridge connected to the agent tank which becomes pressurized by a plunger once activated. The cartridges are carbon dioxide.

23

24 CO2 VS DRY CHEMICAL EXTINGUISHERS
One advantage to using a CO2 extinguisher has over a Dry Chemical fire extinguisher is that it does not leave a residue or corrode electrical contacts.

25 WHEELED DRY CHEMICAL EXTINGUISHERS
Dry chemical wheeled units are similar to the handheld units but on a larger scale. They are rated for Class A, Class B, and Class C fires based on the dry chemical in the unit.

26 WHEELED DRY CHEMICAL EXTINGUISHERS
CAUTION: The top of the extinguisher should be pointed away from the firefighter or other personnel when pressurizing the unit. Because of the size of the nozzle, the firefighter should be prepared for a significant nozzle reaction when it is opened.

27

28 DRY POWDER EXTINGUISHERS
No single agent will control or extinguish metal fires! Portable extinguishers for Class D fires come in both handheld and wheeled models. The agent must be applied in sufficient depth to completely cover the area that is burning to create a smothering blanket. Then, a 1- to 2-inch layer of powder should be spread nearby and the burning metal shoveled onto this layer with more powder added as needed. After extinguishment, the material should be left undisturbed.

29

30 CLASS K EXTINGUISHERS Extinguishing agent is a potassium acetate with a low PH and actually lowers the temperature of the burning material even after the fire has been extinguished. It was designed to discharge a fine mist to help prevent grease splash and fire reflash for the non- expert user at a safe distance from the fire. It can be used on Class C and even some Class A fires and leaves no “dry chemical residue” for clean- up. Required in the cooking areas of all Commercial buildings.

31 CLASS K EXTINGUISHERS Class K fire extinguishers shall be provided for hazards where there is a potential for fires involving combustible cooking media (vegetable or animal oils and fats). Maximum travel distance shall not exceed 30 ft from the hazard to the extinguishers.

32 CLASS K

33 PORTABLE FIRE EXTINGUISHERS RATINGS
Class A extinguisher - rated 1-A through 40-A. Class B extinguisher -- rated 1-B through B. Class C extinguisher -- agent tested for electrical non- conductivity. Class D extinguisher -- rated on types of combustible metal.

34 PORTABLE FIRE EXTINGUISHERS RATINGS
For a 1-A rating, 1 ¼ gallons of water are required. A 2-A requires 2 ½ gallons or twice the 1-A capacity. The rating for Class B is based on the approximate square foot area of a flammable liquid fire that a nonexpert operator can extinguish.

35

36 SELECTION FACTORS Classification of the burning fuel.
Rating of the extinguisher. Hazards to be protected. Severity of the fire. Atmospheric conditions. Personnel available. Ease of handling. Life hazard or operational concerns.

37 FIRE EXTINGUISHER SIZE AND PLACEMENT FOR CLASS A HAZARDS
Criteria *Up to two water-type extinguishers, each with 1-A rating, can be used to fulfill the requirements of one 2-A rated extinguisher †Two 2 ½ gallon water-type extinguishers can be used to fulfill the requirements of one 4-A rated extinguisher ‡See E.3.3 Light (Low) Hazard Occupancy Ordinary (Moderate) Hazard Occupancy Extra (High) Minimum rated single extinguisher 2-A* 4-A† Maximum floor area per unit of A 3000 ft2 1500 ft2 1000 ft2 Maximum floor area for extinguisher 11,250 ft‡ Maximum travel distance to extinguisher 75 ft

38 FIRE EXTINGUISHER SIZE AND PLACEMENT FOR CLASS B HAZARDS
Type of Hazard Basic Minimum Extinguisher Rating Maximum Travel Distance to Extinguishers Light (Low) 5-B 10-B 30 ft 50 ft Ordinary (Moderate) 20-B Extra (High) 40-B 80-B

39 INSPECTION PROCEDURES FOR FIREFIGHTERS
External condition –no apparent damage Hose/nozzle –in place Weight –feels as though it contains agent Pressure gauge (if available) –in operable range

40 INSPECTION PROCEDURES FOR THE PUBLIC
Extinguisher in proper location & accessible. Inspect discharge horn & nozzle. Operating instructions legible. Check lock pins & tamper seals. Full of agent and/or fully pressurized. Date of previous inspection (determined by code). Condition of hose & fittings.

41 RECORDS Month. Year. Type of maintenance. Date of last recharge.
Building owners should keep the following records on maintenance and inspections: Month. Year. Type of maintenance. Date of last recharge.

42 PORTABLE FIRE EXTINGUISHER VALUES
Three important factors that determine the value of a fire extinguisher: Serviceability. Accessibility. Users ability to operate.

43

44

45 MAINTENANCE CHECK Maintenance procedures should include examination of three basic parts: Mechanical parts. Extinguishing agents. Expelling means.

46 REPAIRS Leaking hoses, gaskets, nozzles, and loose labels can be replaced by firefighters. Leaking, corroded, or otherwise damaged extinguisher shells or cylinders should be discarded or returned to the manufacturer for repair. If an extinguisher shows only slight damage or corrosion but it is uncertain whether or not the unit is safe to use, it should be hydrostatically tested by either the manufacturer or a qualified testing agency.

47 CAUTION Never attempt to repair the shell or cylinder of a defective fire extinguisher. Contact the manufacturer for instructions on where to have it repaired or replaced.

48 HYDROSTATIC TEST INTERVAL FOR EXTINGUISHERS
Extinguisher Type Test Interval (Years) Stored-pressure water, loaded stream, and/or antifreeze 5 Wetting agent AFFF (aqueous film forming foam) FFFP (film-forming fluoroprotein foam) Dry chemical with stainless steel shells Carbon dioxide Wet chemical Dry chemical, stored-pressure, with mild steel shells, brazed brass shells, or aluminum shells 12 Dry chemical, cartridge- or cylinder-operated, with mild steel shells Halogenated agents Dry powder, stored-pressure, cartridge- or cylinder-operated, with mild steel shells

49

50

51 OBSOLETE EXTINGUISHERS
Soda-acid extinguisher. Inverted foam extinguisher. Cartridge-operated water extinguishers. Liquid carbon tetrachloride extinguishers. Copper or brass with cylinders either soft soldered or riveted Should have been removed from service by January, 1982

52 OPERATING PORTABLE FIRE EXTINGUISHERS
P-A-S-S P -Pull the pin A -Aim the nozzle at the base of the fire S -Squeeze the handle S -Sweep at the base of the fire

53

54

55

56

57

58 QUESTIONS?

59 REMEMBER…

60 LET’S GO PUT THE WET STUFF ON THE RED STUFF THEN!