Calculation Speed Drill Varied-1
©Ted “Smitty” Smith 2011,2017
2
Click on the left mouse button to begin.
Instructions This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead of two minutes. Attempt to answer the questions and then when the slide show completes, Check your answer. When you reach the end of the drill all of the slides will be repeated without the timer so you will have time to check and verify your answers at that time. Click on the left mouse button to begin.
3
What is the minimum sized THHN conductor that can be used for conductors between the controller and the motor of a part winding connected, 5 HP, single phase, 208 volt motor that has a nameplate rating of amperes? All equipment has a 75 degree C temperature rating.
4
14 AWG
5
What is the demand on the main service entrance of an apartment complex that has a three phase, 480V service for 10 single phase, 208V ranges that have a nameplate rating of 14.2 kW?
6
37,950 VA
7
What size copper bonding jumper is required for the load side of a service if the service conductors are 4/0 copper and the main breaker is 200 amperes?
8
6 AWG
9
What is the maximum size inverse-time circuit breaker allowed for a 30 HP, three-phase, 208 volt, Design B motor for branch circuit, short circuit protection?
10
225 Amp
11
What is the demand on the main service entrance of a restaurant that has the following kitchen equipment? (3) Booster heaters for dishwashing equipment rated at 3.9 kW each (2) Deep fryers rated at 5.9 kW each (2) Electric grills rated at 11.2 kW each (1) Warming table rated at 2.9 kW
12
31.72 kVA
13
What is the minimum sized service that can be used for an office building that has a 480V, three phase service if the total calculated demand on the service is VA?
14
1000 Amp
15
What is the minimum circular mill rating for the feeder conductors that are run 100 ft from the service to an 84 amp calculated load supplied by 240 volt, three-wire system with a voltage drop of 3 percent applied? (CM is based on VD calculation)
16
30,100 CM
17
What size THWN copper conductors are required to supply a load on the secondary side of a transformer if the load is a continuous load of 50 amps and non-continuous load of 20 amps?
18
3 AWG
19
Calculate at continuous operation
What is the load in VA for the following luminaires: VA (each) recess luminaires VA (each) incandescent luminaires VA (each) electric discharge luminaires Calculate at continuous operation
20
VA
21
What size copper grounding electrode conductor is required to a ground rod if the service conductors are rated 250 KCMIL copper?
22
6 AWG
23
What is the demand load in VA for 55-11 kW ranges installed in an apartment complex?
24
66,250 VA
25
What is the lighting load in VA for 140 ft of show window used at continuous operation?
26
35,000 VA
27
What is the general lighting load and receptacle load and small-appliance plus laundry load for sq. ft dwelling units in a complex? (Calculate the load in VA)
28
51,150 VA
29
What is the demand load in VA for a range with a 16 kW rating?
30
9,600 VA
31
What is the load in VA for the general-purpose lighting load in a hotel or motel with 50 units of 420 sq. ft each?
32
18,800 VA
33
What is the demand on the main service entrance for 23- 4
What is the demand on the main service entrance for kW rated electric dryers?
34
40,250 VA
35
What is the load in VA for the general-purpose lighting load in a sq. ft beauty salon used continuously?
36
9,000 VA
37
What is the demand on the main service entrance in VA for a 11 kW range?
38
8,000 VA
39
What size THWN copper conductors are required to supply the secondary load of a transformer having a continuous load output of 212 amps? All terminations are rated at 90 degrees C.
40
300 kCMIL
41
What is the general lighting load and receptacle load and small-appliance plus laundry loads for a sq. Ft dwelling unit? (Calculate the load in VA)
42
6,675 VA
43
What is the maximum size nontime-delay fuse allowed for branch circuit, short circuit protection for a 40 HP, three-phase, 460 volt, Design B motor?
44
175 Amp
45
What is the demand on the main service of a dwelling unit for a 1
What is the demand on the main service of a dwelling unit for a 1.2 kW garbage disposal, a 3.2 kW water heater and a 2.1 kW dishwasher? None of the appliances are cord and plug connected.
46
6500 VA
47
What is the general lighting demand and receptacle demand and small-appliance plus laundry loads on the service entrance for a sq. ft dwelling unit? (Calculate the load in VA)
48
10,140 VA
49
What is the minimum volume allowance required in a plastic box for a duplex receptacle and (3) 14/2 NM cables?
50
12
51
What is the general lighting load and receptacle load and small-appliance plus laundry load for sq. ft dwelling units in a complex? (Calculate the load in VA)
52
45,225 VA
53
What is minimum sized EMT which can be used for the installation of (4) 6 THHN, (3) 2 TW and (1) 12 THHN conductors?
54
1 ½ Inch
55
What is the general lighting demand and receptacle demand and small-appliance plus laundry in a multifamily dwelling unit with the following area? (Calculate the load in VA) sq. ft dwelling units sq. ft dwelling units sq. ft dwelling units
56
69,037.5 VA
57
What is the demand in VA for the general- purpose lighting load and core receptacle demand in a 7000 sq. ft office facility?
58
24,500 VA
59
What is the load in VA for a 208 volt, three- phase, 68 amp load operating for six hours and supplied by an individual branch circuit?
60
30,622 VA
61
What is the maximum size instantaneous trip breaker allowed for branch circuit, short circuit protection for a 20 HP, three-phase, 230 volt, Design A motor?
62
450 Amp
63
What is the minimum rating of an overload device required for a 5 horsepower, single phase, 208V motor with a marked service factor of 1.15 and a full load current of amperes?
64
28.25 amps
65
What is the load in VA for the general-purpose lighting load in a sq. ft bank used continuously?
66
29,750 VA
67
What is the load in VA for the general- purpose lighting load in a school building with the following area: (Calculate at continuous operation) 20,000 sq. ft classroom area 5000 sq. ft auditorium area
68
81,250 VA
69
What is the minimum sized THHN conductor that can be used between the controller and the motor for a 15 HP, three phase, 208V, wye start, delta run connected motor that has a nameplate rating of amperes, a marked service factor of 1.15 if all equipment is rated at 90 degrees C?
70
10 AWG
71
What is the demand load in VA for three pieces of cooking equipment with a 10 kW, 14 kW, and 16 kW rating installed in a dwelling unit?
72
15,400 VA
73
What is the demand load in VA and amps for 15, 208 volt, single phase cooking units rated 10 kW each on a three phase service?
74
37,500 VA
75
What is the minimum ampacity required for the secondary conductors of a transformer which are 23 feet in length when protected by a 300 amp overcurrent protection device on the primary side. The transformer has a 480 volt primary and 208 volt secondary?
76
230 Amps
77
What is the demand load in VA for a 5 kW dryer?
78
5000 VA
79
What size RHW copper conductors are required to supply a feeder with a continuous load of 172 amps and a non- continuous load of 80 amps? All terminations are rated at 90 degrees C.
80
350 kCMIL
81
What minimum sized SO cord which can be used to feed a 50 ampere, three phase, 208V load?
82
Size 5
83
What is the maximum sized time delay fuse allowed for branch circuit, short circuit protection of a 20 HP, three-phase, 208 volt, Design B motor?
84
110 Amp
85
What is the load in VA for the general- purpose lighting load in a 40,000 sq. ft store if 20,000 sq. ft is warehouse space? (Used at continuous operation)
86
81,250 VA
87
What is the load in VA for 50, 120 volt, lighting ballast rated at 1
What is the load in VA for 50, 120 volt, lighting ballast rated at 1.5 amps each and used for 8 hours a day?
88
11,250 VA
89
What is the demand load in VA for 10-3 kW cooktops and 10- 8
What is the demand load in VA for kW cooktops and kW ovens installed in an apartment complex?
90
35,000 VA
91
What is the maximum sized time delay fuse which can be used to protect the feeder conductors for five, 10 HP, 480V three motors? Each motor has a name plate rating of 12.1 A, a marked service factor of 1.15, and they are design B. Each motor has a 20 Ampere time delay fuse branch circuit short circuit protection.
92
70 amps
93
What is the lighting load in VA for 140 ft of show window used at non- continuous operation?
94
28000 VA
95
A separate over load device shall be selected to trip at ____________ amperes for overload protection of a 7.5 HP, two phase, 230 V motor with a marked full load current of amperes and a marked service factor of
96
17 amps
97
What is the total current which can be carried by a 10 THHN aluminum conductor if it is installed in a conduit with a total of 8 current carrying conductors and the conduit is installed in an ambient temperature of 99 degrees F? All terminations will be rated at 90 degrees C.
98
22.3 Amps
99
What is the lighting load in VA for 100 ft of track lighting used at non-continuous operation?
100
7500 VA
101
What is the demand on the main service entrance for two cooktops with a 3 kW rating?
102
4500 VA
103
What size copper grounding electrode conductor is required to concrete encased electrode if the service conductors are four parallel runs of 500 KCMIL copper?
104
4 AWG
105
What is the lighting load in VA for the patient bedrooms in a 52,000 sq. ft hospital? Assume all loads will be used for 3 hours or more at a time.
106
13,500 VA
107
What is the demand on the main service entrance, in VA, for a 12 kW cooktop, 8 kW oven, and 4kW oven installed in a dwelling unit?
108
14,000 VA
109
What is the lighting load in VA for 15 continuous operated luminaires with a 75 VA ballast in each unit and 15 non-continuous operated luminaires with 75 VA in each unit?
110
VA
111
What is the lighting load in VA for 50 continuous operated luminaires with a 150 VA ballast in each unit?
112
9375 VA
113
What is the general lighting demand including the receptacle load and small-appliance plus laundry demand in a multifamily dwelling unit with the following area? (Calculate the load in VA and round answer to nearest whole number) sq. ft dwelling units sq. ft dwelling units sq. ft dwelling units sq. ft dwelling units
114
53,438 VA
115
What size THWN copper conductors are required to supply the secondary side of a 480V to 208V, three phase transformer having a continuous load output of 194 amps? The transformer secondary conductors will not have overcurrent protection. They are 8 feet in length. The transformer primary conductors are protected by a 90 ampere inverse time circuit breaker. The secondary conductors terminate into a 200 A main breaker for a 208V three phase panel. The secondary conductors leave the transformer enclosure. All terminations are rated for 90 degrees C.
116
3/0 THWN
117
What is the voltage drop experienced on a 6 AWG aluminum conductor which is supplying a load of 23 amperes if the load is located 116 meters from the source of power? (Round answer to the nearest whole number)
118
14 Volts
119
What is the minimum sized THHN conductor which can be used to feed eight 5 HP, thee phase motors rated at 208V and FLA, Design C and 1.15 service factor?
120
1/0 THHN
121
What is the primary line current of a 480 to 208 V three phase, delta-wye transformer if the secondary line current is 278 amperes? ( Assume 100% efficiency and round your answer to the nearest whole number.)
122
120 amps
123
What is the demand load in VA for five 10 kW and six 13 kW cooking units?
124
27,300 VA
125
What is the lighting load in VA for 203 ft
What is the lighting load in VA for 203 ft. of track lighting used at continuous operation?
126
19,125 VA
127
What is the minimum sized THHN conductor which can be used to feed five arc welders. Each arc welder has a rating of 60 duty cycle and 28 amps I1eff.
128
1/0 THHN
129
What is the demand load in VA for 28-12 kW ranges installed in an apartment complex?
130
43,000 VA
131
What is the maximum sized inverse time circuit breaker which can be used to protect from overcurrent the RHW feeder conductors which are feeding four resistance welders which are rated at 30 duty cycle and 23 amperes? The feeders are 2 AWG aluminum.
132
300 amps
133
What is the load in VA for the general- purpose lighting load in a 8400 sq. ft church used continuously?
134
10,500 VA
135
What is the demand load in VA for 12-2
What is the demand load in VA for kW ovens and a kW cooktops installed in an apartment complex? ( Give your answer in kVA)
136
20.46 kVA
137
What is the load in VA for 150 ft of multioutlet assembly used to cord-and- plug connect loads that are used simultaneously?
138
27,000 VA
139
What is the minimum sized TW conductor which can be used to feed a 2 HP, single phase, 120V motor which is rated for 15 minute running and will be used for intermittent duty? The motor is rated at FLA.
140
12 AWG
141
What is the ampacity of an XHHW aluminum, 8 AWG conductor installed in an ambient temperature of 102 degrees F? The conductor and all terminations are rated 90 degrees C.
142
39.5 amps
143
A 200 ampere, 208V single phase panel is installed for a single family dwelling. What is the minimum sized aluminum RHW conductor which can be used as a service entrance conductor?
144
4/0 RHW
145
What size copper grounding electrode conductor is required to a metal water main pipe if the service conductors are rated 350 KCMIL copper?
146
2 AWG
147
What is the demand load in VA for twenty five 15 kW ranges installed in an apartment complex?
148
46,000 VA
149
What is the maximum setting for the overload relay for a 30 HP, 480V, synchronous motor with a FLC of 26.1 amperes and a temperature rise of 40 degrees C? Assume the minimum setting has been tried and the motor will not start. Round your answer DOWN to the nearest whole number.)
150
36 amperes
151
What is the demand on the main service entrance of an apartment complex that has a single phase, 240V service for 31 dryers that have a nameplate rating of 4.3 KW? Copyright 2005 Ted "Smitty" Smith
152
48050 VA
153
What is the minimum required bending space required for four parallel runs of 250 kCMIL compact AA conductors if the conductors will enter the enclosure on the side opposite the termination lugs?
154
6.5 inches
155
A run of 4/0 THHN conductors will be ran vertically in a raceway
A run of 4/0 THHN conductors will be ran vertically in a raceway. The total vertical length of the raceway is 376 feet. What is the minimum number of conductor supports that will need to be ordered for each conductor?
156
6
157
What is the demand load in VA for a 4 kW dryer?
158
5000 VA
159
What size copper equipment grounding conductor is required to ground to be ran with the ungrounded 4 THHN conductors feeding a piece of equipment which pulls a load of 18.2 amps. The conductors are fed by a 20 ampere circuit breaker? The ungrounded conductors in the circuit are size 4 THHN.
160
4 AWG
161
What is the fixed-appliance demand in VA for the ungrounded (phase) conductors with the following fastened in place appliances: 6000 VA water heater 1400 VA disposal 1050 VA compactor
162
8450 VA
163
What is the demand load in VA for 45 dryers rated at 6500 VA each?
164
73,125 VA
165
A recreational vehicle park will have ten 50A sites, fifteen 30A sites, ten 20A sites and five sites reserved for tent sites. What is the minimum demand on the main service entrance for all the sites?
166
38,130 VA
167
What is the minimum sized THHN conductor which can be used to feed a fixed storage type water heater rated at 100 gallons and amperes?
168
6 AWG
169
What is the load in VA for 148 general- purpose duplex receptacles used to serve non- continuous operated loads in an office building?
170
36640 VA
171
What is the minimum number of 120V, 20 A circuits which can be used to feed 145 ft of multioutlet assembly used to cord-and-plug connect loads that are not used simultaneously? The assembly will have a duplex receptacle mounted every 12 inches.
172
3
173
What is the demand load in VA and amps for 15, 208 volt, single-phase cooking units rated 9 kW each?
174
30,000 VA
175
What is the demand in VA for a group of 208 volt, three-phase motors rated at 30 HP, 20 HP, and 10 HP? ( Assume these are the only motor loads on the service.) Round your answer to the nearest whole number.
176
69,035 VA
177
What minimum sized copper bonding jumper is required on the line side of a service if the service conductors are five parallel runs of 500 kCMIL copper?
178
350 kCMIL
179
Stop This is the end of the presentation.
You can now review the slides and answers without the timer. Click the slide to advance to the next slide
180
What is the minimum sized THHN conductor that can be used for conductors between the controller and the motor of a part winding connected, 5 HP, single phase, 208 volt motor that has a nameplate rating of amperes? All equipment has a 75 degree C temperature rating.
181
14 AWG
182
What is the demand on the main service entrance of an apartment complex that has a three phase, 480V service for 10 single phase, 208V ranges that have a nameplate rating of 14.2 kW?
183
37,950 VA
184
What size copper bonding jumper is required for the load side of a service if the service conductors are 4/0 copper and the main breaker is 200 amperes?
185
6 AWG
186
What is the maximum size inverse-time circuit breaker allowed for a 30 HP, three-phase, 208 volt, Design B motor for branch circuit, short circuit protection?
187
225 Amp
188
What is the demand on the main service entrance of a restaurant that has the following kitchen equipment? (3) Booster heaters for dishwashing equipment rated at 3.9 kW each (2) Deep fryers rated at 5.9 kW each (2) Electric grills rated at 11.2 kW each (1) Warming table rated at 2.9 kW
189
31.72 kVA
190
What is the minimum sized service that can be used for an office building that has a 480V, three phase service if the total calculated demand on the service is VA?
191
1000 Amp
192
What is the minimum circular mill rating for the feeder conductors that are run 100 ft from the service to an 84 amp calculated load supplied by 240 volt, three-wire system with a voltage drop of 3 percent applied? (CM is based on VD calculation)
193
30,100 CM
194
What size THWN copper conductors are required to supply a load on the secondary side of a transformer if the load is a continuous load of 50 amps and non-continuous load of 20 amps?
195
3 AWG
196
Calculate at continuous operation
What is the load in VA for the following luminaires: VA (each) recess luminaires VA (each) incandescent luminaires VA (each) electric discharge luminaires Calculate at continuous operation
197
VA
198
What size copper grounding electrode conductor is required to a ground rod if the service conductors are rated 250 KCMIL copper?
199
6 AWG
200
What is the demand load in VA for 55-11 kW ranges installed in an apartment complex?
201
66,250 VA
202
What is the lighting load in VA for 140 ft of show window used at continuous operation?
203
35,000 VA
204
What is the general lighting load and receptacle load and small-appliance plus laundry load for sq. ft dwelling units in a complex? (Calculate the load in VA)
205
51,150 VA
206
What is the demand load in VA for a range with a 16 kW rating?
207
9,600 VA
208
What is the load in VA for the general-purpose lighting load in a hotel or motel with 50 units of 420 sq. ft each?
209
18,800 VA
210
What is the demand on the main service entrance for 23- 4
What is the demand on the main service entrance for kW rated electric dryers?
211
40,250 VA
212
What is the load in VA for the general-purpose lighting load in a sq. ft beauty salon used continuously?
213
9,000 VA
214
What is the demand on the main service entrance in VA for a 11 kW range?
215
8,000 VA
216
What size THWN copper conductors are required to supply the secondary load of a transformer having a continuous load output of 212 amps? All terminations are rated at 90 degrees C.
217
300 kCMIL
218
What is the general lighting load and receptacle load and small-appliance plus laundry loads for a sq. Ft dwelling unit? (Calculate the load in VA)
219
6,675 VA
220
What is the maximum size nontime-delay fuse allowed for branch circuit, short circuit protection for a 40 HP, three-phase, 460 volt, Design B motor?
221
175 Amp
222
What is the demand on the main service of a dwelling unit for a 1
What is the demand on the main service of a dwelling unit for a 1.2 kW garbage disposal, a 3.2 kW water heater and a 2.1 kW dishwasher? None of the appliances are cord and plug connected.
223
6500 VA
224
What is the general lighting demand and receptacle demand and small-appliance plus laundry loads on the service entrance for a sq. ft dwelling unit? (Calculate the load in VA)
225
10,140 VA
226
What is the minimum volume allowance required in a plastic box for a duplex receptacle and (3) 14/2 NM cables?
227
12
228
What is the general lighting load and receptacle load and small-appliance plus laundry load for sq. ft dwelling units in a complex? (Calculate the load in VA)
229
45,225 VA
230
What is minimum sized EMT which can be used for the installation of (4) 6 THHN, (3) 2 TW and (1) 12 THHN conductors?
231
1 ½ Inch
232
What is the general lighting demand and receptacle demand and small-appliance plus laundry in a multifamily dwelling unit with the following area? (Calculate the load in VA) sq. ft dwelling units sq. ft dwelling units sq. ft dwelling units
233
69,037.5 VA
234
What is the demand in VA for the general- purpose lighting load and core receptacle demand in a 7000 sq. ft office facility?
235
24,500 VA
236
What is the load in VA for a 208 volt, three- phase, 68 amp load operating for six hours and supplied by an individual branch circuit?
237
30,622 VA
238
What is the maximum size instantaneous trip breaker allowed for branch circuit, short circuit protection for a 20 HP, three-phase, 230 volt, Design A motor?
239
450 Amp
240
What is the minimum rating of an overload device required for a 5 horsepower, single phase, 208V motor with a marked service factor of 1.15 and a full load current of amperes?
241
28.25 amps
242
What is the load in VA for the general-purpose lighting load in a sq. ft bank used continuously?
243
29,750 VA
244
What is the load in VA for the general- purpose lighting load in a school building with the following area: (Calculate at continuous operation) 20,000 sq. ft classroom area 5000 sq. ft auditorium area
245
81,250 VA
246
What is the minimum sized THHN conductor that can be used between the controller and the motor for a 15 HP, three phase, 208V, wye start, delta run connected motor that has a nameplate rating of amperes, a marked service factor of 1.15 if all equipment is rated at 90 degrees C?
247
10 AWG
248
What is the demand load in VA for three pieces of cooking equipment with a 10 kW, 14 kW, and 16 kW rating installed in a dwelling unit?
249
15,400 VA
250
What is the demand load in VA and amps for 15, 208 volt, single phase cooking units rated 10 kW each on a three phase service?
251
37,500 VA
252
What is the minimum ampacity required for the secondary conductors of a transformer which are 23 feet in length when protected by a 300 amp overcurrent protection device on the primary side. The transformer has a 480 volt primary and 208 volt secondary?
253
230 Amps
254
What is the demand load in VA for a 5 kW dryer?
255
5000 VA
256
What size RHW copper conductors are required to supply a feeder with a continuous load of 172 amps and a non- continuous load of 80 amps? All terminations are rated at 90 degrees C.
257
350 kCMIL
258
What minimum sized SO cord which can be used to feed a 50 ampere, three phase, 208V load?
259
Size 5
260
What is the maximum sized time delay fuse allowed for branch circuit, short circuit protection of a 20 HP, three-phase, 208 volt, Design B motor?
261
110 Amp
262
What is the load in VA for the general- purpose lighting load in a 40,000 sq. ft store if 20,000 sq. ft is warehouse space? (Used at continuous operation)
263
81,250 VA
264
What is the load in VA for 50, 120 volt, lighting ballast rated at 1
What is the load in VA for 50, 120 volt, lighting ballast rated at 1.5 amps each and used for 8 hours a day?
265
11,250 VA
266
What is the demand load in VA for 10-3 kW cooktops and 10- 8
What is the demand load in VA for kW cooktops and kW ovens installed in an apartment complex?
267
35,000 VA
268
What is the maximum sized time delay fuse which can be used to protect the feeder conductors for five, 10 HP, 480V three motors? Each motor has a name plate rating of 12.1 A, a marked service factor of 1.15, and they are design B. Each motor has a 20 Ampere time delay fuse branch circuit short circuit protection.
269
70 amps
270
What is the lighting load in VA for 140 ft of show window used at non- continuous operation?
271
28000 VA
272
A separate over load device shall be selected to trip at ____________ amperes for overload protection of a 7.5 HP, two phase, 230 V motor with a marked full load current of amperes and a marked service factor of
273
17 amps
274
What is the total current which can be carried by a 10 THHN aluminum conductor if it is installed in a conduit with a total of 8 current carrying conductors and the conduit is installed in an ambient temperature of 99 degrees F? All terminations will be rated at 90 degrees C.
275
22.3 Amps
276
What is the lighting load in VA for 100 ft of track lighting used at non-continuous operation?
277
7500 VA
278
What is the demand on the main service entrance for two cooktops with a 3 kW rating?
279
4500 VA
280
What size copper grounding electrode conductor is required to concrete encased electrode if the service conductors are four parallel runs of 500 KCMIL copper?
281
4 AWG
282
What is the lighting load in VA for the patient bedrooms in a 52,000 sq. ft hospital? Assume all loads will be used for 3 hours or more at a time.
283
13,500 VA
284
What is the demand on the main service entrance, in VA, for a 12 kW cooktop, 8 kW oven, and 4kW oven installed in a dwelling unit?
285
14,000 VA
286
What is the lighting load in VA for 15 continuous operated luminaires with a 75 VA ballast in each unit and 15 non-continuous operated luminaires with 75 VA in each unit?
287
VA
288
What is the lighting load in VA for 50 continuous operated luminaires with a 150 VA ballast in each unit?
289
9375 VA
290
What is the general lighting demand including the receptacle load and small-appliance plus laundry demand in a multifamily dwelling unit with the following area? (Calculate the load in VA and round answer to nearest whole number) sq. ft dwelling units sq. ft dwelling units sq. ft dwelling units sq. ft dwelling units
291
53,438 VA
292
What size THWN copper conductors are required to supply the secondary side of a 480V to 208V, three phase transformer having a continuous load output of 194 amps? The transformer secondary conductors will not have overcurrent protection. They are 8 feet in length. The transformer primary conductors are protected by a 90 ampere inverse time circuit breaker. The secondary conductors terminate into a 200 A main breaker for a 208V three phase panel. The secondary conductors leave the transformer enclosure. All terminations are rated for 90 degrees C.
293
3/0 THWN
294
What is the voltage drop experienced on a 6 AWG aluminum conductor which is supplying a load of 23 amperes if the load is located 116 meters from the source of power? (Round answer to the nearest whole number)
295
14 Volts
296
What is the minimum sized THHN conductor which can be used to feed eight 5 HP, thee phase motors rated at 208V and FLA, Design C and 1.15 service factor?
297
1/0 THHN
298
What is the primary line current of a 480 to 208 V three phase, delta-wye transformer if the secondary line current is 278 amperes? ( Assume 100% efficiency and round your answer to the nearest whole number.)
299
120 amps
300
What is the demand load in VA for five 10 kW and six 13 kW cooking units?
301
27,300 VA
302
What is the lighting load in VA for 203 ft
What is the lighting load in VA for 203 ft. of track lighting used at continuous operation?
303
19,125 VA
304
What is the minimum sized THHN conductor which can be used to feed five arc welders. Each arc welder has a rating of 60 duty cycle and 28 amps I1eff.
305
1/0 THHN
306
What is the demand load in VA for 28-12 kW ranges installed in an apartment complex?
307
43,000 VA
308
What is the maximum sized inverse time circuit breaker which can be used to protect from overcurrent the RHW feeder conductors which are feeding four resistance welders which are rated at 30 duty cycle and 23 amperes? The feeders are 2 AWG aluminum.
309
300 amps
310
What is the load in VA for the general- purpose lighting load in a 8400 sq. ft church used continuously?
311
10,500 VA
312
What is the demand load in VA for 12-2
What is the demand load in VA for kW ovens and a kW cooktops installed in an apartment complex? ( Give your answer in kVA)
313
20.46 kVA
314
What is the load in VA for 150 ft of multioutlet assembly used to cord-and- plug connect loads that are used simultaneously?
315
27,000 VA
316
What is the minimum sized TW conductor which can be used to feed a 2 HP, single phase, 120V motor which is rated for 15 minute running and will be used for intermittent duty? The motor is rated at FLA.
317
12 AWG
318
What is the ampacity of an XHHW aluminum, 8 AWG conductor installed in an ambient temperature of 102 degrees F? The conductor and all terminations are rated 90 degrees C.
319
39.5 amps
320
A 200 ampere, 208V single phase panel is installed for a single family dwelling. What is the minimum sized aluminum RHW conductor which can be used as a service entrance conductor?
321
4/0 RHW
322
What size copper grounding electrode conductor is required to a metal water main pipe if the service conductors are rated 350 KCMIL copper?
323
2 AWG
324
What is the demand load in VA for twenty five 15 kW ranges installed in an apartment complex?
325
46,000 VA
326
What is the maximum setting for the overload relay for a 30 HP, 480V, synchronous motor with a FLC of 26.1 amperes and a temperature rise of 40 degrees C? Assume the minimum setting has been tried and the motor will not start. Round your answer DOWN to the nearest whole number.)
327
36 amperes
328
What is the demand on the main service entrance of an apartment complex that has a single phase, 240V service for 31 dryers that have a nameplate rating of 4.3 KW? Copyright 2005 Ted "Smitty" Smith
329
48050 VA
330
What is the minimum required bending space required for four parallel runs of 250 kCMIL compact AA conductors if the conductors will enter the enclosure on the side opposite the termination lugs?
331
6.5 inches
332
A run of 4/0 THHN conductors will be ran vertically in a raceway
A run of 4/0 THHN conductors will be ran vertically in a raceway. The total vertical length of the raceway is 376 feet. What is the minimum number of conductor supports that will need to be ordered for each conductor?
333
6
334
What is the demand load in VA for a 4 kW dryer?
335
5000 VA
336
What size copper equipment grounding conductor is required to ground to be ran with the ungrounded 4 THHN conductors feeding a piece of equipment which pulls a load of 18.2 amps. The conductors are fed by a 20 ampere circuit breaker? The ungrounded conductors in the circuit are size 4 THHN.
337
4 AWG
338
What is the fixed-appliance demand in VA for the ungrounded (phase) conductors with the following fastened in place appliances: 6000 VA water heater 1400 VA disposal 1050 VA compactor
339
8450 VA
340
What is the demand load in VA for 45 dryers rated at 6500 VA each?
341
73,125 VA
342
A recreational vehicle park will have ten 50A sites, fifteen 30A sites, ten 20A sites and five sites reserved for tent sites. What is the minimum demand on the main service entrance for all the sites?
343
38,130 VA
344
What is the minimum sized THHN conductor which can be used to feed a fixed storage type water heater rated at 100 gallons and amperes?
345
6 AWG
346
What is the load in VA for 148 general- purpose duplex receptacles used to serve non- continuous operated loads in an office building?
347
36640 VA
348
What is the minimum number of 120V, 20 A circuits which can be used to feed 145 ft of multioutlet assembly used to cord-and-plug connect loads that are not used simultaneously? The assembly will have a duplex receptacle mounted every 12 inches.
349
3
350
What is the demand load in VA and amps for 15, 208 volt, single-phase cooking units rated 9 kW each?
351
30,000 VA
352
What is the demand in VA for a group of 208 volt, three-phase motors rated at 30 HP, 20 HP, and 10 HP? ( Assume these are the only motor loads on the service.) Round your answer to the nearest whole number.
353
69,035 VA
354
What minimum sized copper bonding jumper is required on the line side of a service if the service conductors are five parallel runs of 500 kCMIL copper?
355
350 kCMIL