Risk Management State Electrical Division 2017 State Electrical Code Grounding Electrodes For Single Family Dwellings

2 Notice: The following illustrations are approved by the State Electrical Division of the North Carolina Department of Insurance, Office of State Fire Marshal. These illustrations are intended to demonstrate but not supersede the official written interpretations found at the following web address: Joseph Starling Chief State Electrical Engineer & Inspector Illustrated by: Danny Thomas State Electrical Inspector

3 Only one? Or two? Date: June 12, 2018 2017 Electrical Code
Acme Meter Subject: Grounding Electrodes for Single Family Dwellings Section (A)(2) and (D)(2) Question 1: If only ground rods are used as an electrode system for a single family dwelling, are two required? Only one? Or two?

4 250.53(A)(3) requires rods to be located a minimum of 6 feet apart
Date: June 12, 2018 2017 Electrical Code Subject: Grounding Electrodes for Single Family Dwellings Acme Meter Section (A)(2) and (D)(2) 250.53(A)(3) requires rods to be located a minimum of 6 feet apart (If the GEC is not continuous then 2 clamps may be required) If more than 25 ohms then rod is required to be supplemented 25 ohms or less only one rod required 250.53(A)(2) Exception However, the installer is required to assure this system meets this requirement and submit proof that is acceptable to the local electrical inspector Minimum 6 feet apart

5 Subject: Grounding Electrodes for Single Family Dwellings
Date: June 12, 2018 2017 Electrical Code Metal Water Pipe Subject: Grounding Electrodes for Single Family Dwellings Section (A)(2) and (D)(2) Question 2: If a metal underground water pipe is used as part of an electrode system and is supplemented with a ground rod, is another grounding electrode required to supplement the ground rod?

6 Date: June 12, 2018 2017 Electrical Code Subject: Grounding Electrodes for Single Family Dwellings Section (A)(2) and (D)(2) Answer 2: No. The requirement of section (D)(2) requires one supplement electrode of a type chosen from sections (A)(2) – (A)(8), in which a rod is listed in section (A)(5). Both the water pipe and the rod must comply with the installation requirements of section (A). Because the water pipe and the rod make two electrodes, each supplement the other, thus (A)(2) is satisfied.

7 Connection must be made within first 5 feet 250.68(C)(1)
METAL WATER PIPE Connection must be made within first 5 feet 250.68(C)(1) (Unless permitted otherwise by exception) Only one rod required as supplement for metal water pipe 250.53(D)(2) METAL WATER PIPE ELECTRODE Permitted if 10 feet or more in direct contact with the earth 250.52(A)(1)