Secondary Gas Insulated Switchgear

Similar presentations


Presentation on theme: "Secondary Gas Insulated Switchgear"— Presentation transcript:

1 Secondary Gas Insulated Switchgear
SafeLink CB 12kV SGIS

2 SafeLink CB Contents Ring Distribution & Secondary Network
SGIS Application Operating Conditions SafeLink CB Portfolio, Parameters & Dimensions & Variations Product Safety Cable Termination & Extension Protection, Indication & Measurements Digital (Smart Secondary Switchgear) Manufacturing Facility End-of-life & Environmental Certification

3 Ring Distribution System
SafeLink CB Ring Distribution System Concept & Advantages In the event of fault in Underground Network, appropriate measures are required for quick fault location and isolation. Unlike Radial distribution system for system redundancy, Ring Topology of using RMU can still reduce downtime equally & still remain economical. Ring Main Units are deployed in a manner, that every load centre in the loop has an alternative source of supply available. In the event of fault, the faulty section can be isolated within minutes and supply to affected load centers can be resumed with alternative source. Detailed Simulation follows…… RING SWITCH T-OFF SWITCH Load Centre Back to Contents

4 Secondary Distribution
SafeLink CB 400 kV Secondary Distribution Transmission substation Thermal Hydro Transformer 130 kV Renewables Infrastructure 40-70 kV Main substation 400 V Distribution substation 36kV - 24kV – 12kV Secondary substation Industry Back to Contents

5 Ring Distribution System – Normal Condition
SafeLink CB Ring Distribution System – Normal Condition 33/11kV 33/11kV Normally Open Points Local Receiving Stn. Local Receiving Stn. Back to Contents

6 Ring Distribution System - Faulty Condition
SafeLink CB Ring Distribution System - Faulty Condition FPI’s Indicate path of fault current 33/11kV 33/11kV Local Receiving Stn. Normally Open point is closed Local Receiving Stn. Faulty Section is Isolated Fault Appears in System Grid Blackout! Back to Contents

7 Ring Distribution System – Restored Condition
SafeLink CB Ring Distribution System – Restored Condition 33/11kV 33/11kV Local Receiving Stn. Local Receiving Stn. Supply to Load Centers is Resumed! Back to Contents

8 Secondary Distribution
SafeLink CB Secondary Distribution Back to Contents

9 SafeLink CB Application Packages Back to Contents Renewables Solar
Wind Industry Oil & Gas Textile & Automotive Cement & Glass Utility Power distribution utility Infrastructure & Transport SMART City & Industrial Corridors Military Engineering Services Metro & Railways Back to Contents

10 SafeLink CB Operating Conditions Operating Conditions Back to Contents
Normal operation conditions The rated characteristics of the switchgear are valid under the following ambient conditions: minimum ambient temperature: – 25 °C maximum ambient temperature: + 40 °C Ambient humidity maximum 24 h average of relative humidity 95% maximum 24 h average of water vapour pressure 2.2 kPa maximum monthly average of relative humidity 90% RH maximum monthly average of water vapour pressure 1.8 kPa Altitude Upto 1000 metres above sea level Corrosion Class C3 for Indoor & C2 for Outdoor For different temperature ranges, higher altitudes, special corrosion class please contact ABB sales representative. Back to Contents

11 SGIS Product Evolution
SafeLink CB SGIS Product Evolution Well proven technology Years of experience Global Product Portfolio Global Customer References 36kV 24kV 12kV 1985 Norway Plant 2003 Nasik Plant 2004 2011 2014 2018 Back to Contents

12 SGIS Product Portfolio
SafeLink CB SGIS Product Portfolio Product Family SafeRing / SafePlus 2004 Indoor 12/24kV SafeLink CB 2011 Outdoor 12kV SafeRing / SafePlus 2006 Outdoor 12/24kV SafeRing 36 / SafePlus 36 2014 Indoor/Outdoor 36kV Back to Contents

13 SGIS Product Portfolio
SafeLink CB SGIS Product Portfolio SafeRing/SafePlus SafeLink CB SafeRing 36 / SafePlus 36 Indoor Outdoor Rated Voltage (kV) 12/24 12 36 Rated Current (A) 630 STC (kA/s) 21/3 25/1 Breaking Capacity (kA) 21/16 21 25 Mechanical Endurance (LBS) M1 (1000) Mechanical Endurance (VCB) M1 (2000) M1 (2000) (M2 optional) Electrical Endurance (LBS) E3 Electrical Endurance (VCB) E2 E1 IAC Classification AFLR 20kA/1s AFLR 21kA/1s AFL 21kA/1s* AFLR 25kA/1s** * - AFL 21kA/1s for Tank & AFLR 10kA/0.1s for Cable Box. Higher values available on request ** - AFLR 25kA/1s for Indoor SafeRing 36 / SafePlus 36 Back to Contents

14 SafeLink CB Product Portfolio SafeLink CB Back to Contents
C / V / D Switching / Protection Modular Design Extremely Compact Switchgear CVC, VC, VD, V, C Extensibility on both sides 3 modules in single tank (Any combination) Motorisation/Battery back-up Versatile Bus Metering Solutions with CT/PT Integral LV Box on top of RMU Mechanism Back to Contents

15 SafeLink CB Technical Parameters
Product Portfolio SafeLink CB SafeLink CB Technical Parameters Rated Voltage 12kV Power Frequency Withstand Voltage 38kVp Impulse Withstand Voltage 95kVp Frequency 50Hz Rated Current (RMU) 630A Rated Current (Ring Switch) Rated Current (VCB) Short Circuit Making Current (for 12kV) 52.5kA Short Circuit Breaking Current (VCB) 21kA Short Time Current (for 3s) Main Circuit Peak Withstand Current Main Circuit Short Time Current (for 3s) Earthing Switch Short Time Current (for 1s) Earthing Circuit Short Circuit Making Current (ES) Minimum Operating Pressure 1.2 bar Mechanical Endurance (Ring Switch) M1 Mechanical Endurance (Earth Switch) M0 Electrical Endurance (Ring Switch) E3 Electrical Endurance (Earthing Switch) E2 Mechanical Endurance (VCB) M1* Electrical Endurance (VCB) IAC Classification Tank – AFL 21kA/1s Cable Compartment – AFLR 10kA/0.1s Cable Compartment – AF 21kA/1s (optional) Optional Test Point Bushing Robotic Welding of SS304 Grade Tank 2.5mm Standard thickness for Tank 2mm Standard thickness for Enclosure IP 54 for Enclosure Site Replaceable Cable Bushing Compatible to Digital Upgrade (Details Follows) *M2 optionally available Back to Contents

16 SafeLink CB Design Philosophy SafeLink CB Back to Contents
Compact and Robust Design Simulations application for design validations Personnel safety considerations Modern development and manufacturing techniques Durability and recyclable for environment Back to Contents

17 SafeLink CB Variations V C C SafeLink CB Back to Contents
Non-extensible configurations Extensible configurations – on either sides & both sides 3way configuration CVC 2way configuration VC-VD-DC 1way configuration V-C With & Without Test Point Bushings Vertical & Horizontal Door Cable Compartment 10kA IAC version & 21kA IAC version PEX on either sides for future extensbility SafeLink CB for CSS version C C Back to Contents

18 SafeLink CB Design Philosophy C Module Back to Contents
3 position switch disconnector and earthing switch SF6 as arc quenching and insulating medium Cable Test Point Bushings on bottom of the tank (standard) Single spring latched mechanism for all 3 positions of ON-OFF-EARTH Cable compartments and Test Point compartments interlocked Busbar extension bushing Back to Contents

19 SafeLink CB Design Philosophy V Module Back to Contents
VG5 interrupter from ABB Interruption in vacuum Insulation provided by gas No consumable parts Rugged and reliable 10000 mechanical endurance operations 30000 operations of VI at rated current Three position disconnector and earthing switch Back to Contents

20 SafeLink CB Design Philosophy SF6 Gas Tank Back to Contents
Vacuum BKR aligned to T-off side with cable bushings on back side Switch cable bushings on the left & right sides Mechanisms for Circuit Breaker and Cable Switch on front Disconnector manually operated Test Point Bushings in the bottom of the tank Back to Contents

21 SafeLink CB Description Product Description Back to Contents
Rating Plate Manometer Front Upper Mimic Relay VCB Disconnector Padlock Fault Indicator VPIS for Ring Switch RHS Ring Switch RHS Cable Box for Ring Switch RHS Test Point Box for Ring Switch RHS Switchgear Stand Earth & Circuit Slider for Ring Switch VCB Disconnector Operating Handle Door Handle Padlocking for Switchgear Front Door Switchgear Front Door Gas Spring for Switchgear Front Door Switchgear Earthing T-Off Cable Box (For VCB) Current Transformer (Directly mounted on VCB Bushings) Lifting Hook for Switchgear End Box (For extensible version only) ‘V’ module section ‘C’ module section Back to Contents

22 SafeLink CB Dimensions Back to Contents Bushing C-C 100 mm Front Door
1830 1210 960 Bushing C-C 105 mm 2020 1540 1320 Bushing C-C 100 mm 826 Front Door Open View Back View Back to Contents

23 Dimensions (CVC Non Extensible)
SafeLink CB Dimensions (CVC Non Extensible) Back to Contents

24 Dimensions (+CVC+ Both Sides Extensible)
SafeLink CB Dimensions (+CVC+ Both Sides Extensible) Back to Contents

25 Dimensions (+V+ Both Sides Extensible)
SafeLink CB Dimensions (+V+ Both Sides Extensible) Back to Contents

26 Dimensions (+C+ Both Sides Extensible)
SafeLink CB Dimensions (+C+ Both Sides Extensible) Back to Contents

27 Dimensions (CVC Non Extensible 21kA IAC cable box)
SafeLink CB Dimensions (CVC Non Extensible 21kA IAC cable box) Back to Contents

28 Dimensions (Foundation/Coupling)
SafeLink CB Dimensions (Foundation/Coupling) Back to Contents

29 SafeLink CB Product Portfolio SafeLink CB Back to Contents
V+M ICOG Solution Factory fitted solution Extremely Compact Switchgear Optional Extensibility on left side Motorisation/Battery back-up Versatile Bus Metering Solutions with CT/PT Integral LV Box below Switchgear & Metering Single Base Frame for ease in erection Tested as per IEC , IEC , IEC Back to Contents

30 SafeLink CB Product Portfolio SafeLink CB Back to Contents
CVC+VC+, CVC+CVC+, CVC+V+, CVC+C+ Factory fitted coupled solution for 4way, 5way Optional Extensibility on both sides Motorisation/Battery back-up Versatile Bus Metering Solutions with CT/PT Integral LV Box on top of RMU Mechanism Single Base Frame for ease in erection SCADA Integrated as per latest IPDS specification FRTU/PLC with Modem factory integrated Ready for communication with different protocols Back to Contents

31 SafeLink CB Product Portfolio SafeLink CB Back to Contents CVC Digital
Factory fitted digital solution Optional Extensibility on both sides Motorisation/Battery back-up Versatile Bus Metering Solutions with CT/PT Integral LV Box on side/top of RMU Mechanism Single Base Frame for ease in erection SCADA Integrated as per Middle East specification FRTU/PLC with Modem factory integrated Ready for communication with different protocols Back to Contents

32 SafeLink CB Product Portfolio SafeLink CB Back to Contents
Trafo Coupled Easy fitting in compact CSS Optional Extensibility on both sides Motorisation/Battery back-up Integral LV Box on top of RMU Mechanism SCADA Integrated / Compatible Back to Contents

33 SafeLink CB Product Safety Internal Arc Classification
Tank : AFL 21kA/1s Cable Compartment : AFLR 10kA/0.1s Tank : AFL 21kA/1s Cable Compartment : AF 21kA/1s Back to Contents

34 Interlocks & Padlocks SafeLink CB
Product Safety Interlocks & Padlocks SafeLink CB Vacuum Circuit Breaker Ring Switch 1 Interlock Type Operation Condition Comment Mechanical Interlock - C Module Closing LBS ES is open, Cable Door is closed Standard Interlock Opening LBS ES is open Mechanical Interlock - C, V Modules Closing ES LBS/Disconnector is open Opening ES Opening Cable Door ES is closed Mechanical Interlock - V Module Closing CB No interlock Opening CB Closing Disconnector CB is open, ES is open, Cable Door is closed Opening Disconnector CB is open, ES is open Electrical Interlock Closing/Opening - LBS/VCB As per customer request Optional Padlock Closing/Opening - LBS/DS/ES/VCB Only provision Ring Switch 2 Disconnector Ring Switch 1 & 2 Back to Contents

35 Cable Termination & Extensibility
SafeLink CB Cable Termination & Extensibility Cable Termination Interface C (400 series) with M16 metric threads Standard for C, F, V, D, De Modules including extensibility Standard till 630A For 12kV, terminal protector shall be provided as standard For 24kV/36kV, termination kits shall be provided upto request. For more information on cable termination details, respective catalogues/O&M Manuals shall be referred Back to Contents

36 SafeLink CB Extensibility Extensibility Back to Contents
Optional extensibility on both sides Coupling at site to existing RMU without cable disconnection Detailed Coupling Instructions available for more information Back to Contents

37 Protection, Indication & Measurement Solutions
SafeLink CB Protection, Indication & Measurement Solutions Protection/Indication Measurements/Metering Self Powered OC+EF Relays Auxiliary Powered Feeder Protection Relays Feeder IEDs Voltage Indicators (Signalling contact optional) SC+EF Indicators Bus Metering solutions available Indoor/Outdoor Metering CT/PT as per site requirements/specification SCADA Integrated metering solutions on offer For more details, please contact ABB Sales representative Back to Contents

38 Manufacturing Facility
SGIS Plant as selected as “Best in Class shop floor” by CNBC Info media TV18, industrial magazine 13th Anniversary SafeLink CB Manufacturing Facility State-of-Art SGIS Manufacturing Facility State-of-Art SGIS Plant in Nashik, Maharashtra, India Robotic Welding Station (ABB Robots) SCADA Automated Helium Leak Check SF6 Filling Unit Single Piece Feed Line for Tank & Finish Ergonomically designed lines for worker friendly Lean Six Sigma Methodology implemented Back to Contents

39 Environment Certification
SafeLink CB Environment Certification End of Life & Environment Certification Life Expectancy of Products Products developed in compliance with IEC Design incorporates a life span of over 20 years Switchgear is gas-tight with expected leakage rate of < 0.1%/yr SF6 Gas Pressure is 1.4 bar Switchgear will maintain gas-tightness (gas-pressure >=1.3bar) throughout its designed life span. End of Life ABB committed to protection of the environment & adheres to ISO Standards ABB Obligates to facilitate end of life recycling of all ABB products No explicit requirements for how to handle discarded switchgears ABB’s recycling service is according to IEC 1634 edition 1995 section 6: «End of life of SF6 filled equipment» In particular a: «Low decomposition»: «No special action is required; non-recoverable parts can be disposed of normally according to local regulations.» Back to Contents