Download presentation
Presentation is loading. Please wait.
Published byMarianna Gray Modified over 5 years ago
1
Status of the retriggering boxes and measurements
J. Rodziewicz
2
Overview JURA3 measurements - noise coupled to the RTL from PTC when the generator is pulsing; JURA3 measurements – signals delivered to the PTC from the RTB for the pickup presence check; JURA3 measurements of the chassis potential ‘jump’ with reference to the copper base of the generator; JURA1 – MKDH pickups source signals at min and max energy; RTB output transformer saturation - test to be performed in the tunnel; Status of the RTBs; 11/18/2019 Document reference
3
Noises coupled to the RTL from the PTC MKD pulsing at 450GeV
PTC mesurements connected PTC mesurements disconnected RTL is high impedance, voltage is probed though the output transformer of the RTB by the oscilloscope (CH1); Measurement in configuration no ‘PTC meas.’ repeated at 2TeV and 4TeV,coupled noise was negligible; Repeated with the MKB RTB Proto; It has been observed that the PTC measurement outputs are coupling the noises into the RTL. In this measurements an old PTC was used. Is it critical? Noise level to be confirmed with the new PTC… CH1 – RTL voltage x1.2 ; CH2 – TRIGGERS IN 11/18/2019 Document reference
4
New RTB outputs to the PTC Summary table
For the test purpose we use a dummy PTC. The PTC outputs are loaded with 3.6kΩ PRINA is the CTs2 signal received by the PTC CPDIS is the VRD signal received by the PTC RTB input stage schematics Amp (PRINA) [V] Amp (CPDIS) [V] 450 GeV CTs2 & VRD 29 CTs2 only 2 (noise) VRD only 32 7 TeV 56 49 20 (noise) 14 (noise) 48 At the first view the observed coupling is favorable for the RTS function as it generates signal to the RTL from the pulsing generator. In principal the noise level measured at high energy is lower than the signal level at low energy. Therefore it is possible to set a fixed threshold in the PTC for the detection of a faulty pickup. SAM is deactivated during the pulse sequence of the generators. Example waveform. Signal at the RTL (CH1) and delivered by a PTC output (CH2). -> All RTB inputs are disconnected -> Generator is pulsing at 7.5 TeV
5
Chassis potential ‘jump’
The MKD generator is pulsing at 7.5TeV. New measurement was done with reference to the cooper base of the generator. Previous measurement New measurement Peak to peak 23V New measurement shows 23Vp-p Vs. 11.3Vp-p measured previously with reference to the bottom of the chassis. 11/18/2019 Document reference
6
MKDH | CTs2 450GeV Consolidated generator (JURA 1 measurements done on 05/07/2019) Trigger (Time ‘0’) is set to 2V threshold of the ‘TRIGGERS IN’ signal available at the generator front panel; 11/18/2019 Document reference
7
MKDH | VRD 450GeV Consolidated generator (JURA 1 measurements done on 05/07/2019) Trigger (Time ‘0’) is set to 2V threshold of the ‘TRIGGERS IN’ signal available at the generator front panel; 11/18/2019 Document reference
8
MKDH | CTs2 7TeV Consolidated generator (JURA 1 measurements done on 05/07/2019) Trigger (Time ‘0’) is set to 2V threshold of the ‘TRIGGERS IN’ signal available at the generator front panel; 11/18/2019 Document reference
9
MKDH | VRD 7TeV Consolidated generator (JURA 1 measurements done on 05/07/2019) Trigger (Time ‘0’) is set to 2V threshold of the ‘TRIGGERS IN’ signal available at the generator front panel; 11/18/2019 Document reference
10
MKD RTB output transformer saturation considerations –> September Test
INPUT Transformers Allowable flux: 80 uV.s First diagnostic pulses (issued by Trigger Delay) will be propagated within ~110us following the main pulse of consolidated LBDS. In order to correctly propagate the diagnostic pulses the RTL impedance should be close to the nominal. It is mandatory to ensure that the flux seen by the output transformers along the line will be below the limit given by the manufacturer. OUTPUT Transformers Allowable flux: 280 uV.s Simplified simulation gives sufficient margin, however in real system apart of the propagation delay the phases differences between generators can lead to the saturation of the output transformers. Therefore the RTL test at high energy will be highly recommended in the tunnel before the MKD RTB production launch. 11/18/2019 Document reference
11
MKB RTB status EDA-04023-V1-0 Pre-series box validated in JURA1
Production ready to be launched, but few improvements will be possibly applied to the PCBs (routing, labeling etc.) 11/18/2019 Document reference
12
MKD RTB status EDA-04101-V1-0 PCB design released
Mechanics to be prototyped 3 Prototype units pending Number of Pre-series for the test in the tunnel to be confirmed 11/18/2019 Document reference
13
Summary A unwanted coupling from the pulsing generator to the measurement link between RTB and PTC was observed. So far it is not hazardous for any of the sub-systems. MKD chassis potential voltage ‘jump’ of the pulsing generator was measured almost twice higher when referenced to the generator ‘copper base’ instead of the chassis ‘bottom’ The signals from the pickups of consolidated MKBH generator are updated and can be used for further analysis. MKD transformers matching to be confirmed in the tunnel (date to be confirmed). MKB Pre-series validated in JURA1. MKD box in prototyping. 11/18/2019 Document reference
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.