Presentation is loading. Please wait.

Presentation is loading. Please wait.

Looseness or? Bill Kilbey

Similar presentations


Presentation on theme: "Looseness or? Bill Kilbey"— Presentation transcript:

1 Looseness or? Bill Kilbey
WWTF Blower Looseness or? Bill Kilbey

2 Overall vibration increasing motor

3 Overall increasing on blower

4 Motor

5 High resolution on motor

6 2x TS/2x LF

7 1x TS Modulation of RBPF

8 Blower

9 Hi res blower inbd vert Note the sideband modulation. Caused by load or driver?

10 Bearing defects on blower?
Very close to BPFO for 6314 bearing.

11 Modulation of 4.5 Hz (.225 sec. approx.)

12 Peak List PEAK FREQUENCY PEAK ORDER NO. (CPM) VALUE VALUE The red highlight peaks are sidebands. Diff. of .076 orders (271.5 CPM/4.5 Hz) Not discrete non-synch bearing freqs.

13 Review of observations
Blower has audible beat Looseness in motor and blower High 1x TS from imbalance/misalignment Modulation on blower and motor Is it load/process related or driver (motor) related?

14 Motor closer look… Audible beat and sidebands may be related to rotor problems. Slip is .44 Hz, sidebands on motor at .88 = # of poles * slip = .44 * 2 MCSA will be performed next week.

15 Sidebands at pole pass

16 Log Scale


Download ppt "Looseness or? Bill Kilbey"

Similar presentations


Ads by Google