Welcome Herzlich Willkommen Bienvenue JUMO eTRON T data sheet
2
Digital thermostat JUMO eTRON T
Displays and controls LC display 3-digit 9-segment display, 6 mm high, with symbols for °C and °F LED K1 status indication of relay output programming increase value, select picture status at release level decrease value, select picture status at release level PL 70 / © JUMO Klaus Otto
3
Functions 1 measurement input for resistance thermometer, thermocouple, current, voltage (different hardware versions) 1 relay (changeover contact) configurable for heating and cooling function indication of min- / max-alert time delayed switch-on after power-on is adjustable configuration via device or setup program available with supply: AC 230V +10%/-15%, 48…63Hz ; AC/DC 20…53 V, 48…63Hz ; DC 12…24V +15%/-15%, AC 24V +15%/-15%, 48…63Hz PL 70 / © JUMO Klaus Otto
4
Dimensions and assembling
PL 70 / © JUMO Klaus Otto
5
Block structure JUMO eTRON T Measurement input group 1
Pt100, Pt1000 or KTY2X-6 in 2-wire circuit, configurable JUMO eTRON T Setup interface for configuration from PC Measurement input group 2 thermocouples Fe-CuNi „J, L“ or NiCr-Ni „K“, configurable or floating changeover contact 10A/250V Output Measurement input group 3 current 0(4)…20mA or LC display 3-digit display for representation of measurement and parameter Measurement input group 4 voltage 0…10 V or LED indication 1 LED for the switching status of relay K1 Supply -AC 230V +10/-15%, 48…Hz -AC 115V +10/-15%, 48…63Hz -DC 12…24V +15/-15% AC 24V+15/-15%, 48…63Hz Keys 3 keys for instrument operation PL 70 / © JUMO Klaus Otto
6
Connection PL 70 / © JUMO Klaus Otto
7
Operational concept PL 70 / © JUMO Klaus Otto
8
Assignment of user rights
Operational concept Assignment of user rights PL 70 / © JUMO Klaus Otto
9
Parameter chart PL 70 / © JUMO Klaus Otto
10
Setup program PL 70 / © JUMO Klaus Otto
11
Setup program PL 70 / © JUMO Klaus Otto
12
Order details PL 70 / © JUMO Klaus Otto
13
Main fields of application
ventilation technology heating and air conditioning technology baking ovens and chip pans solar and heat pumps transformer and storage temperature control PL 70 / © JUMO Klaus Otto
14
General benefits 10A relay (changeover contact)
Replaces an additional auxiliary relay or a contactor in many applications. 3-digit LC display with special symbols °C and °F Offers a clearly arranged display of process values and parameters. Setup program For easy configuration and storage of device data. Customized linearization via tabular function in the setup program Enables linearization via 20 supporting points by own specifications. PL 70 / © JUMO Klaus Otto