Download presentation
1
Tri-Tech Medical Inc. Medical Gas Outlets
2
Medical Gas Outlets DISS Ohmeda style Allied style Puritan style
Recessed wall DISS Recessed ceiling Surface wall Console / Headwall Ambulance / Surgical Arm
3
Common Backs Recessed/Console Ambulance/ Surgical Arm
360º swivel inlet tube 1/2” OD copper tubing Accommodates all styles of Outlet Latch Plates ETL listed Ambulance/ Surgical Arm 360º swivel inlet tube DISS or hose barb Accommodates all styles of Outlet Latch Plates ETL listed
4
DISS Outlets Frontall™ design Gangable Full faceplate color coding
5 inch centers Primary & secondary checks 360° positioning of extension tube
5
DISS Surface Outlets Frontall™ design Full faceplate color coding
Primary & secondary checks
6
Frontall™ Feature Allows routine service of both the primary and secondary check valves without removing the nameplate or gas specific portions. Very fast & easy to service Primary check cartridge
7
Repairing DISS Front Bodies
These parts would be ordered separately Cartridge (Negative and Positive gases) Primary Check Seat and Ball Check (Positive gases only) Chrome-Plated Body
8
Ohmeda Style Outlets
9
Ohmeda Style Outlets Accepts Ohmeda gas specific compatible male adaptors Gangable 5” centers Allows routine service of both the primary and secondary check valves. Full faceplate color coding
10
Ohmeda Style Surface Outlet
Accepts Ohmeda gas specific compatible male adaptors Allows routine service of both the primary and secondary check valves. Full faceplate color coding
11
Repairing Ohmeda style fronts
Remove screws Remove body and plate
12
U-clip and washer remain.
Front body and plate
13
Replace body Replace plate and screw
14
XQ1000-D Ohmeda style Front Latch Body
Can be ordered as an assembly, or in parts
15
Allied Style Outlets
16
Allied Style Outlets Accepts Allied style gas specific compatible male adapters Gangable, 5” centers Full faceplate color coding 1/2” OD copper tubing Metal back and front plates 360º swivel inlet tube
17
Allied Style Surface Outlets
Accepts Allied gas specific compatible male adapters Full faceplate color coding
18
Repairing an Allied Style Front
Remove screws Remove body and plate
19
Place body on housing and replace plate
Position o-ring and washer on new body
20
Replace Screws
21
XA1000-D Front Latch Body Can be ordered as an assembly, or in parts
22
Puritan Style Outlets
23
Puritan Style Outlets Accepts Puritan style gas specific compatible male adapters Gangable, 5” centers Full faceplate color coding 1/2” OD copper tubing Metal back and front plates 360º swivel inlet tube
24
Puritan Style Outlets Accepts Puritan gas specific compatible male adapters Full faceplate color coding
25
Repairing a Puritan Style Front
Using manual screwdriver, remove screws Remove body and small plate
26
Remove ONLY these parts
27
Screw plate back in place with Manual screwdriver.
Do not over tighten Replace parts or entire body
28
XP1000-E Puritan Latch Body
Can be ordered as an assembly or in parts
29
Console / Headwall Outlets
Available in DISS, Ohmeda, Puritan and Allied styles DISS style includes Frontall™ features Full faceplate color coding Optional trim plate available
30
Console / Headwall Outlets
31
Console / Headwall Outlets
32
Ambulance / Surgical Arm Outlets
Available in DISS and Quick Connect styles DISS and hose barb inlet connections DISS includes Frontall™ features Full faceplate color coding
33
DISS x ¼” npt outlets and DISS x hose barb outlets
34
Fairfield Rail
35
Fairfield Rail Outlets
Three different styles
36
Outlet Conversion Kits
37
Conversion Kits
38
Conversion Kit - Disassembly
39
Conversion Kits - Disassembly
40
Conversion Kits - Installation
41
Trim Plates Single gang through six gang
Large array of on center spacing Can be customized to meet your needs
42
Ohmeda to Ohmeda Conversion Kits
Available for Diamond I to Diamond III Available for Diamond II to Diamond III Easy to install Easy to service
43
Other Ohmeda Conversion Kits
Available for Melco/Foregger/Linde 9/16-18 and Chemetron/NCG to Diamond III Easy to install and service
48
NFPA 99 REQUIREMENTS FOR STATION OUTLETS/INLETS TRI-TECH PRODUCT GAS SPECIFIC YES STATION OUTLET TO HAVE PRIMARY AND SECONDARY CHECK YES STATION INLET TO HAVE PRIMARY CHECK (SECONDARY CHECK PERMITTED) YES SECONDARY VALVE TO CLOSE WHEN PRIMARY VALVE IS REMOVED YES EACH OUTLET/INLET LEGIBLY IDENTIFIED ACCORDING TO YES THREADED OUTLETS/INLETS SHALL COMPLY WITH CGA V-5 (DISS) YES STATION OUTLET/INLET COMPONENTS THAT ARE GAS SPECIFIC NOT INTERCHANGEABLE YES COPPER TUBES ON STATION OUTLETS SHALL BE 3/8 OD MIN AND LESS THAN 8 INCHES LONG YES COPPER TUBES ON STATION INLETS SHALL BE ½ OD MIN ADDITIONAL TESTING PERFORMED BY TRI-TECH INITIAL PRESSURE TEST AND FINAL TIE IN TEST REQUIRED FOR LEAKAGE AS WELL AS THE OPERATIONAL PRESSURE TEST REQUIRED FOR FLOW IS PERFORMED ON ALL STATION OUTLETS/INLETS PRIOR TO SHIPPING
49
Gas Control Panels and Gas Control Panel Conversion Kits
Tri-Tech Medical Inc. Gas Control Panels and Gas Control Panel Conversion Kits
50
Gas Control Panel Stainless steel front Self-relieving regulator
Frontall™ DISS outlet features High quality ball valve Painted steel rough-in box 2” Inlet & outlet pressure gauges
52
MIDAS REX EQUIPMENT: APPROX 5% OF TOOLS IN FIELD ARE OLDER TOOLS REQUIRING PSI CFH LPM NEW TOOLS REQUIRE PSI CFH LPM OR CFH LPM NITROGEN CONTROL PANEL MAXIMUM FLOW CAPACITY BASED ON 180 PSI INLET FLOWING TO ATMOSPHERE STATIC DEL FLOW FLOW DEL PRESS PRESSURE PSIG SCFH LPM FLOWING PSIG
53
Gas Control Panel Conversion
Converts existing panels by several major brands Same features as our regular panel Easy to install using a universal mounting plate over existing back box
54
Gas Control Panel Conversion
Existing back box
55
Gas Control Panel Conversion
Installing conversion connections
56
Gas Control Panel Conversion
Installing conversion plate
57
Gas Control Panel Conversion
Back of the front panel conversion
58
Gas Control Panel Conversion
Connecting tube
59
Gas Control Panel Conversion
Installing gas control panel
Similar presentations