Download presentation
Presentation is loading. Please wait.
Published byAnahi Chalcraft Modified over 9 years ago
1
Luiz Cheim, Lan Lin - IEEE Fall Meeting - Milwaukee 10/23/2012 IEEE C57.104 Revision (Nov 2011) TF Database Analysis TF Database Analysis Luiz Cheim and Lan Lin ABB Inc.
2
Building the Database + HQ = 521,700 records
3
Transformers Age Groups
4
Transformers Power Ratings
5
Transformers Voltage Classes
6
Transformers Oil Preservation Type
7
Reason for DGA
8
Percentiles of Hydrocarbons (all data) % ppm
9
Percentiles of CO,CO2 and TDCG (all data) % ppm
10
Percentiles of H2, C2H2 and CO vs. Age Groups % ppm
11
Percentiles of H2, C2H2 and CO vs. Voltage Class % ppm
12
Percentiles of H2, C2H2 and CO vs. Power Ratings % ppm
13
Percentiles of H2, C2H2 and CO vs. Source of Data % ppm
14
Percentiles of All Gases (Suspicious Units) % ppm
15
Percentiles of H2, C2H2 and CO vs. Power Ratings (Suspicious Units) % ppm
16
Percentiles of H2, C2H2 and CO vs. Voltage Class (Suspicious Units) % ppm
17
Percentiles of H2, C2H2 and CO vs. Oil Preservation % ppm
18
Annual Rate of Gas Formation (ppm/year) Percentiles of All Gases % ppm
19
After that… 1. HQ Data incorporated 2. Discussed unknown oil preservation system 3. Question of Rate of Gas Formation vs Levels
20
Montreal Meeting (May 2o12) Revisited Percentiles with Following Condition: O2/ (N2 + O2) 70,000 => N2 Blanket 5 – 15% Membrane/Rubber Bag > 15% Open Breather
21
Legend (next slides) IEEECondition 1 Limit CigreTypical Value (Brochure SCD1.32, 2010) AFMoArc Furnace, 90th Percentile (mineral oil) AFSiArc Furnace, 90th Percentile (Silicon oil)
22
H2 – All Data IEEE AFMo AFSi Cigre
23
CH4 – All Data IEEE AFMo AFSi Cigre
24
C2H2 – All Data IEEE AFMo AFSi Cigre
25
C2H4 – All Data IEEE AFMo AFSi Cigre
26
C2H6 – All Data IEEE AFMo AFSi Cigre
27
CO – All Data IEEE AFMo AFSi = 1936 Cigre
28
CO2 – All Data IEEE AFMo AFSi = 25,387 Cigre
29
TDCG – All Data IEEE AFMo AFSi = 2,160 Cigre
30
Further Breakdown… Given a type of oil preservation (say, N2 Blanket) What happens to Gas Levels vs Voltage Class, MVA, Age?
31
H2, 90th Percentile – Per Voltage Class IEEE AFMo AFSi Cigre
32
H2, 90 th Percentile – Per MVA Rating IEEE AFMo AFSi Cigre
33
H2, 90 th Percentile – Per Age Group IEEE AFMo AFSi Cigre
34
C2H6, 90th Percentile – Per Voltage Class Cigre
35
Revision C57.104 – TF on Data Analysis Gas Rate Subject 1. Should we calculate rates percentiles for all gases? 2. Should we associate rates to levels? How? 3. Cigre recent experience
36
Revision C57.104 – TF on Data Analysis Cigre Levels vs Sampling Intervals Cigre SCD1.32 Brochure, December 2010
37
Revision C57.104 – TF on Data Analysis Cigre Rates vs Sampling Intervals Cigre SCD1.32 Brochure, December 2010
38
Revision C57.104 – TF on Data Analysis Cigre SCD1.32 Brochure December 2010
39
Revision C57.104 – TF on Data Analysis Proposal Under Discussion – Level vs Rate Frequency of DGA
40
Revision C57.104 – TF on Data Analysis Proposal Under Discussion – Level vs Rate Severity of Fault (?)
41
Revision C57.104 – TF on Data Analysis Gas Rates (IEEE Database)
42
Revision C57.104 – TF on Data Analysis Gas Rates (IEEE Database)
43
Revision C57.104 – TF on Data Analysis Gas Rate Issues 72 115 133 days
44
Revision C57.104 – TF on Data Analysis Gas Rate Issues 72 115 133 days
45
Revision C57.104 – TF on Data Analysis Gas Rate Issues ± 15% Cigre Typical Lab Accuracy 133 days
46
Revision C57.104 – TF on Data Analysis Gas Rate Issues 72 115 343 days 68 ?
47
Revision C57.104 – TF on Data Analysis Gas Rate Issues
48
Revision C57.104 – TF on Data Analysis Another Example
49
Revision C57.104 – TF on Data Analysis Another Example 27 ppm/year 500 ppm/year
50
Revision C57.104 – TF on Data Analysis Inherent Uncertainty in Trend Calculation 1. Multiple Laboratories 2. Lab Variations (repeatability, reproducibility, accuracy) 3. Seasonal variations (temperature, etc) 4. Sampling errors (humans, sample contamination, etc) 5. Type of Transformer (N2, etc…) 6. Sampling interval??
51
Revision C57.104 – TF on Data Analysis Distribution of DGA Sampling Interval
52
Revision C57.104 – TF on Data Analysis Distribution of DGA Sampling Interval
53
Revision C57.104 – TF on Data Analysis Distribution of DGA Sampling Interval
54
Revision C57.104 – TF on Data Analysis Gas Rates Distribution vs DGA Sampling Interval
55
Revision C57.104 – TF on Data Analysis Gas Rates Distribution vs DGA Sampling Interval
56
Revision C57.104 – TF on Data Analysis Gas Rates Distribution vs DGA Sampling Interval
57
Revision C57.104 – TF on Data Analysis Gas Rates Distribution vs DGA Sampling Interval
58
Revision C57.104 – TF on Data Analysis Gas Rates Distribution vs DGA Sampling Interval
59
Revision C57.104 – TF on Data Analysis Gas Rates Distribution vs DGA Sampling Interval
60
Revision C57.104 – TF on Data Analysis Gas Rates Distribution vs DGA Sampling Interval 38%
61
Revision C57.104 – TF on Data Analysis Rates Distribution vs DGA Sampling Interval
62
Revision C57.104 – TF on Data Analysis 53 204
63
Revision C57.104 – TF on Data Analysis
67
Food for Thought!
68
Revision C57.104 – TF on Data Analysis Proposal for Discussion – Level vs Rate Severity of Fault (N2 Blanket, etc) 90 th | t 95 th | t … Table conditioned to t = Sampling Interval
69
Revision C57.104 – TF on Data Analysis Rate of Gas Increase vs Sampling Interval???
70
Revision C57.104 – TF on Data Analysis Rate of Gas Increase vs Sampling Interval???
71
Revision C57.104 – TF on Data Analysis Rate of Gas Increase vs Sampling Interval??? Food for Thought…