1
Check Beam Shear
2
Bending moment design 2.5m 245 166 Short direction
3
Central band ratio = Central band of short direction = 0.83 As = 0.83 (10.1)=8.6cm2
5
Footing Design Part II Combined footing
6
Example 1 Design a combined footing As shown
7
Dimension calculation
The base dimension to get uniform distributed load 2000kN 800 kN 1200 kN A x1=0.2m x2=6.2m x 800(0.2)+1200(6.2)=2000(x) x = 3.8m 800 kN 1200 kN Try thickness =80cm 2x =7.6 m
8
Area required
9
Check for punching Shear
d = 730 mm 1.13m 0.765 A
10
B
11
Draw S.F.D & B.M.D Stress under footing = 190 *1.8 = 342 kN/m
12
Check for beam shear b = 1800mm, d = 730mm
13
Bending moment Long direction
14
Bending moment Short direction
Under Column A
15
Shrinkage Reinforcement in short direction
Under Column B Shrinkage Reinforcement in short direction
17
Combined footing, strip footing, & Mat foundation
Footing Design Part III Combined footing, strip footing, & Mat foundation
18
Example 2 Design a combined footing As shown
19
Dimension calculation
The base dimension to get uniform distributed load x2=4.2m 1200 kN 750 kN x 1950kN A 750(4.2)+1200(0.2)=1950 (x) x = 1.75m x1=0.2m
20
Area required
21
Check for punching Shear
h= 750mm d = 732 mm A B2=1m B1=4m
22
B
23
Draw S.F.D & B.M.D
24
Empirical S.F.D & B.M.D m Convert trapezoidal load to rectangle Mmax
Clear distance between column B in moment design = ave. width = 2.5m
25
Check for beam shear d = 665mm Y=1.5m 1m 4m x b
26
Bending moment Long direction
Top Bottom
27
Bending moment Short direction
Under Column A
28
Shrinkage Reinforcement in short direction
Under Column B Shrinkage Reinforcement in short direction
29
Reinforcement details
30
Example 3 (Strip footing)
Design a combined footing As shown
31
Dimension calculation
The base dimension to get uniform distributed load 3040kN 800 kN 1280 kN 960 kN A Assume L1=0.6 x1=5.2m L2 x2=10.7m x 800(0.6)+1280(5.1)+960(10.6)= 3040 (x) x = 5.65m, 2(x)=11.3m L2= (10.6)=0.7
33
B Check for punching Shear h = 700 mm d=630mm Example
You can check other columns
34
Draw S.F.D & B.M.D Stress under footing = 195 *1.8 = 351 kN/m
35
Check for beam shear b = 1800mm, d = 630mm
36
Bending moment Long direction
Design Short direction as example 1 (lecture 11)
37
Reinforcement details
38
Mat Foundation
40
Check for punching Shear
41
General Example, Ref. 2 Modified load
42
General reinforcement details