New electronic controls
Technical Updating New electronic controls Scheda Pco OEM monocircuito
2
New electronic control Microchiller
New electronic device CAREL Pco OEM Monocircuit. Will be installed in: TCAE/THAE 150/160:immediatly TCAE/THAE 105/109 will replace En.gy 210b TCCE/THCE 105/109 will replace En.gy 210b TCAE THAE 114/138 will replace En.gy 210b Scheda Pco OEM monocircuito
3
User interface –in the unit
CAREL 3 YES INLET water TEMP MANUFACTURER N° BUTTONS BACK LIGHTING DISPLAY MICROTECH 2 NO INLET water TEMP Scheda Pco OEM monocircuito
4
Scheda Pco OEM monocircuito
Key utilization programmation /alarms KEY: allows the access the programmation parameters or ,with red led ON, to display the alarm list and and to reset them mode up KEY: Allows to change from the summer to the winter mode (for heat pump), the scroll of the parameters and the increase of the displayed value. Scheda Pco OEM monocircuito
5
Scheda Pco OEM monocircuito
Utilizzo tasti on/off down KEY: Allow the switch on and off of the unit ,the scroll down of the parameters and the decrement od the displayed value. up + down KEY: If you are inside of a group of masks allows to go back to the upper level group of masks .Allows also to confirm the new inputed values . Scheda Pco OEM monocircuito
6
Electrical board Layout
Installed in the chiller Scheda Pco OEM monocircuito
7
Electrical board Layout
Clock Board Serial interface Igital Inlets Probes NTC Press Transducers Digital outlets Scheda Pco OEM monocircuito
8
TIME ZONE MANAGEMENT BY CLOCK BOARD:
Comparison OLD - NEW NEW OLD TIME ZONE MANAGEMENT BY CLOCK BOARD: YES Management of 4 daily time zone with the chance to change the set point or to manage the On/Off time of the unit NO
9
Activable by parameter under manufacturer menu .
Comparison OLD - NEW NEW OLD 2 PUMPS MANAGEMENT: YES Activable by parameter under manufacturer menu . Manage the pump rotation according to the working N° of hours one in stand by to the other. NO Scheda Pco OEM monocircuito
10
COMPATIBLE SUPERVISION SYSTEMS :
Comparison OLD - NEW OLD NEW COMPATIBLE SUPERVISION SYSTEMS : Carel Modbus (Accessory KRS485) Lonmark (Accessory KFTT10) Only Modbus
11
NEW ALARMS MANAGED BY THE ELECTRICAL BOARD :
Comparison OLD - NEW NEW NEW ALARMS MANAGED BY THE ELECTRICAL BOARD : Wrong phase sequence :activated from the phase monitor integrated in the electrical board Hi and low Voltage supply:activated by a board that measures the width of the phases and verify eventual anomaly in the absorption of the phases . Scheda Pco OEM monocircuito
12
NEW’ :ALARM HISTORY FOR EACH ALARM IS MEMORIZED:
Accessory: Remote keyboar KTR OLD NEW NEW’ :ALARM HISTORY FOR EACH ALARM IS MEMORIZED: Compressors working hours Condensation Temperature/pressure Stato compressor/s and fans satus one istant before the alarm. Alarm hour and date (with clock board) Total N° of memorized alarms Alarm code and description Evap water inlet/outlet temperature
13
CLOCK BOARD
14
Serial converter RS485/RS232
15
Serial converter RS 485/USB
16
Serial Interface FTT10 LonWorks (KFTT10)
Scheda Pco OEM monocircuito
17
Serial Interface RS485 Modbus (KRS485)
Scheda Pco OEM monocircuito