IntegraPower Features and Models
2
L1L2L3 T1T2T3 RS-232 cable to PC TB1 connections: Remote ON/OFF Remote indicator light Y- Control Bypass contactor control TB2 connections: Remote power supply Escalator safety chain Indicator LEDs Line Side Load Side (to motor) Basic Connections 35A IntegraPower-E
3
Operator Interface Software MAIN CONTROL SAVINGS CONTROL SOFT START SAFETY CONTROL SOFT STOP WYE-DELTA CONTROL DATA FEEDBACK
4
Two Energy Saving Methods Combined in One Controller 1. Power Attenuation using SCRs 2. Intelligent Y- Switching
5
Energy-Saving Method 1: Power Attenuation Using SCR Switches
6
Motor A AA a bc V VV Voltage Sensors Current Sensors SCR Switches Voltage Zero Crossing Current Zero Crossing A / D Calculate Phase Angle SCR Control Signal Digital Signal Processor Basic Architecture 3-Phase Power Phase angle between current & voltage Light Motor Load: large phase angle Heavy Motor Load: small phase angle
7
Energy Saving Method Explained Further… No SavingsWith Savings Voltage AC Waveform Current AC Waveform
8
kW without IntegraPower controller 2.05 kW with IntegraPower controller1.43 kW reduction29.5% Escalator Example: Nevada Casino (up escalator)
9
Energy-Saving Method 2: Intelligent Wye/Delta Switching (if Y- starter present)
10
Timer RelayY-Contactor -Contactor Up / Down Contactors Circuit Breaker Overload Protection Typical Y- Control Components
11
Energy Saving In Wye Mode 480VAC 277VAC 10A30A 17.3A L1 L2 L3 L1 L2 L3 10A WYE Configuration* Delta Configuration* Power Consumption = 1/3 of Delta Line Current = 1/3 of Delta Motor Torque = 1/3 of Delta Winding Voltage = 58% of Delta Line Impedance = 3 times Delta *balanced load 17.3A 60 o R R R S S Motor L1 L2 L3 T1 T6 T2 T4 T3 T5
12
Added Savings with Y- Switching Sterling Electric Model EMOLO4FFA Y- Motor 10HP 3-phase 230/460 VAC 25.2/12.6 A
13
Electronic powerreduction Power reductionby Y- switching IntegraPower-E
14
Y- and Voltage Reduction Savings
15
Example Wiring Diagrams
16
Basic Connection
17
With 2 button On/Off Control
19
PLC Remote Control
20
Indicator Light Control GREEN – Control board has power Self test passed YELLOW – Start signal received (controller will output power to motor) AMBER – Controller is in savings mode (Y – Delta) RED – Fault condition detected Switch S1 - setting selects when 1 to 2 shorts
21
Like most Soft Starters
22
Bypass & Disconnect
23
WYE – Delta
24
The Logic for Y - Delta
25
Escalator
26
Typical Industrial Application
27
Mounting on Unistrut
28
Power Quality Capacitors Data taken on GE 4 pole motor for 2 different loads (PF =.87 and PF =.64 before the capacitors. Based upon this limited data, it is observed that the % KW savings is slightly higher with the capacitors than without the capacitors. The % KVA savings is slightly lower with the capacitors than without the capacitors.
29
No CapacitorsBefore CapacitorsAfter Capacitors LOAD 1 Power Factor with no Controller 0.350.640.35 Power Factor with Controller 0.440.720.43 % KW Savings25.70%26.30%24.70% % KVA Savings 39.90%35.00%38.80% LOAD 2 Power Factor with no Controller 0.60.870.6 Power Factor with Controller 0.640.940.65 % KW Savings4.60%5.10%4.90% % KVA Savings 11.40%8.40%11.10%
30
The User Interface
31
S2 GUI mode & cable
32
PrecisionPower software interface Soft Start Soft Stop Main Control Savings Safety WYE – Delta Data Feedback