NetSure™ RDB Series
2
NetSure™ RDB Series 48V Plug-n-Play Rack Distribution
Designed to feed up to 8.6kW from 200A breaker Zero U, rear mount Plug-n-play connectors for tool-less add/move/change Includes ground plug Breaker trip notification Universal mounting – can be mounted on the left or right in both top and bottom cable applications Model options by application: 1-2U Rack Mount Devices 6 or 15 outlet (L6 or L15) versions Larger Rack Mount Devices 6 outlet (M6) version Blade Chassis and High Power Devices 2 or 3 outlet (H2 or H3) versions
3
Rack Distribution Concept
DC Power System IT Rack IT Rack 20A Load 20A Load Zero U Power Strip 20A Load A side B side Output Breakers A side B side Quick Connect Plug What does distribution in the rack look like? By locating power conversion very close to the point of use, no more than a 4/0 cable is required to carry each of the (22) 8.5kW max branch circuits within 60’ of the DC UPS, minimizing the amount of copper required. Take for example racks full of blade servers, each requiring (3) 70A breakers per side. WE have developed a series of rack distribution units to easily provide this secondary distribution with quick connect plugs. Typical 4/0 Cables No conduit req’d in cable tray Rack Mount Server Example (15) 20A inputs / side Blade Server Example (3) 70A inputs / side
4
Available Models
5
NetSure™ RDB L6 NetSure™ RDB Model Outlets Power Rating Part Number
Per Outlet Per PDU Max Watts Max Amps1 Max kW L6 6 420 10 2.5 60 547692 630 15 3.8 90 547693 840 20 5.0 120 547499 1 Max Amps rated at end of battery discharge (42V) 2 PDU power rating limited to 200A, 8.4 kW each All NetSure™ RDB Series PDUs are designed for up to 200A input
6
NetSure™ RDB L15 NetSure™ RDB Model Outlets Power Rating Part Number
Per Outlet Per PDU Max Watts Max Amps1 Max kW L15 15 420 10 6.3 150 547694 630 8.42 2002 547695 840 20 547615 1 Max Amps rated at end of battery discharge (42V) 2 PDU power rating limited to 200A, 8.4 kW each All NetSure™ RDB Series PDUs are designed for up to 200A input
7
NetSure™ RDB M6 NetSure™ RDB Model Outlets Power Rating Part Number
Per Outlet Per PDU Max Watts Max Amps1 Max kW M6 6 1,050 25 6.3 150 547696 1,260 30 7.6 180 547697 1,470 35 8.42 2002 547503 1 Max Amps rated at end of battery discharge (42V) 2 PDU power rating limited to 200A, 8.4 kW each All NetSure™ RDB Series PDUs are designed for up to 200A input
8
NetSure™ RDB H2 NetSure™ RDB Model Outlets Power Rating Part Number
Per Outlet Per PDU Max Watts Max Amps1 Max kW H2 2 3,360 80 6.7 160 547500 1 Max Amps rated at end of battery discharge (42V) 2 PDU power rating limited to 200A, 8.4 kW each All NetSure™ RDB Series PDUs are designed for up to 200A input
9
NetSure™ RDB H3 NetSure™ RDB Model Outlets Power Rating Part Number
Per Outlet Per PDU Max Watts Max Amps1 Max kW H3 3 2,100 50 6.3 150 547698 2,520 60 7.6 180 547699 2,940 70 8.42 2002 547501 1 Max Amps rated at end of battery discharge (42V) 2 PDU power rating limited to 200A, 8.4 kW each All NetSure™ RDB Series PDUs are designed for up to 200A input
10
Output Cables Quick connect to PDU Un-terminated to IT equipment
2 Models: 547613: Power Cord for H2, H3 Models - 4' Long 547595: Power Cord for L6, L15, M6 Models - 6' Long
11
Breaker Trip Alarm Scheme
Alarm scheme for NetSure™ RDB Series -48 VDC signal provided to indicate a breaker has tripped Signal can be “daisy-chained” to connect to multiple power strips Alarm signal can be connected to NetSure™ controller, or to other monitoring system that accepts -48 VDC signal 2 position removable terminal block provides a simple customer connection point for alarm signal requiring only a stripped wire
12
PDU Rack Mounting Bracket
Mounts in rear of IT rack Includes bracket and hardware to mount to one side of rack Left side or right side mounting P/N:
13
Mating Input Quick Connect Kits
Provides mating connector to input of NetSure™ RDB Series Installs on cables from NetSure™ DC Power System Includes mating SB350 housing and two contacts 4 kits to accommodate 1/0 through 4/0 wire QTY: 1 per distribution strip depending on input wire size KIT P/N Wire Size 547668 1/0 AWG 547669 2/0 AWG 547670 3/0 AWG 547671 4/0 AWG