Download presentation
Presentation is loading. Please wait.
Published byRachael Pitts Modified over 9 years ago
1
IEEE Power Engineering Society Toronto Chapter Ontario Wind Turbines – Testing of Electrical Safety Kinectrics Seminar May, 2007 Eugene Peter Dick IEEE Senior Member 49 Lynngrove Ave Toronto, Ontario epdick@ieee.org 647 438 8116
2
1.5 MW GE Wind Turbine
3
Foundation - Elevation
4
Tower Height: 65 to 80+ m Base Flange: 5 m , circa 200 bolts (ext, interior) Sections: 3 joined by interior flanges, platforms Access: ladder with fall restraint Bus type: rigid or locomotive flexible cable Section: 500+ mm 2 (1 000+ mcm) Erection: 500 tonne crane
5
Bolt Ring – Duplicated Inside
6
500 Tonne Crane
7
Nacelle
8
Rotor Blades Diameter: 71 m Speed: 12 – 22 rpm Gearbox: 3-step planetary spur gear, ratio 72 Power vs wind speed:kWk/hr 5014 15021 45028 90036 1 50043 cut out90
9
Generator Rating: 1.5 MW, 1.72 MVA, 575 V, stator 1 509 A Type: double fed, 3 , (induction?) synchronous Rotor via PWM drive rated 300 kW Poles: 6, - / + 20 % speed (864 to 1 440 rpm) H (inertial const): 6.55 s (gen alone 0.8 s) Xd” (subtransient reactance): 0.27 pu Protection: V over / under / unbal, f over / under Control: pf or current compensated V
10
Typical Interconnect Requirements < 88 % V trip in 2 s, < 50 % V trip in 0.16 s > 110 % V trip in 1 s, > 120 % V trip in 0.16 s < 59.8 Hz trip in 300 s, < 57 Hz trip in 0.16 s V on synch: < 5 %, flicker IEEE Std 519, 1453 dc: < 0.5 % on I harmonics: < 4, 2, 1.5, 0.6 % (h<11, 17, 23, 35) islanding with load: trip in less than 2 s no impact on utility feeder protection
11
Stepup Transformer
12
Transformer / Collection System Xmer: 575 / 34.5 kV, Yg / , Z = 0.76 + j 5.70 % 35-kV, 67 mm 2 (AWG 2/0) concentric Neu cable several units daisy-chained to riser pole may run Neu / bond back to main substation overhead line may be 3 or 4-wire typically 4 collection lines to main station, CB each collection line may have gnding Xmer main Xmer: 34.5 / 230 kV, 100 MVA
13
Stepup Transformer Cabinet
14
Cable Run to Riser Pole
15
Collection Line to Main Substation
16
Main Substation
17
Grounding Transformers
18
230-kV System Tie
19
Erie Shores Setting
20
Erie Shores Layout
21
Erie Shores Ground Electrode
22
Sault Ste Marie (Prince) Wilderness
23
Prince Layout
24
Prince in Autumn
25
Prince in Late Autumn
26
Prince Ground Electrode
27
Prince 1 Collection Cable
28
Grounding - Objectives limit V between touchable objects provide low Z path so protection sees fault I direct fault I, lightning away from equipment minimize interference
29
Grounding - Definitions Remote earth: soil not rising in potential on faults Bonding: to connect two objects with low Z path Grounding: to provide bonding to remote earth G System: all conductors that facilitate grounding G Current: fault current that enters a G system G Electrode: conductors that dissipate I into soil G Potential Rise: V between G system, remote soil Step Potential: foot-to-foot V during system fault Touch Potential: hand-to-foot V on system fault
30
Grounding – Tested Quantities GPR: general hazard indicator, telco pairs Step V: coord to safe body withstand (180, 1 550 V) Touch V: coord to safe body withstand (168, 663 V) Touch types: structure, mesh, fence, gate, exterior Current splits: on external connections: Neu, Ohg Soil resistivity: model all of above Surface stone resistivity: check for deterioration Conductor integrity: measured and modelled
31
GPR = Rg Ig Ig - Vg + Telco
32
Measure Rg with Fall of Potential C1 P1 C2 P2 x c
33
Locate Probe P at 62 % of Probe C 1 2 3 4 5 6
34
When Soil Has Two Layers C1 P1 C2 P2 x c h 11 22
35
Adjust Location for P to C Ratio
36
Interconnections Affect P to C Ratio C1 P1 C2 P2 x c
37
Soil Anomalies Affect P to C Ratio low C1 P1 C2 P2 x c high
38
Proximity Correction: Arbitrary P, C low C1 P1 C2 P2 x c high
39
Running Out Leads in Fair Weather
40
Testing When Snow Flies
41
Reading the AC Milliohm Meter
42
Six Towers Left Before Nightfall
43
Network Analyzer for Current Splits low C1 Split- Core CT c high C2 Network Analyzer
44
Rogawski Coil for Current Splits
45
Counterpoise Current Split
46
Network Analyzer, Scope, Megger
47
Network Analyzer for Impedance low C1 P1 P2 x c high C2 Network Analyzer
48
Equiv Cct for Proximity Corrections XcgXgp Xcp Ic - Ic Rcg + Ic + Ic Rgp - Ic Rcp + + Vp - Zd Rg
49
Proximity Correction Method Zg= Zm + Rgp + Rcg – Rcp = Zd / ( Zd + Rg ) =b + Rcg / ( Rcg + Zd ) measure Zm and read Zm at several locations for P find Zg for each, average these estimates calculate standard deviation as quality check
50
Measuring Step Potential
51
Measuring Touch Potential
52
Summary When sandy soil or rock raise Rg, tests useful Fall of Pot bad with soil anomalies, interconnections Proximity Correction method has P and C opposite Multiple estimates of Zg averaged for less noise Standard deviation of Zg checked for quality Measuring current splits good with interconnections
Similar presentations
© 2024 SlidePlayer.com. Inc.
All rights reserved.