Download presentation
Presentation is loading. Please wait.
Published byClarissa claudia Kempson Modified over 9 years ago
1
Power Electronics in Hybrid Energy Networks Johan Enslin David Elizondo Johan.Enslin@kema.com Delizondo@kema.us KEMA Inc. T&D Consulting Raleigh, NC USA
2
2 Outline n The Future of Energy Hydrogen Economy Hybrid Hydrogen Economy Energy Web Concept and Distributed Power n Power Electronics’ role in the Future of Energy Interconnection of Large-scale PV Interconnection of Wind Energy n Energy Storage’s and FACTS role in the Future of Energy
3
3 Hydrogen Hope and Gamble
4
4 Grid-less Hydrogen Society?
5
5 Electrolyzer - Water purification - Regulators - Gas dryer - Integrated Heating - CHP Hydrogen Storage Hybrid AC/DC Networks H 2 Gas + - V Water Supply H 2 Trucking H 2 Pipeline O 2 Gas Peak Shaving Fuel Cell Power Electronics - Grid Interconnection - STATCOM / APF - Max Power Tracker - Electricity Storage - Transfer Switch Control, Protection Comms Local H 2 Use DP - Network - Hydrogen Hybrid System Concept Electrical Interconnection Transport
6
6 Energy Web Concept Residence Factory CHP Wind Microturbine Commercial CHP Central Generation Fuel Cell Flywheel Substation Photovoltaic Storage Power & Communications Links Gas Turbines Fuel Cell Car Flow Batteries Pumped Storage Decentralized DER Dispatch Data Centers
7
7 Energy Web Concepts n Characteristics of Energy Supply in 2010 Nuclear Generation: Upgrade and Replace Centralized Nuclear Generation and Small Scale Pebble Bed Modular Nuclear Reactors Gas & Electrical Networks merge – Move to Hydrogen Renewable Energy Generation: Targets 10 - 20% (Environmental) High premium on Network Reliability and Security Shift from power supply to service orientated culture
8
8 Energy Web Concepts--Cont n Technology Higher Efficiency for Distributed Generation Flexible and lower cost power electronic interfaces Less NO x and CO 2 generation Low-cost, flexible energy storage n Interconnections and Regulations Standardization of Power and Communication Interfaces Simplified regulations for small DP Safety considerations in island operation Formation of self-sustained islanding mini grids
9
9 Energy Web Concepts--Cont n Distributed Power has to Offer: “Plug & Play” Functionality with enforced standards Intelligent Communicating Components – Extra services Network Reliability, Quality, Stability and Security built-in Power Electronics Multi-fuel driven micro-turbine technologies High efficiency technologies with CHP functionality Interface Between Hybrid AC / DC / Gas / Hydrogen Networks
10
10 Distributed and Renewable Power n Dutch Government and Utilities promote use of renewables with subsidies and customer programs. n Dutch generation > 35% distributed CHP Wind (10%) n Some whole suburbs are installed with roof-mounted PV arrays n Nieuwland 500 homes in total 12 000 m² PV. 1 GWh Renewable Energy n 6 GW off-shore wind power is currently planned for 2020. Amersfoortse suburb Nieuwland
11
11 Distributed Power Trends 2010
12
12 Interconnection Issues with DP n Power Quality considerations on system level Background system distortion; All indices; Network Resonances Require integrated mitigation solutions n Protective Relaying Considerations Feedback Power Islanding n Voltage and Angular Stability Distribution Networks behave like Transmission Networks Require innovative solutions – FACTS; Storage; Hybrid Networks n Interconnection Standards and Guidelines Crucial to do updates: IEEE 1547, IEC 61400-21, EN 50160
13
13 Case A: Interconnection of Large-scale PV
14
14 Interconnection Issues with DP inverters n 200-500 Homes with PV panels 1-3 kW PV inverters, connected at 220 Volts feeder 1GWh is generated annually n By Measurements at the site… n Voltage regulation and Flicker: Exceeding voltage limits and inverters trip Voltage fluctuations due to power fluctuations n Harmonics: Inverters individually satisfy IEC 61000-3-2 specification EN 50160 can temporarily be exceeded. Inverters trip unexpectedly
15
15 Interconnection Issues with DP inverters n Attention Points on Standards Effect of background supply distortion Increased distortion due to a resonance phenomenon Islanding may be a good alternative
16
16 Case B: Interconnection of Wind Energy
17
17 Network Interconnection of 6 GW Wind n Feasibility of 6 GW Wind Power in 2020 n Total cost 10.000 M€ n Stability Issues and Reactive Power Compensation n Required 350 M€ - 650 M€ network upgrades n Conventional solution requires 100 M€ expenditure
18
18 Energy Storage for 6 GW Wind Farm n Possible savings of 250 M€ - 550 M€ network upgrades if storage is included n Requires 2,5 GW and 62 GWh storage for 6 GW wind farm
19
19 Storage Options for 6 GW Wind Farm n Based on Flow-battery technology 6,000 M€, 30 years NPV, 1x1 km size n Not feasible by factor 10 as a single solution VSC Interface
20
20 Integrated Storage Approach n Primary Application: Wind Power Stabilization. n Secondary Applications: Interface of Constant Speed Offshore Wind Turbines Power Balance and Reserve Power Management Power Quality and Reactive Power management Spinning Reserve Management Black-start Availability Stop-start Reduction of generating units Network security - UPS operation
21
21 Conclusions n Hydrogen economy Will be gradual process with DP playing a key role An excellent opportunity for power electronics – Mobile & Stationary applications n Distributed Power Preferred option to integrate renewables at high network reliability, stability and security levels Power electronics are key for better DP interconnections
22
22 Conclusions--Cont n Interconnection Issues Large-scale wind energy interface provide major network interconnection challenges – Hydrogen hybrids Design and control of DP converters for system integration needs attention n Futuristic View… Cost effective H 2 and electricity storage together with Power Electronics.
23
23 Hybrid Wind Network Options
24
24 Distributed Power: Mobile HYPERCAR NECAR
25
25 Energy Storage for Renewable and Distributed Power CHP
Similar presentations
© 2024 SlidePlayer.com. Inc.