Liquid Level Control Control Valves Pressure Control Temperature Control Glycol Pump
2
Temperature Controllers
3
Indirect Thermostat T12 Negative feedback for linear output
5 to 30 psi air or gas supply pressure Stainless steel housing Bi-metal sensing element for accurate control Single adjustment over Wide temperature range: T to 400oF HT to 700oF Output pressure proportionate to temperature at any setting T12
4
? Direct or Indirect ? Direct Mode Indirect Mode
Rising Temperature Rising Temperature Rising Output Falling Output Direct Indirect
5
Indirect Thermostat Indirect
6
Thermostat with Separable Socket
Maximum Working Pressure Without Separable Socket psi With Separable Socket psi With Special Separable Socket psi
7
Direct Acting Thermostat
Supply Output T 12DA Direct
8
T 12DA Thermostat Reversed for Indirect Throttle Mode Supply Output
9
High Temperature Thermostat
Supply Output HT 12 Indirect
10
Direct Snap Thermostat
Output Supply Direct
11
Indirect Snap Thermostat
T 12DAS Output Supply Indirect
12
Indirect Throttle Thermostat
Output Supply Indirect
13
Direct Throttle Thermostat
Output Supply T 12TDA Direct
14
Direct Semi-Throttle Thermostat
T 12DAT Output Supply Direct
15
Indirect High Temperature Shut-Down
T 12M Output Supply Indirect
16
Direct Low Temperature Shut-Down
T 12DAM Output Supply Direct
17
High Temperature Pilot Guard
Supply HT 12PG Output Direct
18
Typical Installation High temperature shutdown thermostat
Burner control thermostat Burner valve Main burner Safety shutdown valve Pilot Pilot Guard thermostat Instrument Gas
19
Typical Burner Control Installation
Low liquid shutdown pilot High temperature shutdown thermostat Burner control thermostat Main burner Pilot Instrument Gas Pilot Guard thermostat Safety shutdown valve Burner valve
20
Trouble Shooting SYMPTOM CAUSE Bent sensing element
Erratic temperature changes Continuous venting Bent sensing element (element should be centered in base and should “ring”) Incomplete immersion of probe Dirty pilot plug seat Hole in diaphragm Weak pilot plug spring Faulty ‘O’ ring
21
Trouble Shooting To check small seat: increase temperature setting
several degrees and see if venting stops. To check large seat: decrease temperature setting Replace pilot plug and seats if unable to stop venting by cleaning seats.