Controller Programming

Similar presentations


Presentation on theme: "Controller Programming"— Presentation transcript:

1 Controller Programming

2 Relay Control

3 Relay Control -- Introduction
Two-position control, using a digital (relay) output, is used to turn something on and off. We use a differential and an offset to tell an output when to open and close based on the control variable and setpoint.

4 Relay Control -- Definitions
Differential – amount of change in the control variable from when the output turns on to when it turns off Offset – a value that creates a deadband for a stage – the first stage typically has an offset of 0

5 Offsets and Differentials, 2 Setpoints

6 Offsets, Differentials and Deadband, 1 Setpoint
Used on the SZ1025b and SZ1143b

7 Proportional Control

8 Proportional Control -- Introduction
Analog outputs are called modulating outputs. These outputs vary based on how far the input is away from setpoint. Modulating outputs provide tighter control than two position outputs.

9 Proportional Control -- Definitions
Proportional Control – generates an output that is related to the distance between the active setpoint and the input Proportional Band/Throttling Range – number of degrees (or percent of span) that the input must change to drive the output from 0 to 100% (either 0 to 20 mA or 4 to 20 mA)

10 Proportional Control -- Definitions
Setpoint Offset – a value that creates a deadband before modulation starts Aquastat – allows the action to reverse when a digital input is made (SZ1017a, SZ1018, SZ1143b, SZ1051) or an analog input exceeds a certain value (SZ1025a, SZ1018, SZ1062, SZ1064)

11 Proportional Control -- Definitions
Direct Acting – the output increases as the input increases Reverse Acting – the output decreases as the input increases

12 Direct Acting - Output 12mA @ Setpoint

13 Reverse Acting - Output 12mA @ Setpoint

14 Direct Acting - Output 4 or 20mA @ Setpoint
Cooling Heating

15 Reverse Acting - Output 4 or 20mA @ Setpoint
Cooling Heating

16 Keypad Programming

17 Thermostat Keypad Layout

18 SZ1060 Series Keypad Layout

19 Comparison of Thermostat Keypads
Typical Superstat™ Keypad SZ1060 Series Keypad

20 SL1001a & SZ1140 Series Keypad Layout

21 Conventional Thermostats
Menu-by-Menu Example Follow Along Using Demo Panel Slides Printed in Handout Catalog Page 183 All Thermostats Basically the Same Complete Sequences in Product Manuals All Sequences in Product Catalog

22 SZ-QD Trainer Demo Panel (SZ1031)
248 always works!!! Use down arrow to get to 248 more quickly.

23 SZ-QD Trainer Demo Panel (SZ1031) -- continued
Use your badge number as the address for your stat.

24 SZ-QD Trainer Demo Panel (SZ1031) -- continued

25 SZ-QD Trainer Demo Panel (SZ1031) -- continued

26 SZ-QD Trainer Demo Panel (SZ1031) -- continued
This Screen is Repeated for Occupied Periods B, C, and D This Screen is Repeated for Occupied Periods B, C, and D

27 SZ-QD Trainer Demo Panel (SZ1031) -- continued

28 Model Specific Features – SZ1035

29 Additional Model Specific Features -- continued

30 SZ-QD Trainer Demo Panel (SZ1031) -- continued

31 SZ-QD Trainer Demo Panel (SZ1031) -- continued

32 SZ-QD Trainer Demo Panel (SZ1031) -- continued

33 SZ-QD Trainer Demo Panel (SZ1031) -- continued

34 SZ-QD Trainer Demo Panel (SZ1031) -- continued

35 SZ-QD Trainer Demo Panel (SZ1031) -- continued

36 SZ-QD Trainer Demo Panel (SZ1031) -- continued

37 SZ-QD Trainer Demo Panel (SZ1031) -- continued

38 SZ-QD Trainer Demo Panel (SZ1031) -- continued
NOTE: This is a secondary access code.

39 Setting the Clock & Schedule (SZ1031)
248 always works!!! Use down arrow to get to 248 more quickly.

40 Setting the Clock & Schedule (SZ1031) -- continued
This Screen is Repeated for Occupied Periods C and D

41 Setting the Clock & Schedule (SZ1031) -- continued
These Screens are Repeated for Wed., Thurs., Fri., Sat., Sun., Plus Holiday #1 & #2. This Screen is Repeated for Occupied Periods C and D

42 Setting the Clock & Schedule (SZ1031)-- continued
Total Possible Holidays x x 99 = 2,376 scheds. instances days days

43 Setting the Clock & Schedule (SZ1031)-- continued

44 Where to Get Help or Answers
Instructions Sent with Product TCS Basys Controls Catalog Training & Reference Manual Call TCS Directly –

45 Software Programming

46 PC Based Software -- Revelation Professional
Menu Driven Programming Use for Network Setup & Testing, Commissioning, & Load Balancing “Read” Before Making Changes “Write” Before Going to NEXT Menu “Write” vs. “Write Half / Write Page” “Load All” & “Save All” Options *** NOT SUPPORTED AS OF JAN 2009 ***

47 Superstat™ – conventional heat/cool…
Rev Pro Manual pg C-9

48 Superstat™ – conventional heat/cool…
Rev Pro Manual pg C-9

49 Superstat™ – conventional heat/cool…
Rev Pro Manual pg C-9

50 PC Based Software -- Insight
Similar to Revelation Professional… Tab Driven Interface Uses Same Datasheets as Ubiquity Use for Network Setup & Testing, Commissioning, & Load Balancing Shows Current Values (no “read” required) “Write Page” Before Going to New Tab *** NEW SOLUTION AS OF JAN 2009 ***

51 Superstat™ – heat pump…

52 Superstat™ – heat pump…

53 Superstat™ – heat pump…

54 Superstat™ – heat pump…

55 Superstat™ – heat pump…

56 Superstat™ – heat pump…

57 Internet Style Software – Ubiquity
Similar to Revelation Professional… Single Page for All Programming Info Shows Current Values (no “read” required) Writes All Values on “Submit” “Read Controller” Option (if needed)

58 Single Page Programming Screen

59 General Info, Alarms, & Assigned Assets

60 Schedule

61 Controller Summary & Ubiquity Functions

62 System and Setpoints & Digital Inputs

63 Digital Outputs

64 Additional Functions, Comments & Buttons

65 Superstat™ – heat pump…SZ1033

66 Superstat™ with 1 analog output…SZ1017a

67 Superstat™ with 1 analog output…SZ1041

68 Superstat™ with 2 analog outputs…SZ1051

69 Superstat™ with 2 analog outputs…SZ1053

70 General Purpose Controller…SZ1143b

71 General Purpose Controller…SZ1143b - cont’d

72 General Purpose Monitor…SZ1145

73 General Purpose Monitor…SZ1145 - cont’d

74 General Purpose Monitor…SZ1145 - cont’d

75 VAV Box Controller…SZ1025b

76 VAV Box Controller…SZ1025b - cont’d

77 VAV Box Controller…SZ1025b - cont’d

78 2 Channel, 365-Day Time Clock…SL1001a

79 2 Ch., 365-Day Time Clock…SL1001a - cont’d