Download presentation
Presentation is loading. Please wait.
Published byAntonio Buzbee Modified over 9 years ago
1
Foundations of Real Estate Management BOMA International ® Module 3: Building Operations I Heating, Ventilating, and Cooling the Building ®
2
Foundations of Real Estate Management Module 3: Building Operations I 2 ® Objectives List the three components of the HVAC system List the three tasks of the ventilation system Explain why it is important to balance outside air and exhaust air pressures, and tell what happens in a commercial building if the pressures are uneven Trace the flow of air through the duct work distribution system
3
Foundations of Real Estate Management Module 3: Building Operations I 3 ® Objectives Describe how electric reheat coils in a VAV box provide heat Describe how baseboard heating systems provide heat Describe the refrigeration cycle Describe the chilled water cycle Describe the condenser water cycle List at least five methods to improve efficiency of heating and cooling functions
4
Foundations of Real Estate Management Module 3: Building Operations I 4 ® HVAC Heating Ventilating Air Conditioning
5
Foundations of Real Estate Management Module 3: Building Operations I 5 ® Ventilation Provides outside air Removes stale air Filters
6
Foundations of Real Estate Management Module 3: Building Operations I 6 ® Ventilation Outside Air Damper Photo courtesy of PM 101
7
Foundations of Real Estate Management Module 3: Building Operations I 7 ® Ventilation Variable Frequency Drive Photo courtesy of Transwestern
8
Foundations of Real Estate Management Module 3: Building Operations I 8 ® Ventilation It’s a continuum No outside air 100% outside air Maximum energy efficiency Minimum energy efficiency Minimum IAQ Maximum IAQ
9
Foundations of Real Estate Management Module 3: Building Operations I 9 ® Ventilation Free cooling Using outside air to condition the space
10
Foundations of Real Estate Management Module 3: Building Operations I 10 ® Ventilation Exhaust Removing odors and carbon dioxide
11
Foundations of Real Estate Management Module 3: Building Operations I 11 ® Ventilation Separate exhaust for kitchens and restrooms
12
Foundations of Real Estate Management Module 3: Building Operations I 12 ® Ventilation Ensure restaurant tenants clean their exhaust system regularly
13
Foundations of Real Estate Management Module 3: Building Operations I 13 ® Ventilation Plenum Return Ducted Return
14
Foundations of Real Estate Management Module 3: Building Operations I 14 ® Ventilation Partition Walls Demising Walls Fire Dampers Protection
15
Foundations of Real Estate Management Module 3: Building Operations I 15 ® Ventilation Photos courtesy of Transwestern
16
Foundations of Real Estate Management Module 3: Building Operations I 16 ® Humidity ASHRAE recommends 50% relative humidity (range of 30-60%) Dehumidification Humidification (rare)
17
Foundations of Real Estate Management Module 3: Building Operations I 17 ® Pressure The Goal: Pressure In = Pressure Out
18
Foundations of Real Estate Management Module 3: Building Operations I 18 ® Pressure Over Pressurization More air is brought in than is exhausted Inoperable exhaust fan, incorrect VFD settings Front doors will not close properly People feel pressure (like on airplane) HVAC becomes inefficient
19
Foundations of Real Estate Management Module 3: Building Operations I 19 ® Pressure Under Pressurization More air exhausted than brought in Inoperable outside air fan, incorrect VFD settings Front doors hard to open HVAC becomes inefficient Façade will leak
20
Foundations of Real Estate Management Module 3: Building Operations I 20 ® Filtration Filters remove dust, debris, insects, and other contaminants Pleated filters v. fiberglass filters HEPA filters Charcoal filters for odors Changed routinely
21
Foundations of Real Estate Management Module 3: Building Operations I 21 ® Air Distribution Air Handler Trunk Line Branch Line VAV Boxes/Terminal Units Supply Air Diffusers
22
Foundations of Real Estate Management Module 3: Building Operations I 22 ® Air Distribution - Zoning Areas of the building operate differently from one another Zones determined by: Function/Use Location
23
Foundations of Real Estate Management Module 3: Building Operations I 23 ® Air Distribution Air Handling Unit (AHU) or Air Handler
24
Foundations of Real Estate Management Module 3: Building Operations I 24 ® Air Distribution VAV Box – controlled by a thermostat
25
Foundations of Real Estate Management Module 3: Building Operations I 25 ® Air Distribution Supply Air Diffuser
26
Foundations of Real Estate Management Module 3: Building Operations I 26 ® Air Distribution Trunk and Branch Ducts VAV Boxes and Supply Air Diffusers
27
Foundations of Real Estate Management Module 3: Building Operations I 27 ® Thermostat Types Pneumatic Direct Digital Control (DDC) Set point temperature Impossible to please everyone Location
28
Foundations of Real Estate Management Module 3: Building Operations I 28 ® Thermostat ASHRAE-recommended set points 71 o F for heating (68-75 o F) 76 o F for cooling (73-79 o F) Balance tenant comfort with energy efficiency
29
Foundations of Real Estate Management Module 3: Building Operations I 29 ® Thermal Layering Temperature is measured in the middle 1/3 (On top of the desk) Bottom 1/3 is coolest (space heaters) Heat Rises – Top 1/3 is warmest
30
Foundations of Real Estate Management Module 3: Building Operations I 30 ® Space Heaters
31
Foundations of Real Estate Management Module 3: Building Operations I 31 ® Heating Involves adding heat
32
Foundations of Real Estate Management Module 3: Building Operations I 32 ® Heating Fuel Sources Electricity Natural Gas Heating Oil
33
Foundations of Real Estate Management Module 3: Building Operations I 33 ® Heating Systems Central Local
34
Foundations of Real Estate Management Module 3: Building Operations I 34 ® Heating In most buildings, heating occurs only around perimeter – not in core Air handler provides cooling to entire building Electric heaters in perimeter VAV boxes heat perimeter as needed
35
Foundations of Real Estate Management Module 3: Building Operations I 35 ® Heating Baseboard heating Electric Hot water or steam Under floor or sidewalk (radiant) Interlock
36
Foundations of Real Estate Management Module 3: Building Operations I 36 ® Cooling Involves removing heat
37
Foundations of Real Estate Management Module 3: Building Operations I 37 ® Cooling Just 3 Loops Refrigerant Loop Chilled Water Loop Condenser Water Loop The loops do not mix!
38
Foundations of Real Estate Management Module 3: Building Operations I 38 ® Cooling The Refrigeration Loop/Cycle Refrigerant Compressor Condenser Expansion Valve
39
Foundations of Real Estate Management Module 3: Building Operations I 39 ® Cooling Refrigerant Fluid that absorbs heat Moves from liquid to gas (add heat) and back to liquid (remove heat) easily Boiling point is low: 50-60 o F Gas at room temperature
40
Foundations of Real Estate Management Module 3: Building Operations I 40 ® Cooling Compressor Applies pressure Changes refrigerant from low pressure gas to a high pressure, super-heated vapor
41
Foundations of Real Estate Management Module 3: Building Operations I 41 ® Cooling Condenser Rejects heat outside building Either air cooled or water cooled Enters as a super-heated vapor Leaves as a high temperature, high pressure liquid
42
Foundations of Real Estate Management Module 3: Building Operations I 42 ® Cooling Expansion Valve Sprays liquid into a fine mist Reduces pressure and cools refrigerant
43
Foundations of Real Estate Management Module 3: Building Operations I 43 ® Cooling Evaporator Transfers heat from building to refrigerant Heating the refrigerant causes it to boil Heated refrigerant then passes to compressor and the cycle continues…
44
Foundations of Real Estate Management Module 3: Building Operations I 44 ® Cooling The refrigeration cycle is nothing more than changing the refrigerant from a liquid to a gas and back to a liquid…over and over again It’s a closed loop system
45
Foundations of Real Estate Management Module 3: Building Operations I 45 ® Cooling The Refrigeration Cycle
46
Foundations of Real Estate Management Module 3: Building Operations I 46 ® Cooling Heat always moves from higher to lower temperature
47
Foundations of Real Estate Management Module 3: Building Operations I 47 ® Coils and Bundles Coils Transfer heat between air and refrigerant Bundles Transfer heat between liquid and refrigerant
48
Foundations of Real Estate Management Module 3: Building Operations I 48 ® Coils and Bundles Photo courtesy of PM 101 Coils
49
Foundations of Real Estate Management Module 3: Building Operations I 49 ® Coils and Bundles Shell and Tube Bundles
50
Foundations of Real Estate Management Module 3: Building Operations I 50 ® Moving Heat from Inside to Outside Chilled Water Loop Rejects heat from occupied spaces to the refrigerant Condenser Loop (air-cooled) or Condenser Water Loop (water- cooled) Rejects heat from the refrigerant to outside of the building
51
Foundations of Real Estate Management Module 3: Building Operations I 51 ® Cooling Chilled Water Loop Water treatment is critical Picks up heat in evaporator coil (in AHU) and takes heat to refrigerant loop Cooler chilled water returns to evaporator coil to start process over again As heat is removed, cooler air is blown through duct system by the AHU
52
Foundations of Real Estate Management Module 3: Building Operations I 52 ® Cooling Condenser Water Loop (water-cooled) Water treatment is critical Picks up heat in refrigerant loop loop and takes heat to heat to cooling tower
53
Foundations of Real Estate Management Module 3: Building Operations I 53 ® Cooling Cooling Tower Condenser water pipes bathed in cool water sprayed inside cooling tower. Large fans also help transfer hea t Heat is transferred to outside Cooler condenser water is pumped back inside to start cycle again
54
Foundations of Real Estate Management Module 3: Building Operations I 54 ® Cooling Condenser Loop (air-cooled) Air is blown over refrigerant loop to reject heat
55
Foundations of Real Estate Management Module 3: Building Operations I 55 ® Cooling Water- or Air-Cooled Systems Chillers Self-Contained Units (SCUs) Air-Cooled Systems Rooftop Units (RTUs) Split System Heat Pump
56
Foundations of Real Estate Management Module 3: Building Operations I 56 ® Cooling Chiller Photo courtesy of PM 101
57
Foundations of Real Estate Management Module 3: Building Operations I 57 ® Cooling Self-Contained Unit (SCU) Photos courtesy of PM 101
58
Foundations of Real Estate Management Module 3: Building Operations I 58 ® Cooling Rooftop Unit (RTU) Photo courtesy of Thomas J. Easley
59
Foundations of Real Estate Management Module 3: Building Operations I 59 ® Cooling Split System Photo courtesy of Thomas J. Easley
60
Foundations of Real Estate Management Module 3: Building Operations I 60 ® Cooling Heat Pump
61
Foundations of Real Estate Management Module 3: Building Operations I 61 ® Piped Systems Types 2 Pipe 4 Pipe Fan coil units
62
Foundations of Real Estate Management Module 3: Building Operations I 62 ® Free Cooling Rejecting heat without using the compressor Flat plate heat exchanger Photo courtesy of Transwestern
63
Foundations of Real Estate Management Module 3: Building Operations I 63 ® Control Systems Building Automation System (BAS) Energy Management System (EMS)
64
Foundations of Real Estate Management Module 3: Building Operations I 64 ® Controlling HVAC Costs Optimize EMS Use free cooling Pay attention to weather Coasting Check temperatures with hand-held thermostat Control tenant adjustment abilities Aggressive water treatment Keep all components clean
Similar presentations
© 2024 SlidePlayer.com. Inc.
All rights reserved.