Download presentation
Presentation is loading. Please wait.
Published byAsa Divers Modified over 9 years ago
1
Foundations of Real Estate Management TM BOMA International ® Module 3: Building Operations I Heating, Ventilating, and Cooling the Building
2
Foundations of Real Estate Management Module 3: Building Operations I TM 2 Objectives List the three components of the HVAC system List the three tasks of the ventilation system Explain why it is important to balance outside air and exhaust air pressures, and tell what happens in a commercial building if the pressures are uneven Trace the flow of air through the duct work distribution system Describe how electric reheat coils in a VAV box provide heat Describe how baseboard heating systems provide heat Describe the refrigeration cycle Describe the chilled water cycle Describe the condenser water cycle List at least five methods to improve efficiency of heating and cooling functions
3
Foundations of Real Estate Management Module 3: Building Operations I TM 3 HVAC Heating Ventilating Air Conditioning
4
Foundations of Real Estate Management Module 3: Building Operations I TM 4 Ventilation System Provides outside air Removes stale air Filtration
5
Foundations of Real Estate Management Module 3: Building Operations I TM 5 Variable Frequency Drive (VFD) Used to regulate speed of pumps/motors Reduces energy costs Improves efficiency
6
Foundations of Real Estate Management Module 3: Building Operations I TM 6 Ventilation System It’s a continuum – building settings are somewhere in the middle No outside air 100% outside air Maximum energy efficiency Minimum energy efficiency Minimum IAQ Maximum IAQ
7
Foundations of Real Estate Management Module 3: Building Operations I TM 7 Energy Savings Free Cooling Using outside air to condition the space without mechanical cooling Many types of free cooling options Depends upon HVAC system design
8
Foundations of Real Estate Management Module 3: Building Operations I TM 8 Exhaust System Removes odors and carbon dioxide (CO 2 ) Separate exhaust system for kitchens and restrooms Restaurant/commercial kitchen exhaust systems need to be cleaned regularly
9
Foundations of Real Estate Management Module 3: Building Operations I TM 9 Humidity ASHRAE recommends 50% relative humidity (range of 30-60%) in commercial buildings Dehumidification Humidification
10
Foundations of Real Estate Management Module 3: Building Operations I TM 10 Air Moves in a Circle Supply Return Plenum return Ducted return
11
Foundations of Real Estate Management Module 3: Building Operations I TM 11 Walls Can Impact HVAC Partition walls Floor slab to ceiling Demising walls Floor slab to deck Principal purpose Fire protection Impact plenum return Fire dampers
12
Foundations of Real Estate Management Module 3: Building Operations I TM 12 Pressure
13
Foundations of Real Estate Management Module 3: Building Operations I TM 13 Over Pressurization More air is brought in than is exhausted Inoperable exhaust fan Incorrect VFD settings Front doors will not close properly People feel pressure (like on airplane) HVAC becomes inefficient
14
Foundations of Real Estate Management Module 3: Building Operations I TM 14 Under Pressurization More air exhausted than brought in Inoperable outside air fan Incorrect VFD settings Front doors hard to open HVAC becomes inefficient Roof and façade will leak
15
Foundations of Real Estate Management Module 3: Building Operations I TM 15 Filtration Filters remove dust, debris, insects, and other contaminants Pleated filters v. fiberglass filters Changed routinely
16
Foundations of Real Estate Management Module 3: Building Operations I TM 16 Air Distribution Air handler Fan Ductwork Trunk line Branch line VAV boxes/terminal units Temperature/air flow regulation Controlled by thermostat Supply air diffusers Distribute air in space
17
Foundations of Real Estate Management Module 3: Building Operations I TM 17 Air Distribution - Zoning Areas of building operate differently from one another Zones determined by Function/use Location Heat sources External Internal
18
Foundations of Real Estate Management Module 3: Building Operations I TM 18 Thermostat Usually, each zone has a thermostat Set point temperature Impossible to please everyone ASHRAE recommends 71 o F for heating (68-75 o F) 76 o F for cooling (73-79 o F) Location Balance tenant comfort with energy efficiency
19
Foundations of Real Estate Management Module 3: Building Operations I TM 19 Thermal Layering Temperature is measured in the middle 1/3 (on top of the desk) Bottom 1/3 is coolest (space heaters) Heat rises – top 1/3 is warmest
20
Foundations of Real Estate Management Module 3: Building Operations I TM 20 Space Heaters
21
Foundations of Real Estate Management Module 3: Building Operations I TM 21 Heating Involves adding heat
22
Foundations of Real Estate Management Module 3: Building Operations I TM 22 Heating Systems Central Local Fuel sources Electricity Natural gas Heating oil
23
Foundations of Real Estate Management Module 3: Building Operations I TM 23 Heating Heating only around perimeter – not in core Air handler provides cooling to entire building Common perimeter heating systems Electric heaters in perimeter VAV boxes Baseboard heat 2-pipe/4-pipe central heating Radiant heat Under concrete sidewalks and drive lanes Under floor
24
Foundations of Real Estate Management Module 3: Building Operations I TM 24 VAV Box with Reheat Coils
25
Foundations of Real Estate Management Module 3: Building Operations I TM 25 Cooling Involves removing heat
26
Foundations of Real Estate Management Module 3: Building Operations I TM 26 Cooling HVAC systems have 1, 2, or 3 loops Refrigerant loop Chilled water loop Condenser water loop The loops do not mix!
27
Foundations of Real Estate Management Module 3: Building Operations I TM 27 Cooling Refrigeration cycle Refrigerant Compressor Condenser Expansion valve Evaporator
28
Foundations of Real Estate Management Module 3: Building Operations I TM 28 Refrigerant Makes air conditioning and refrigeration possible Absorbs heat efficiently Moves from liquid to gas (add heat) and back to liquid (remove heat) easily Low boiling point: 50-60 o F Gas at room temperature
29
Foundations of Real Estate Management Module 3: Building Operations I TM 29 Refrigeration Cycle
30
Foundations of Real Estate Management Module 3: Building Operations I TM 30 Refrigeration Cycle
31
Foundations of Real Estate Management Module 3: Building Operations I TM 31 Refrigeration Cycle
32
Foundations of Real Estate Management Module 3: Building Operations I TM 32 Compressor Applies pressure Changes refrigerant from low pressure gas to a high pressure, super- heated vapor
33
Foundations of Real Estate Management Module 3: Building Operations I TM 33 Condenser Rejects heat outside Air or water cooled cooled Enters as super-heated vapor Leaves as high temperature, high pressure liquid
34
Foundations of Real Estate Management Module 3: Building Operations I TM 34 Expansion Valve Sprays liquid into fine mist Reduces pressure and cools refrigerant
35
Foundations of Real Estate Management Module 3: Building Operations I TM 35 Evaporator Transfers heat from building to refrigerant Heating refrigerant causes it to boil Heated refrigerant then passes to compressor… and the cycle continues
36
Foundations of Real Estate Management Module 3: Building Operations I TM 36 Closed Loop System The refrigeration cycle is nothing more than changing refrigerant from a liquid to a gas and back to a liquid…over and over again It’s a closed loop system Heat always moves from higher to lower temperature
37
Foundations of Real Estate Management Module 3: Building Operations I TM 37 Single Loop System Refrigeration cycle only Air cooled Condenser loop To condenser outside Air blows against coils to reject heat Like your home air conditioner Split system Heat pump Rooftop unit
38
Foundations of Real Estate Management Module 3: Building Operations I TM 38 Coils
39
Foundations of Real Estate Management Module 3: Building Operations I TM 39 Double Loop System Heat transferred to/from refrigerant using water via bundles System has either Condenser water loop From refrigeration loop to cooling tower Chilled water loop From tenant space to refrigeration loop
40
Foundations of Real Estate Management Module 3: Building Operations I TM 40 Triple Loop System Heat transferred to/from refrigerant using water via bundles System has both Condenser water loop From refrigeration loop to cooling tower Chilled water loop From tenant space to refrigeration loop
41
Foundations of Real Estate Management Module 3: Building Operations I TM 41 Cooling Tower Hot condenser water enters top of cooling tower Large fans help transfer heat Heat is transferred to outside air Cooler condenser water is pumped back inside to start cycle again
42
Foundations of Real Estate Management Module 3: Building Operations I TM 42 Typical Commercial Cooling Systems Water- or Air-Cooled Systems Chillers Self-Contained Units (SCUs) Air-Cooled Systems Rooftop Units (RTUs) Split System Heat Pump
43
Foundations of Real Estate Management Module 3: Building Operations I TM 43 Chiller
44
Foundations of Real Estate Management Module 3: Building Operations I TM 44 Self-Contained Unit (SCU)
45
Foundations of Real Estate Management Module 3: Building Operations I TM 45 Rooftop Unit (RTU)
46
Foundations of Real Estate Management Module 3: Building Operations I TM 46 Split System
47
Foundations of Real Estate Management Module 3: Building Operations I TM 47 Heat Pump
48
Foundations of Real Estate Management Module 3: Building Operations I TM 48 Control Systems Building Automation System (BAS) Energy Management System (EMS)
49
Foundations of Real Estate Management Module 3: Building Operations I TM 49 Controlling HVAC Costs Optimize EMS Use free cooling Pay attention to weather Coasting Control tenant HVAC adjustments Aggressive water treatment Keep all components clean
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.