Download presentation
Presentation is loading. Please wait.
1
Left Side Discharge Pressure Regulator
Remove Cap to Adjust Valve Schrader Valve
2
Adjusting Discharge Pressure Regulating Valve
Unit must be on defrost for adjustment of setting Proper setting for R404a is ~ 240 to 270 psig Use 5/16 inch Allen wrench to adjust CW rotation increases pressure, CCW decreases pressure Replace cap after adjustment
3
Right Side Suction Pressure Regulator & Hot Gas Valve
Electrical connection to Solenoid of Valve Hot Gas Valve Remove cap to adjust suction pressure regulator valve Electrical cable to compressor junction box
4
Adjusting Suction Pressure Regulating Valve
Box temp should be above 5 C Setting should be ~ 30 to 35 psig for R404A Use 5/16 inch Allen wrench to adjust 1 turn changes setting by 2.5 psig CW rotation increases pressure, CCW decreases pressure Run system 15 minutes to confirm setting Be sure to replace cap
5
Filter Dryer & sight glass with protective cover To replace Filter Dryer:
Have new filter ready for installation Perform Low Side Pump down, but make sure to have a slight positive presure Loosen Bracket Loosen flare nuts Replace filter Tighten flare nuts Tighten bracket Open liquid line hand valve
6
Liquid Line Sight Glass & Filter Dryer
Check for moisture in system Observe color in sight glass If yellow replace filter dryer and recycle the refrigerant Run for 12 hours or until sight glass is green, and look for leaks on the suction side If not green after 12 hours, replace filter dryer, recycle and look for leaks again
7
Hot Gas Solenoid Valve for Defrost
Solenoid of the Hot Gas valve Hot Gas valve When energized directs hot gas to the evaporator for evaporator coil defrosting Suction pressure regulating valve
8
High Pressure Switches
If pressure too high switch opens and de-energizes compressor contactor coil Right side compressor high pressure safety switch Unscrew flare fitting to remove switch Left side compressor high pressure safety switch Loom removed to show switch wires
9
Compressor check With condenser contactor disconnected run unit
Discharge pressure should increase until high pressure switch opens Close hand valve on receiver Compressor should pump down to 15 – 20 inches Vacuum or lower Check current on L1, L2 and L3; 7 to 12 Amps is OK
10
TXV Placement and Adjustment
TXV located in unit Proper Bulb location Tightly clamped to suction line After it is properly located and clamped, bulb is wrapped with insulation (not shown) Remember TXV is set at factory and should not need adjustment
11
Thermal Expansion Valve (TXV)
Sensing Bulb Capillary line Power Element Liquid Line in Line out to Distributor Equalizer Line Removable Cap for adjustment
12
TVX Adjustment is Seldom Required
Pull container down to -20 C Remove cap from TX with adjustable wrench Adjust superheat (SH) setting with refrigeration wrench CCW reduces SH and CW increases SH Do not adjust more than 1 turn Let system run and settle out It may take as much as 30 minutes for the system to balance after the adjustment Replace cap
13
Detecting Blockage in Refrigeration System
Blockage is usually caused by dirt, moisture, or TXV power element loosing its charge Blockage can be detected by lower than normal suction pressure and reduced capacity When moisture in the system exceeds the capacity of the dryer to remove it, ice will form in the dryer. This causes a pressure drop and the liquid refrigerant will evaporate. There may be frost on the dryer and/or the liquid line leaving the dryer. There will not always be frost visible, but the liquid into the dryer should be warm and the liquid out should be cold Dirt or moisture may cause the TXV to stick in one position Check this by watching the suction gauge to see if the TXV is modulating. It the suction pressure stays steady the TXV is stuck. The evaporator return air temp must be at -5 C or below to check this. Check for frozen TXV Shut unit down Wait ~ 20 minutes for ice on TXV to melt At start up unit operation should be normal, after running for awhile if the TXV again sticks and does not modulate, then the problem is moisture. If after start up, unit operation has not changed it is most likely dirt in the system or the TXV element has lost its charge
14
Properly Adjusted TXV Conditions
Suction Line from Evaporator Should be frost on suction line Possible frost on suction service valve (not shown) Little or no frost on end of bell Oil sump should feel warm
15
Evaporator Coil with Temperature Probes
Hot Gas Defrost Line Return Air temperature probe Defrost temperature probe
16
Condenser Section with Grill removed
Condenser fan Motor junction box Coils
17
Evaporator Supply Air Discharge
Louvers removed to show supply air port Evaporator fan pulls return air through evaporator coil And blows it through this opening into the cargo area Louvers prevent short cycling of supply air back into evaporator section
18
Liquid Receivers with Sight Glasses
Left Side Right Side
19
Fusible Plug and Purge Valve of Receiver
Hand Valve Purge Valve from rear Fusible Plug from rear
20
Removal of Non-Condensable Gasses
Existence of Non-Condensable Gasses is the major cause of high discharge pressure. Air and Non-Condensable Gasses collect at the top of receiver Refrigeration reclaim equipment must be connected to the purge valve on the receiver Hose from reclaim equipment must be able to depress Schrader valve Remove small amount of refrigerant through reclaim device Observe discharge pressure for 5 minutes Repeat until discharge pressure is normal, saturated discharge pressure should be 11 to 17 degrees C above the ambient If discharge pressure fails to return to normal, reclaim refrigerant charge, pump system into a vacuum and recharge with refrigerant
21
Refrigerant Leak Testing
Check all joints and fittings The preferred method for leak detection is use of an electronic leak detector Leak testing with soap suds will reveal only larger leaks Portable electronic leak detectors are usually used for field testing
22
Mega-Ohm Testing Purpose: test motor insulation with high Voltage DC
A Go-No-go proof test of motor insulation Megger will produce voltage pulse and indicate pass or fail Used to check compressor and fan motors Three basic types: Hand crank, line operated and battery Test Voltage: Device rating up to 100 Vac – test voltage is 100 to 250 Vdc Device rating 440 to 550 Vac – test voltage is 500 to 1000 Vdc Device rating 2000 Vac – test voltage 1000 to 2500 Vdc Caution: Never touch test leads during test and electrically isolate the motor being tested
23
Test Procedure Record nameplate information Select test voltage
To test insulation between lead and earth ground, connect 1 terminal to the lead and the other to a good earth ground To test between a winding and frame, connect 1 terminal to the lead and 1 terminal to ground Test L1, L2 and L3 For hand crank megger, turn at ~ 160 RPM Megger will indicate pass or fail Record test results, test every 8 to 12 months
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.