VARIODYN D1 Webinar – Product training
Michael Köhler International Business Development VARIODYN D1 Webinar – Product training
2
Your Contact: Michael Köhler Business Development International VA/PA Novar GmbH a Honeywell Company Dieselstr Neuss, Germany Mobile:
3
Welcome ! CoModerator today:
The Presentation will be available as download later Axel Hillmann (Lead Sales Support Administration)
4
Please ask your question in the chat window:
Your questions will be not forwarded to others
5
Please answer the question
Are you satisfied with the audio and video quality? – poor, fair, good
6
VARIODYN D1 Webinar – Product training
Michael Köhler International Business Development VARIODYN D1 Webinar – Product training
7
Components
8
VARIODYN D1 - Components
Digital Output Module with 8 loudspeaker lines DOM4-8 Digital Output Module with 24 loudspeaker lines DOM4-24 Digital Call station DCS15 Universal Interface Module UIM System Communication Unit SCU Digital Power Amplifier 2x250W (Class D) 2XD250 2x400W (Class D) 2XD400 Analog Power 2x200W to 2x500W
9
DOM
10
Digital Output Module DOM4-8 DOM4-24
For connection to max. 4 amplifier channels, 2 lines each DOM4-24 For connection to max. 4 amplifier channels, 6 lines each
11
Digital Output Module DAL-Bus
12
Digital Output Module DOM 4-24
PA 1 PA 2 DAL-Bus
13
Digital Output Module DOM 4-8
PA 1 PA 2 DAL-Bus
14
Digital Output Module DOM 4-24
Backup amplifier PA 1 PA 2 DAL-Bus
15
Modular concept Rack 1 Rack 2 Rack 3
16
Backup Organization (DOM 4-8)
one DOM 4-8 + one Backup Amp = Backup for 2 other‘s DOMs
17
Backup Org. (DOM 4-24) – Dynamic!
Die Ethernet (gelb) dürfen und sollen Zusammen laufen. Soll die ETH-Verbindung bestehen bleiben und auch ohne Pfeil dargestellt werden, oder wie ist dies gemeint? one DOM one Backup Amp = Backup for 6 other‘s DOM
18
Backup Organization backup working
19
Back up organization ~ 300 Meter Ethernet Backup RC22 Ethernet
100 V cable (e.g.: 300 m distance (total cable length) 2x 2x4 mm2 for 250 W amp!) Ethernet(*) Backup RC22 Ethernet Backup RC22 Ethernet Backup (*) This mean a complex infrastructure, not a single copper cable; or a fiber
20
Call Station
21
Full duplex intercom function
DCS Call stations Full duplex intercom function
22
Intercom between call stations
OCC Gate A Gate C Gate B
23
New Call Station Housing 584961/62
For one DCSF 12 or DCSF 1 (584961) or For two DCSF 12 or DCSF 1 Or one DCSF and one DKM18 (584962)
24
Simple call station DIGIM1 and DIGIM4
25
Simple call station DIGIM1 and DIGIM4
2 3 Max 40
26
Simple call station DIGIM1 and DIGIM4
1 or 4 button call station max. 4 different zone’s each UIM Input up to 40 call stations in total each UIM Input One call in the same time / UIM input No call stacker function Daisy chain or star cabling possible
27
AMP’s
28
Digital Power Amplifier:
2x250W (Class D) 2XD250 2x400W (Class D) 2XD400
29
2XD250 and 2XD400 More stable design (low thermal factors)
Higher reliability (no or low ventilation) Less maintains (less dust inside) Low BTU (heating) Low power consumption > For the amp it self and for rack cooling! Honeywell developed
30
Network and other Features
31
Ethernet Ethernet is THE world wide standard for Network
Components can be installed anywhere Using Ethernet vs. proprietary cabling(*) means reducing : design cost cabling cost training efforts using existing cables lower the cable length of loudspeaker lines (*) Including also CobraNet, which is a small Standard
32
Ethernet the number of announcements is limited by the
available bandwidth (0,5 MBit per announcement) In a 100Mbit Network < 100 channels the network is permanently monitored Up to 250 DOMs in one network
33
Audio in- and outputs UIM, audio inputs Analogue audio inputs
CD-Player UIM, audio inputs CD-Player Configuration LAN TCP-IP Analogue audio inputs via UIM (2x Line) - via DCS15 (1x Line) Analogue audio outputs via UIM (2x) - via DCS15 (1x)
34
Digital I/O Contacts UIM/CIM DOM Control contacts UIM LAN TCP-IP
Usable as In- or Outputs Control outputs DOM 8 configurable outputs 8x Control contacts CIM 8 contacts BMZ oder z.B. VARIODYN 3000 System Usable as In- or Outputs
35
Audio Memory Audio memory DOM 16 memory places
LAN TCP-IP 16 memory places overall 260 sec. per DOM Audio memory Audio memory SCU - More than 60 channels simultaneously playable - Storage capacity of approx. 120 min for alarm messages memory spaces Storage capacity of approx hours for less critical messages like commercial messages
36
DAL, audio signal processing
CD-Player Configuration LAN TCP-IP Audio signal processing Per audio stream on DAL-Bus - Volume Configurable limiter for microphones (DCS, DCSF)
37
PA, audio signal processing
CD-Player Configuration LAN TCP-IP Per power amplifier channel - Volume High-pass 2nd, 4th, 6th order (Frequency response: 20Hz-20kHz) Low-pass 2th, 4th, 6th order (Frequency response: Delay (0-2000msec) Parametric Equalizer, 8 Bands
38
Volume Control Volume control, AVC - via buttons, contacts
CD-Player Configuration LAN TCP-IP - via buttons, contacts - time-controlled, e.g. lower volume at tram stations during nighttime - Control commands via PC Audio memory Automatic (AVC) by using sensor microphones also background music
39
Interfaces Serial to Notifier Serial to Esser Fire Panels
Serial to BacNet via Multiprotokoll Gateway Via LAN to any other System (VARIODYN PA-Protokoll) LAN TCP-IP ? BMZ oder z.B. VARIODYN 3000 System
40
VARIODYN D1 - Redundant Power Supply
41
VARIODYN D1 - UPS Just two U heigh VARIODYN D1 Design
Up to 210A(!) power on 24 Volt 3 single protected 24V outputs for 3 DOM‘s 6 single protected 24V outputs for 6 amp‘s EN54-4 certified
42
Configuration
43
D1 Designer Graphical programming platform Easy, intuitive handling
Programming of In- and Outputs Time triggers Contact closures etc
45
VARIODYN D1 LAN TCP-Transport CD Player Graphical User Interface PAMMI
DCS15 DCS15 DAL DAL DCS15 DAL CD Player DAL DAL DCS15 ETH DAL LAN TCP-Transport ETH ETH DCS15 Configuration ETH DAL ETH DAL DCS15 ETH ETH Graphical User Interface PAMMI ETH ETH ETH 3rd party PA Systems PIDS Alarm System Communi- cation System other Systems Digital audio storage
46
Cable
47
Easy and fast!
48
D1 Cabling 583491 amplifier cable DOM 583477.21 amplifier output cable
RC 22 backup cable Meter CAT 5 DAL Bus cable (or /83 = 2/3 Meter) Backup AMP Meter CAT 5 network cable (or /88 = 2/3 Meter) UIM DOM AMP AMP
49
Cabling for the DOM
50
Summary
51
VARIODYN D1 - Key Features
Minimum number of components Easy to design Fully monitored in real time Interface to fire panels Network based and scalable High quality audio GUI including DVA
52
VARIODYN D1 - Key Features
More than 50 simultaneous channels Intercom (full duplex) between call stations Time triggered internal events Quick cabling and installing EN compliant EN certified
53
Check Out! Our Webinar’s about acoustics basics I + II and
PAMMI and others Frequency (logarithmic scale) Level 20Hz 200Hz 2kHz 20kHz 160Hz 10kHz
54
Please answer the question
Was this Webinar too long? Was this Webinar useful for you? (Very useful; useful; not useful) If the Webinar wasnt usefull, what can we do better? How long you work already with VARIODYN D1? (1 Month; 6 Month; more than 6 Month)
55
Thank you for your attention