Glenpool South Tank Farm Glenpool, Oklahoma April 7, 2003 Storage Tank Explosion and Fire ConocoPhillips
3
Rick Flint Investigator-in-Charge Dr. Joseph Kolly, Explosion and Fire Nancy McAtee & Dr. Merritt Birky Leslee ShumwaySCADA and Control Systems Frank ZakarMaterials Laboratory Robert Moore &Editors Meg Athey Estimated man hours for the investigation: 4,500 Investigation Team and Support Staff
4
Parties to the Investigation ConocoPhillips Explorer Pipeline Office of Pipeline Safety Glenpool Fire Department
5
12 7 8 9 Tank 11 North
6
131st Street Highway 75 North Tank 11 9 12 8 7 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 138,00 volt power lines
7
Explorer and ConocoPhillips Tank Farms 7 1112 8 9 N 28” Explorer mainline from Texas Explorer 24” line to ConocoPhillips 30” line to tank 11 Explorer Pipeline Glenpool Tank Farm ConocoPhillips Glenpool South Tank Farm 12” crude oil pipeline power lines
8
Tank 11 Dike wall Location of 138,000 volt power lines Pipeline overpressure protection equipment
9
Fire picture here
10
power poles Power lines dike wall
11
Tank 11 Tank 7 Pipeline overpressure protection equipment
13
Tank 7 Tank 11
14
Tank 8: damage from internal fire
15
12 7 8 9 Tank 11 North
16
16
17
Safety Issues Tank operations, including switch loading The adequacy of emergency planning and emergency response by ConocoPhillips and American Electric Power The adequacy of Federal regulations and industry standards for emergency planning
18
Tank operations, including switch loading, at the ConocoPhillips tank farm Safety Issue #1
19
Switch Loading Hazards of switch loading Empty tank that previously contained gasoline was being filled with diesel
20
Flow Tank 11 with the floating roof landed roof support legs 10" diameter pontoons gasoline sump 30” fill & drain pipe bond wires internal floating roof pressure/vacuum vents in floating roof vent openings in fixed roof and shell
21
Tank Operations Diesel is a static charge accumulator Increased risk of a static discharge inside tank 11 Fill velocity and turbulence increase static charge
22
Tank Operations - Flammability Tank operations with gasoline on April 4 to 7 created a flammable mixture inside the tank
23
23 vent openings in tank roof and shell (always open) no flow Gasoline in storage gasoline roof: floating roof support legs mechanical pressure/ vacuum vents in floating roof (closed) tank shell
24
24 closed Flow Gasoline removed (roof floating) gasoline roof: floating
25
25 Flow Gasoline removed (roof landed) roof: landed gasoline open gasoline
26
26 Flow Gasoline added (roof landed) roof: landed gasoline
27
27 roof: floating closed after roof floats Flow Gasoline added (roof floating) gasoline
28
28 Flow Gasoline removed (roof landed) roof: landed gasoline
29
29 No flow Tank empty roof: landed closed
30
30 roof: landed Flow Diesel added (switch load) diesel
31
Conclusion All the conditions necessary for fuel vapor ignition were present in the storage tank at the time of the accident, and the explosion most likely occurred when a static discharge ignited a flammable fuel- air mixture in the space between the surface of the diesel and the floating roof. The extensive damage to the tank is consistent with the flammable fuel- air mixture above the floating roof contributing to the force of the explosion.
32
32
33
Safety Issue # 2 Emergency Response and Emergency Planning
34
Failure of energized power lines and additional fire Unsuccessful management of the electrical hazard Emergency Response Emergency response by American Electric Power
35
No coordinated emergency planning between facility operators Emergency Planning
36
Conclusions The American Electric Power responder did not coordinate his actions with the incident command staff, and American Electric Power did not take effective emergency action.
37
Conclusions (Continued) Because ConocoPhillips Company and American Electric Power did not preplan their response to emergencies near the Glenpool South Tank Farm, the emergency response was unsuccessful in managing the electrical hazard caused by the tank explosion and fire.
38
38
39
Safety Issue #3 Federal Regulations and Industry Standards for Emergency Planning
40
Federal Pipeline Regulations Require operators to prepare an emergency plan Emergency plan must include procedures for notifying appropriate fire, police and other public officials No requirements to coordinate with electric utilities
41
Industry Standards American Society of Mechanical Engineers (ASME) pipeline codes do not require pipeline operators to coordinate with electric utilities Institute of Electrical and Electronic Engineers (IEEE) electrical safety code has no requirements for emergency response planning
42
Conclusion Comprehensive, practical industry guidance for the preparation of emergency plans would help operators of electric systems respond effectively to emergencies involving their utilities.
43
43