Modular Capacity - Test - System CS

Similar presentations


Presentation on theme: "Modular Capacity - Test - System CS"— Presentation transcript:

1

2 Modular Capacity - Test - System CS - 3001

3 Modular test system Easy to operate Expandable up to 4 strings with 192 voltage inputs Block voltage : ± 16,6 VDC, (detection of voltage reversals) 600VDC CAT III (5000VAC test voltage) Parallel test of up to 4 batteries

4 Connection area

5 Connection example Standard 4mm safety connection

6 Bus area

7 Daisy chain connection
Bus connection Daisy chain connection Power supply and communication in a single cable Standard RJ45 cable Each string of modules can have a total connection length of > 100m

8 Connection example of a 24VDC battery
Bluetooth communication

9 Testing of an UPS ( 2 racks with 5 x 4 x 12V-Block)
For ease of contact, not all input channels of a module must be used. Only the blocks on one level of a cabinet need to be connected

10 Maximum installation 1 2 31 32 String 1 String 2 String 3 String 4
RJ 45 CS-3001 Module CS-3001 Module CS-3001 Module CS-3001 Module String 1 DC IN RJ 45 CS-3001 Module CS-3001 Module CS-3001 Module CS-3001 Module String 2 RJ 45 CS-3001 Module CS-3001 Module CS-3001 Module CS-3001 Module String 3 DC IN RJ 45 CS-3001 Module CS-3001 Module CS-3001 Module CS-3001 Module String 4 CS-3001/PU 4 x 192 x 2V-Block

11 Resistance between any input > 2 MΩ (leakage < 0,3 mA)
Safety aspects Resistance between any input > 2 MΩ (leakage < 0,3 mA) 5000 VAC Isolation The system uses no fragile mechanical relays for scanning the block voltages. Semiconductor switches for voltage selection has been eliminated. Defect switches can cause an electric shock, if no protection gloves are used.

12 Capacity Test

13 Capacity Test

14 Capacity Test

15 Capacity Test

16 Capacity Test