Air Conditioning & Refrigeration:
MECH3005 – Building Services Air Conditioning & Refrigeration: Air-side Systems Dr. Sam C M Hui Department of Mechanical Engineering The University of Hong Kong
2
Contents Fundamental HVAC Concepts Air Handling Units
Air System Basics Fan-duct systems Fan modulation & combinations Year-round operation & economizers Fan energy use & outdoor air
3
Fundamental HVAC Concepts
Five subsystems or loops of HVAC Air-side Chilled water Refrigeration equipment Heat rejection Controls
4
33 oC, 28 oC 27 oC 33 oC 25 oC Conditioned space
5
33 oC, 28 oC 27 oC 33 oC 25 oC 13 oC 13 oC Air side system
6
Chilled water system 33 oC, 28 oC 27 oC 33 oC 25 oC 12 oC 12 oC 7 oC
7
Refrigeration equipment 33 oC, 28 oC 27 oC 33 oC 25 oC 12 oC 10 oC
8
Heat rejection 33 oC, 28 oC 27 oC 33 oC 25 oC 12 oC 10 oC 12 oC 49 oC
9
Control Loop 33 oC, 28 oC 27 oC 33 oC 25 oC 12 oC 10 oC 12 oC 49 oC
10
Individual room air-conditioning system
11
Primary air fan coil unit system
12
What type of air conditioning system it is?
Dual duct system
13
Air Handling Units
14
Air Handling Units Terminal unit or device Air handling unit (AHU)
Such as fan coil units, VAV boxes Air handling unit (AHU) Primary equipment of the air system Handle & condition the air, control it to a required state, and transport it Basic components: Supply fan, water cooling coil, filters, mixing box, dampers, controls & outer casing A return or relief fan is optional, so as a humidifier
15
Air Handling Units Types of AHUs: Horizontal or vertical
Draw-through or blow through Factory-fabricated and field built-up Rooftop and indoor Make-up (primary) air Recirculating
18
Air Handling Units Package units Rooftop package units
A self-contained air conditioner Equipped with a DX (direct expansion) coil “Air handler”: the portion inside that handles air Rooftop package units Gas heating / electric cooling Electric heating / electric cooling Heat pump system
20
Air Handling Units Indoor package units Split package units
Factory-assembly unit installed in a fan room or machinery room Floor-mounted or ceiling-mounted Cooling, cooling/heating, heat pump Heat rejection: Connected to an air-cooled condenser, OR Water-cooled condenser Split package units Indoor air handler + outdoor condensing unit
21
Air Handling Units Rating conditions & minimum performance
ARI and ASHRAE standards Rating indices: Energy efficiency ratio (EER) Seasonal EER Integrated part-load value (IPLV) Heating seasonal performance factor (HSPF)
22
Air Handling Units Coils Indirect contact heat exchangers
Heat transfer between air flowing over the coil and water, refrigerant, steam or brine insider the coil Fins: extended (secondary) surfaces Fin spacing and density Water circuits Number of water flow passages
23
Air Handling Units Direct expansion (DX) coil
Refrigerant is fed (e.g. R-22 and R-134a) Air and refrigerant flow: Usually counterflow and cross flow Typical evaporating temperature = 3-10 oC Condensate drain pan (to collect condensation) Performance factors: Face velocity, heat transfer coefficients, air-side pressure drop, physical size
24
Air Handling Units Water cooling coils - dry-wet coil
Chilled water flowing at 4-10 oC Brine or glycol-water at 1-4 oC Temperature rise (typical) = 7-14 oC Water cooling coils - dry coil Sensible cooling (dry); no condensation Poorer heat transfer coefficient Steam heating coil
25
Direct expansion (DX) coil
Water cooling coil
26
Water heating coil Steam heating coil
27
Air Handling Units Air filters Air cleaning and filtration
Operating performance: Efficiency or effectiveness of dust removal Dust holding capacity Initial & final pressure drop Service life Types: low-, medium-, and high-efficiency filters + carbon activated filters
28
Air Handling Units Test methods of air filters Weight arrestance test
For low-efficiency air filters Atmospheric dust spot efficiency For medium-efficiency air filters DOP (dioctyl phthalate) penetration and efficiency test For high-efficiency air filters HEPA (high-efficiency particle air) ULPA (ultra-low penetration air)
29
Activated carbon filter HEPA and ULPA filters
Low efficiency (panel-type) Medium efficiency (bag-type)
30
Air Handling Units Humidifiers Selection of AHUs Steam humidifiers
Air washers Selection of AHUs Face velocity < 3 m/s to prevent entrained droplets Proper size of the equipment (energy efficiency) Medium-efficiency filter >50% dust spot eff.: improve IAQ, prevent smudging & discoloring Air economizer: save energy
31
Steam grid humidifier
32
Air washer
33
Air-side Components EcoAdvisor: Energy Trainer for Energy Managers: HAVC Module 1 [AV 697 E19] HVAC components Distribution equipment Air-side components Dampers, filters, coils, fans, ducts and plenums, terminal units, diffusers, humidifiers, dehumidifiers
34
Air System Basics
35
Air System Basics Fan-duct systems
Flow resistance R, pressure drop Δp and volume flow rate V Duct sections in series: Duct sections in parallel: o
36
Air System Basics Fan-duct systems Terminology
Primary air (conditioned air or makeup air) Secondary air (induced space air, plenum air, or recirculating air) Transfer air (indoor air that moves from an adjacent area) System curve: volume flow vs pressure loss System operating point
37
Air System Basics Fan Laws Speed (n) Volume flow (V)
Total pressure loss (Δp ) Air density (ρ) For air systems that are geometrically & dynamically similar: (D = impeller diameter)
38
Air System Basics System effect Δpts
Its additional total pressure loss caused by uneven or non-uniform velocity profile at the fan inlet, or at duct fittings after fan outlet Due to the actual inlet and outlet connections as compared with the total pressure loss of the fan test unit during laboratory ratings Inlet Outlet
39
Fan system operating point & system effect
40
Air System Basics Modulation of air systems Constant volume system
Volume flow rate remains constant; supply temperature is raised during part load Variable-air-volume (VAV) system Volume flow rate is reduced to match part load operation Modulation curve
41
Fan modulation curve
42
Air System Basics Fan modulation methods
Damper (vary the opening of the air flow passage) Waste energy Inlet vanes (opening & angle of inlet vanes) Low cost; less efficient than following types Inlet cone (peripheral area of fan impeller) Inexpensive; for backward curved centrifugal fan Blade pitch (blade angle of axial fan) Fan speed (using adjustable frequency drives) Most energy-efficient; but more expensive
43
Damper, inlet vanes & fan speed modulation
44
Air System Basics Fan combinations in AHUs
Supply and exhaust fan/barometric damper Used when no return duct or low return pressure loss Barometric relief damper: to prevent excessive high space pressure Suitable for systems w/ no air economizer mode & a low pressure drop in return system
45
Supply and exhaust fans
46
Air System Basics Fan combinations in AHUs Supply and relief fan
Relief fan to prevent excessive high space pressure Usually operated in air economizer mode Outdoor air damper is fully opened; recirculating damper closed Suitable when pressure drop of return system < 75 Pa, or there is a considerable pressure drop in relief or exhaust flow passage
47
Supply and relief fans
48
Air System Basics Fan combinations in AHUs Supply and return fan
Return fan at the upstream of the junction of return, recirculating and exhaust flow passage (ru) Has similar characteristics as supply+relief fan, but a higher total pressure at junction “ru” Careful selection of return fan is needed to avoid excessive pressure in the duct system Suitable when pressure drop of return system > 150 Pa, or those requiring a negative space pressure
49
Supply and return fans
50
Air System Basics Year-round operation of a VAV system
Region I: Refrigeration/evaporative cooling Enthalpy of outdoor > that of recirculating air Region II: Free cooling & refrigeration Enthalpy of outdoor ≤ that of recirculating air Region III: Free cooling, evaporative cooling & refrigeration Region VI: Winter heating
51
Control diagram of a VAV reheat system for year-round operation
52
Year-round operation Region I: Refrigeration/evaporative cooling
Region II: Free cooling & refrigeration Region III: Free cooling, evaporative cooling & refrigeration Region VI: Winter heating
53
Air System Basics Economizer
A device consisting of dampers and control that uses free cooling capacity of either outdoor air or evaporatively cooled water from cooling tower instead of mechanical refrigeration Air economizer: Enthalpy-based Temperature-based Water economizer
54
Air System Basics Fan energy use For each l/s air supplied:
For system using separate outdoor ventilation:
55
Air System Basics Outdoor ventilation air supply Aims
Provide acceptable indoor air quality Achieve energy efficiency in the system ASHRAE Standard (IAQ standard) Demand-based outdoor ventilation air control using CO2 as an indicator CO2 concentration < 800-1,000 ppm A specific indoor air contaminant can also be used
56
Air System Basics Outdoor ventilation air supply
Minimum outdoor air control Type I: uses a CO2 or mixed gas sensor + DDC controller to control the volume flow rate of outdoor air The best one but can be expensive Type II: uses a CO2 or mixed gas sensor + DDC controller to control the ratio of the openings between outdoor and recirculating dampers Suitable for VAV system
57
Air System Basics Outdoor ventilation air supply
Minimum outdoor air control (cont’d) Type III: uses a flow sensor or a pressure sensor + DDC controller to control the dampers to provide nearly constant volume outdoor air intake More complicated & may cause energy waste Type IV: adjust the opening of outdoor damper manually to provide constant volume outdoor air Mainly used for constant-volume systems