Download presentation
Published byMarlee Dowler Modified over 9 years ago
1
Unit 3 Fire Suppression Section 1 Detection and Alarm Systems
2
1. Importance of Fire Detection and Alarm Systems
1.1. Time Element 1.2. Notification a. Type A Manual Alarm b. Type B Automatic Alarm 1.3. Activation Note: Studies with children and notification!
3
2. Types of Detectors 2.1. There are three broad classifications of fire detection: Heat, Smoke & Flame Detectors. 2.2. Fire Detectors are used in a variety of fire prevention and suppression systems.
4
3. Classification of Heat Detectors
3.1. Heat Detectors respond to the excess heat generated in a fire 3.2. Two subclassifications based on operation Fixed Temperature which operate at predetermined temperature Rate of Rise operate based on a specified rate of temperature rise (degrees/min.)
5
4. Smoke Detectors 4.1. Smoke detectors respond to the presence of smoke 4.2. General Information
6
4.3. Classifications of Smoke Detectors
4.3. Two Classifications Photoelectric smoke detectors Ionization smoke detectors
7
4.3. Classifications of Smoke Detectors
Photoelectric smoke detectors
8
4.3. Classifications of Smoke Detectors
Ionization smoke detectors
9
PROPER LOCATION OF SMOKE DETECTORS
VS 19-2 PROPER LOCATION OF SMOKE DETECTORS On Each Level of House Outside Sleeping Areas Dining Kitchen BR BR Bedroom No. 1 Bedroom No. 2 Hallway Dining Room Living Room Bath Basement Living Room Entry Master Bedroom
10
PROPER MOUNTING OF SMOKE DETECTORS
VS 19-3 PROPER MOUNTING OF SMOKE DETECTORS Horizontal Distance from Peak No Closer than 4 inches (102 mm) From Side Wall Best in Center of Ceiling Dead Air Space Mount on Wall at least 4 inches (102 mm) from ceiling No more than 12 inches (305 mm) from ceiling 3 Feet (1m) Best Location Acceptable Location
11
5. Flame Detectors 5.1. Flame detectors respond to the presence of a flame 5.2. General Information 5.3. Principle of Operation
12
6.0 Placement of Fire Detectors
6.1. In general, fire detectors are normally placed on the ceiling or within 12" of ceiling 6.2. Where possible the detectors should be located throughout entire building
13
6.0 Placement of Fire Detectors Cont’d
6.3. Spacing of detectors will vary based on several factors 6.4. Connection to Remote Locations 6.5. Testing & Maintenance of fire detectors
14
7.0 Components to a Fire Alarm System
7.1. Power supply 7.2. Detectors & manual pull boxes 7.3. Signal supervisors
15
7.0 Components to a Fire Alarm System Cont’d
7.4. Local Alarms 7.5. Indicator Boards 7.6. Reference for Alarm Systems
16
Section 2 “Fixed Extinguishment Systems”
Unit 3 Fire Suppression Section 2 “Fixed Extinguishment Systems”
17
1. Introduction to Sprinkler Systems
1.1. Effectiveness of Sprinkler Systems 1.2. Function of Sprinklers 1.3. Advantages of Sprinklers 1.4. Cost of Sprinklers
18
2. Types of sprinkler systems
2.1. There are four major classifications of sprinkler systems
19
2. Types of sprinkler systems
2.2. Wet-pipe Systems Operation of system
20
2. Types of sprinkler systems
Dry Pipe System Operation of system
21
activation / trip pressure for valve
Dry Pipe System Two question to ask: activation / trip pressure for valve is air pressure greater than activation/trip pressure (should be 10 – 15 psi greater) Activation/Trip pressure = 40 psi Air Air pressure should be 50 – 55 psi Water Activation/Trip pressure set by the manufacture 70 psi
22
2. Types of sprinkler systems
2.4. Pre-action Systems Operation of System Advantages over dry pipe system Disadvantage--two systems must both function properly
23
2. Types of sprinkler systems
Deluge sprinkler system Operation of system Uses of Deluge System
24
3. Basic Sprinkler System Components
3.1. Water Supplies Types of water supplies · Public Water · Pressure Tanks
25
Basic Sprinkler System Components
Types of water supplies Gravity feed from tank Easier for water to flow down than up
26
3. Basic Sprinkler System Components
Types of water supplies · Fire pumps · Fire Department Connections
27
3. Basic Sprinkler System Components
Amount of water supply a. Hazard of Occupancy—most important · Light hazard class · Ordinary hazard class Group 1 Group 2 · Extra hazard class
28
Basic Sprinkler System Components
a. Hazard of occupancy Hazard Class Combustibility of Content Amount of Combustibles Heat Liberation Heads Open Light Low Few Ordinary Group 1 Moderate Ordinary Group 2 Moderate - High Extra Hazard Group 1 Very High Many Extra Hazard Group 2
29
3. Basic Sprinkler System Components
Amount of water supply b. Obstructions to water delivery c. High ceilings d. Unprotected vertical openings between floors e. Division of spaces
30
3. Basic Sprinkler System Components
Calculating water supply Q = k √P Where: Q = supply (GPM) k = coefficient of orifice (inside pipe size) P = pressure (PSI)
31
3. Basic Sprinkler System Components
3.2. Sprinkler Piping The piping and type of valve will vary depending on type of system Types of piping Hydraulic design of systems
32
SPRINKLER PIPING public water supply - 8” – 12”
riser (alarms, water flow valve, sprinkler valve) tank (or natural water supply yard main 6” – 8” always below freeze line cross main “open” or “closed” should be “open” feed main sprinkler head branch lines post indicator valve pad lock unlock to close valve public water supply - 8” – 12”
33
3. Basic Sprinkler System Components
3.3. Sprinkler Valves The purpose of a sprinkler valve is to retain & control flow of water and to isolate individual risers.
34
CONTROL VALVE LOCATION
VS 15-4 CONTROL VALVE LOCATION Every system will have two valves: a main water control valve and a sprinkler valve. The main control valve should always be in the OPEN position. Main Control Valve (OS&Y)
35
TYPES OF CONTROL VALVES
VS 15-5 OS&Y (Outside Screw and Yoke) PIV (Post Indicator Valve) WPIV (Wall Post Indicator Valve)
36
3. Basic Sprinkler System Components
3.4. Alarms on Sprinkler Systems Every sprinkler system should have an alarm that sounds when water flows through the system. 3.4.2. Types of Alarms Supervisory signals
37
3. Basic Sprinkler System Components
3.5. Test Connections Two Inch Drain Test Inspectors Test Connection
38
3.6. Sprinkler Heads 3.6.1. Operating Principle
Deflector Frame Arms Release Mechanism (Fusible Link) Lever Arms Valve Cap
39
3. Basic Sprinkler System Components
3.6. Sprinkler Heads Type based on position
40
VS 15-3 SPRINKLER DESIGNS Pendant Upright Sidewall
41
3. Basic Sprinkler System Components
3.6. Sprinkler Heads Type based on activation a. Solder-link b. Frangible bulb c. Fusible pellet
42
Fusible Link (Standard) Fusible Link (Quick Response)
VS 15-2 RELEASING MECHANISMS Fusible Link (Standard) Frangible Bulb Fusible Link (Quick Response) Chemical Pellet
43
3. Basic Sprinkler System Components
3.6. Sprinkler Heads Deflectors Flow rates
44
VS 15-3 SPRINKLER DESIGNS Pendant Upright Sidewall
45
3. Basic Sprinkler System Components
3.6. Sprinkler Heads 3.6.6. Temperature rating of sprinkler heads Non-Colored Ordinary F White Intermediate F Blue High F Red Extra High F Green Very High F Orange Ultra High F
46
3. Basic Sprinkler System Components
3.6. Sprinkler Heads Special service sprinkler heads
47
4. Location and Spacing of Sprinklers
4.1. Fundamental rule Reference on location and spacing: NFPA code 13, Sprinkler Standards
48
4. Location and spacing of sprinklers
4.3. Spacing depends on the class of hazard of occupancy and the type of ceiling construction Light hazard - 15' maximum between sprinklers Ordinary hazard ' ft depending on use of area Extra hazard - 12' maximum
49
4. Location and spacing of sprinklers
4.4. Sprinklers must also be spaced so that each sprinkler does not protect more than a specified area: Light hazard occupancy—floor area/sprinkler maximum of square feet, depending on type of ceiling Ordinary hazard occupancy--max. area per sprinkler square feet, depending on use of space Extra hazard occupancy--90 square feet sprinkler maximum Extra High Hazard 90 ft2
50
4. Location and spacing of sprinklers
4.5. Determine protection area for sprinkler heads using the following formula: As = S X L Where “S” is the distance between heads on the lines and “L” is the distance between branch lines.
51
4. Location and spacing of sprinklers 4. 5
4. Location and spacing of sprinklers Protection area of sprinklers along “walls” As = S X L S is the larger of either twice the distance to the wall or the distance to the next sprinkler head L is the larger of either twice the distance to the wall or the distance to the next branch line. 4 ft AS = S x L S = 3 x 2 = 6 or 10 L = 4 x 2 = 8 or 9 AS = 90 ft 10 ft 3 ft 9 ft
52
4. Location and spacing of sprinklers
4.6. Other location specifications that may influence spacing
53
5. Carbon Dioxide Extinguishing Systems
5.1. Application 5.2. Advantages 5.3. Disadvantage
54
5. Carbon Dioxide Extinguishing Systems
5.4. Storage of CO2 5.5. Delivery Mechanism
55
5. Carbon Dioxide Extinguishing Systems
5.6. Types of fixed systems Total flooding Local application 5.7. Inspection of Systems
56
6. Dry Chemical Fire Extinguishing Systems
6.1. Application 6.2. Operation of system
57
Carbon Dioxide Extinguishing Systems
Types of fixed systems Total flooding apply to an entire room or confined area Local application applying CO2 over the surface of the tank local application Acid Pickling Tank
58
6. Dry Chemical Fire Extinguishing Systems
6.4. Quantity and rate of application is determined by a qualified professional Inspection and maintenance must be completed at least once each year (NFPA Code #17)
59
7. Foam Fire Extinguishing System
7.1. Application 7.2. Inspection and maintenance 7.3. Fire code for foam systems is NFPA # and NFPA #16 for foam-H2 combination systems
60
Foam Fire Extinguishing System
7.4. Types of systems fixed activate with detector head high hazard areas portable fire departments 7.5 Video on Foam mechanical agitation air liquid
61
Unit 3 Fire Extinguishment
Section 3 “Explosion Prevention”
62
1. Introduction 1.1. Principles of Explosion Prevention
a) Venting to relieve the pressure b) Suppression to extinguish or retard the deflagration c) Purging to eliminate the combustible mixture
63
2. Fundamentals of explosion venting
2.1. Location of hazardous operations 2.2. Design of the vent Location of vent is important Size of vent Design variables for vents
64
2. Fundamentals of explosion venting
2.3. Design of vent closures Most effective vent for release of explosion pressure is an unobstructed vent opening Several small vents may be as effective as one large opening as long as total area is the same
65
2. Fundamentals of explosion venting
2.3. Design of vent closures The nearer a vent is located to the point of explosion the more effective it will be If diaphragms (of the same size and thickness) are made thicker then more pressure will be required to rupture them
66
2. Fundamentals of explosion venting
2.4. Maintenance of vents
67
3. Explosion Suppression
3.1. Elements in the system Pressure Detector Suppressors Suppressant Material
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.