A Fundamental Review of Solar Thermal Systems Installation, Sizing and Benefits of a Bradford White Solar Thermal Water Heater Bradford White Solar Thermal Training Program
2
The sun’s rays hits a solar collector, heating the fluid inside. The heated fluid in the collector passes through a heat exchanger, which transfers its heat energy to the surrounding potable water. If an internal or external heat exchanger is not available, the heated collector fluid goes directly into the potable water in the tank. How Does Solar Thermal Work?
3
–One way of expressing the thermal performance of a solar system is by stating the percentage of the load met by solar energy on a month-by-month basis. –Monthly totals can be combined to yield the annual solar fraction, expressed as a decimal percentage (e.g. 0.15 = 15%) –If a solar system has a SF of 0 then there is no solar energy utilized. If it has a SF of 1.0 then all energy provided is from solar. –Dependent on many factors such as load, collector size, climate, etc. –Example, the same solar equipment installed in a home in Arizona may have a SF of 75%, but if installed in Connecticut, it may only have a SF of 30%. Solar Fraction (SF)
4
System Types Active is when a circulator pushes the fluid. Passive is when water temperature difference moves the water. Hot water rises/cold water falls. Open loop is when the potable water goes through the collector to be heated. Closed loop is when the heating fluid is closed off from the potable water and is contained in a loop.
5
Open Loop System
6
Closed Loop System
7
Solar Rating The Solar Rating and Certification Corporation (SRCC) was provides independent testing, rating and certification of active solar collectors and solar domestic water heating systems. Standard OG-100 “Operating guidelines for certifying solar collectors” Standard OG-300 “Operating guidelines and minimum standards for certifying solar water heating systems”
8
OG-300 Certification Standard OG-300 combines the physical testing of collectors and all major components in a solar water-heating system proposed for sale by manufacturer. The standard also provides simulated performance estimates for that system in specific geographical locations. Once a water heater is OG-300 certified, it then becomes ENERGY STAR® certified.
9
Storage Tank –Stores and delivers heated potable water. Collectors –Flat Panel; more efficient in warmer climates –Evacuated Tube; more efficient in colder climates Circulation –Circulators Controls –Thermistors Fluid - the more glycol in the system, the harder the circulator works and lower the heat transfer capability. Solar Thermal System Components
10
Heat Exchange Coil Vitraglas® lined, 1 ½” O.D. carbon steel coil. Single Wall provides greater heat transfer. Double Wall provides additional protection from heating fluid and surrounding water. Because of the large diameter, a smaller and lower cost pump can be installed. Smooth internal surface area limits the amount of mineral deposit, which could decrease heat transfer capabilities. Glycol and toxicity rating of 1 (practically non-toxic) fluid can be introduced into coil.
11
1” NPT female fittings on single wall ¾” NPT female fitting on double wall The coil has a heat transfer area of 14.2 sq ft Stored water volume of 2.7 gallons Because of the material and thickness of the coil, maximum supply temperature from a heating source can be upwards of 240°F Maximum supply temperature from a heating source must not exceed 250 F Heat Exchange Coil
12
Single WallDouble Wall
13
Double Wall Heat Exchange Coil
14
Head Loss Head loss due to friction of water flowing in a pipe is determined in feet of head. As water moves through pipe and fittings, it loses energy to friction. Pumps or circulators provide the energy to make up for this loss “head loss” through the system. The more water you push through the pipes, or the smaller the pipes are, the higher the head loss will be. Higher head loss means larger more expensive pumps.
15
Sizing a Circulator Heat Exchanger Pressure Drop
16
Integrated Mixing Device Features: Push to turn hand wheel prevents accidental temperature change. Included thermo-strip to approximate outlet water temperature. Allows water in the tank to be stored at higher temperatures, increasing usable hot water by as much as 50%, while controlling the hot water outlet at lower temperatures. Additional outlet piping connection to draw off unmixed tank temperature water. Additional intlet piping connection for recirculation water into the mixing device. Additional outlet piping connection to draw off cold water without installing a saddle valve. Teflon® coated internal components to extend product life. Integrated Mixing Device Package
17
Integrated Mixing Device* Mixed Hot Water Outlet ½” NPT Un- Mixed Hot Water Outlet ½” NPT Recirculation Inlet ¼” NPT Cold Water Outlet Cold Water Inlet *ASSE and UPC (IAPMO) Certified Stainless Steel Flexible Connector Push to Turn Hand Wheel
18
100°F to 145ºF Temperature Range Graduation marks to allow easy adjustment. Each increment is 5ºF. Arrow is approximately 120°F
19
Solar Saver® Electric Backup (Open Loop)
20
Models available –No heat exchanger; potable water is circulated through the solar collector. Suitable for frost free locations. Single (upper) heating element Supplied thermistor wires Connections –Potable -- Inlet dip tube; Anodic outlet device –Solar – Dip tubes in top of water heater Alternate side connects in 80 & 120 gallon models. Solar sensor can be mounted by means of threaded stud. Solar Saver® Models
21
Solar Saver® Specification Data Open Loop
22
EcoStor™ Electric Backup
23
Models available –Single Wall Heat Exchanger for increased performance –Double Wall Heat Exchanger for additional protection between the heating fluid and potable water. Single (upper) or Dual Incoloy elements –4.5 or 5.5 kW elements. Integrated Mixing Device for piping flexibility Supplied thermistor wires Two Anodes EcoStor™ Solar Indirect Models
24
EcoStor™ Specification Data Single Wall Heat Exchanger
25
EcoStor2™ Specification Data Double Wall Heat Exchanger
26
EcoStor™ Heat Exchanger Backup
27
Models available –Single Wall Upper Heat Exchanger –Double Wall Lower Heat Exchanger Dual Heat Exchanger Design –Can be connected to a variety of different heating systems. –Solar, space heating, geothermal heating, boiler heating Integrated Mixing Device Supplied thermistor wires Two Anodes Heat Exchanger Backup
28
Solar Thermal
29
EcoStor™ Specification Data Dual Heat Exchanger
30
Dual Heat Exchanger Connections
31
EcoStor2™ Gas Backup Atmospheric Vent
32
Models Available –Natural Gas or Propane Gas –Atmospheric Vent –Double Wall Heat Exchanger –61,000 – 76,000 BTU/hr. input range Honeywell Self Diagnostic Gas Control –Advanced temperature control system –Intelligent diagnostics Integrated Mixing Device Supplied thermistor wires Two Anodes EcoStor2™ Gas Backup
33
EcoStor2™ Specification Data Propane models feature a Titanium Stainless Steel Propane Burner. For propane (LP) models, change suffix “BN” to “SX”.
34
EcoStor2™ Gas Backup Power Vent
35
Models Available –Natural Gas or Propane Gas –Power Vent (3” or 4” PVC, CPVC, ABS) –Double Wall Heat Exchanger –60,000 – 76,000 BTU/hr. input range Honeywell Self Diagnostic Electronic Gas Control –Advanced temperature control system –Intelligent diagnostics –Optional Programmable Setback Control Integrated Mixing Device Supplied thermistor wires Two Anodes EcoStor2™ Gas Backup
36
EcoStor2™ Specification Data Propane models feature a Titanium Stainless Steel Propane Burner. For propane (LP) models, change suffix “BN” to “SX”.
37
EcoStor2™ Gas Backup Atmospheric Vent Ultra Low NOx
38
Models Available –Natural Gas Only –Atmospheric Vent –Double Wall Heat Exchanger –40,000 – 55,000 BTU/hr. input range –Ultra Low NOx radiant burner –Meets the most stringent air quality requirements for allowable NOx emissions in the country Honeywell Self Diagnostic Gas Control –Advanced temperature control system –Intelligent diagnostics Integrated Mixing Device Supplied thermistor wires Two Anodes EcoStor2™ Gas Backup
39
EcoStor2™ Specification Data
40
Determine the Daily Hot Water Demand (Gal.) –If unknown, estimate 30 gallons per person per day. –Determine typical inlet water temperature (°F) and desired outlet temperature (°F). –Calculate the amount of Btu’s needed per day. BTU = Gallons x 8.25 x (Outlet – Inlet) Example: 4 people with 58°F inlet with a 125°F tank 4 people x 30 gallons/day = 120 gallons per day BTU = 120 x 8.25 x (125-58) = 66,330 Btu/day How Do I Size a System? Water Demand
41
Flat panel – (Btu/day/1,000) x 1.1 = ft. 2 of area. –More efficient in warmer climate/summer. Evacuated Tube – (Btu/day/1,000) x 1.3 = ft. 2 of area. –More efficient in cooler climate/winter. –Collector temperature - outside temperature is larger. Calculate the amount of collector surface area. –Flat Panel: (66,330 Btu/day/1,000) x 1.1 = 73.0 ft 2. –Evacuated Tube: (66,330 Btu/day/1,000) x 1.3 = 86.2 ft 2. Other variables exist such as climate and panel location How Do I Size a System? Collector Demand
42
Questions?