1
www.kensaheatpumps.com Ground Loop Design
2
Heat Sources Horizontal ground loops Collector pipework laid horizontally Requires large land area Cost effective Slinkies Pre coiled pipework laid in trenches Requires large land area, but less digging Cost effective Vertical boreholes Closed loop pipework inserted into vertical hole Typically 100-150m deep Most common in commercial buildings Space efficient Surface water (closed loop) o Ideal solution where surface water (eg lake) is available o Extremely efficient and cost effective Open loop Extracts ground water from an underground aquifer Efficient Costly Horizontal ground loops Collector pipework laid horizontally Requires large land area Cost effective Slinkies Pre coiled pipework laid in trenches Requires large land area, but less digging Cost effective Vertical boreholes Closed loop pipework inserted into vertical hole Typically 100-150m deep Most common in commercial buildings Space efficient Surface water (closed loop) o Ideal solution where surface water (eg lake) is available o Extremely efficient and cost effective Open loop Extracts ground water from an underground aquifer Efficient Costly o Ground provides a highly efficient source of heat o Unaffected by air temperature o Recharged by solar energy and rainfall o Ground type (thermal conductivity) needs to be factored into sizing calculations o Important not to over extract – sizing important
3
www.kensaheatpumps.com Ground Loop Design Table 3 of MIS3005 can be used to help design the ground array in conjunction with MCS022 ground heat exchanger look up tables.
4
www.kensaheatpumps.com 3 Bed Semi detached. From room by room heat losses:- Space Peak Heat Load = 5.188 kW (6kW heat pump) Annual Energy load = 11212 kWh/y DHW load = 3438 kW/y Heating System Radiators with a flow temperature of 50C (3 stars)
5
www.kensaheatpumps.com 14650 Kensa Room by room heat loss calculator 6 kW heat Pump at a flow temp of 50C 6 2442 11 1.7
6
www.kensaheatpumps.com Look up extraction tables
7
www.kensaheatpumps.com 14650 Kensa Room by room heat loss calculator 6 kW heat Pump at a flow temp of 50C 6 2442 11 1.7 44 Wet Clay Southwest From MCS 022
8
www.kensaheatpumps.com 3.4 From Heat Emitter Guide 4235.3 96.25 5 481.3 500
9
www.kensaheatpumps.com Property 2 Bed Detached Property Peak Heat Load 3.5kW Annual Energy Load 6580kWh DHW annual load = 2578kWh Underfloor at a flow temperature of 40C (5 stars) SPF 4.1
10
www.kensaheatpumps.com 9158 Kensa Room by room heat loss calculator 4kW heat Pump at a flow temp of 40C 5.1 1796 11 1.7 59 Wet Clay Southwest From MCS 022
11
www.kensaheatpumps.com 4.1 From Heat Emitter Guide
12
www.kensaheatpumps.com Maximum Power Extracted from the ground:- [ Box 2] x 1000 x (1- ( 1/[ Box 7])) =5.1 x 1000 x (1-(1/4.1)) = 5.1 x 1000 x (0.756) = 3856 W Maximum Power Extracted from the ground:- [ Box 2] x 1000 x (1- ( 1/[ Box 7])) =5.1 x 1000 x (1-(1/4.1)) = 5.1 x 1000 x (0.756) = 3856 W
13
www.kensaheatpumps.com 4.1 From Heat Emitter Guide 3856 65.36 5 326.8 400
14
www.kensaheatpumps.com Slinkies Myths: You need less land area – FALSE You need less pipe – FALSE They are less efficient – FALSE They are more likely to freeze the ground than straight pipe – FALSE Facts: You need the same land area as a straight pipe collector There require only a fifth of the digging of a straight pipe collector Quicker, easier and more cost- effective to install Myths: You need less land area – FALSE You need less pipe – FALSE They are less efficient – FALSE They are more likely to freeze the ground than straight pipe – FALSE Facts: You need the same land area as a straight pipe collector There require only a fifth of the digging of a straight pipe collector Quicker, easier and more cost- effective to install
15
Slinkies Horizontal Slinky Trenches Horizontally installed slinkies should be placed in a 1.2m wide by 1.2m deep trench. Vertical Slinky Trenches Vertically installed slinkies should be placed in a 300-400mm wide by 2m deep trench. Separation Distances Each trench should be separated by a minimum of 5m between centres Energy Absorption For every 10m of slinky 1kW of energy can be absorbed from the ground. Trench Layout Trenches do not have to be straight, they can twist and turn as long as the 5m separation distance is maintained. Crossing Services Insulate about 1m either side of crossing point
16
www.kensaheatpumps.com Unrolling a slinky
17
www.kensaheatpumps.com Manifolds Above ground manifolds Compression Joints – Asymmetrical olives Subterranean manifolds Electrofusion joints 40 -32mm EF joints 63mm to the heat pump Kensa Supply An optional expansion vessel can be fitted to the slinky pipework.
18
www.kensaheatpumps.com Pressure testing the slinkies Pressure test with water (generally safer) Remove all the air Pressure Test to EN805 Section 11.3.3.4 (See manual) Pressure test with water (generally safer) Remove all the air Pressure Test to EN805 Section 11.3.3.4 (See manual)
19
www.kensaheatpumps.com Purging the Slinkies
20
www.kensaheatpumps.com Antifreeze samples 2 independent antifreeze samples are required by MCS. Taken from the schrader values an hour apart. Tested using a refractometer and samples returned to Kensa. Beware some refractometers measure concentration some measure freezing temperature 20% concentration or -10C protection 2 independent antifreeze samples are required by MCS. Taken from the schrader values an hour apart. Tested using a refractometer and samples returned to Kensa. Beware some refractometers measure concentration some measure freezing temperature 20% concentration or -10C protection
21
Installation of the heat pump
22
www.kensaheatpumps.com
23
Installation of the heat pump Flow to heating system from heat pump 28 mm OD Return from heating system to heat pump. Connected via ‘Y’ connector 28mm OD Speedfit connection termination. Supply to ground 28 mm OD. Connected via ‘F’ connector with a single 50mm Plasson connection termination. Return from ground 28 mm OD. Connected via ‘L’ connector with a single 50mm Plasson connection termination. ‘Y’ Connector ‘F’ Connector ‘L’ Connector
24
www.kensaheatpumps.com Meter Ready Installations Pipe Diameter (mm) Total length of straight pipework required in return pipe (mm) Total length of straight pipework required in the flow pipe (mm) 15300175 22440175 28560175 35700175 42840175
25
www.kensaheatpumps.com Electrical Connections
26
www.kensaheatpumps.com Simple diagnostics and fault finding.
27
www.kensaheatpumps.com B readings and settings B01 – Heating Distribution Temperature B02 – Temperature of water returning from the ground arrays B03 – Temperature of water going out to ground arrays B04 – Refrigerant pressure
28
www.kensaheatpumps.com Fault Codes
29
www.kensaheatpumps.com Fault Codes