jackie eury senior thesis presentation lighting | electrical 15 april 2015 DENVER POLICE DPT. CRIME LAB.

Similar presentations


Presentation on theme: "jackie eury senior thesis presentation lighting | electrical 15 april 2015 DENVER POLICE DPT. CRIME LAB."— Presentation transcript:

1

2 jackie eury senior thesis presentation lighting | electrical 15 april 2015 DENVER POLICE DPT. CRIME LAB

3 denver crime lab introduction lighting depth lobby south plaza electrical depth photovoltaic array construction breadth structural breadth conclusion

4 building statistics building location location | denver, colorado occupant | denver police department type | laboratory size | 60,000 gsf constructed | march 2011 – july 2012 actual cost | $28 million denver crime lab introduction lighting depth lobby south plaza electrical depth photovoltaic array construction breadth structural breadth conclusion

5 l i g h t i n g d e p t h denver crime lab introduction lighting depth lobby south plaza electrical depth photovoltaic array construction breadth structural breadth conclusion

6 introduction lighting depth lobby south plaza electrical depth photovoltaic array construction breadth structural breadth conclusion i d e n t i t y denver crime lab concept investigation myster y trials discovery teamwork analysi s researc h justice chemistr y

7 l o b b y denver crime lab introduction lighting depth lobby south plaza electrical depth photovoltaic array construction breadth structural breadth conclusion orientation plan section

8 denver crime lab introduction lighting depth lobby south plaza electrical depth photovoltaic array construction breadth structural breadth conclusion concept corebeginning d n a

9 denver crime lab introduction lighting depth lobby south plaza electrical depth photovoltaic array construction breadth structural breadth conclusion qualitative criteria aesthetics TaskE h (lux)Avg:Min Transition- - Day Night 100 50 4:1 Reception1504:1 Lounge1502:1 quantitative criteria lighting power density SpaceAllowance (W/ft 2 ) Lobby1.10 illuminance levels transition welcoming bright

10 introduction lighting depth lobby south plaza electrical depth photovoltaic array construction breadth structural breadth conclusion denver crime lab reflected ceiling plans first floorthird floor

11 denver crime lab introduction lighting depth lobby south plaza electrical depth photovoltaic array construction breadth structural breadth conclusion renderings plan view first floor

12 denver crime lab introduction lighting depth lobby south plaza electrical depth photovoltaic array construction breadth structural breadth conclusion renderings plan view first floorsecond floor

13 denver crime lab introduction lighting depth lobby south plaza electrical depth photovoltaic array construction breadth structural breadth conclusion quantitative data Illuminance average | 206 lux average/minimum | 3.7:1 lighting power density | 1.0 w/sf elumtools calculation

14 s o u t h p l a z a denver crime lab introduction lighting depth lobby south plaza electrical depth photovoltaic array construction breadth structural breadth conclusion plan orientation

15 introduction lighting depth lobby south plaza electrical depth photovoltaic array construction breadth structural breadth conclusion denver crime lab concept individuality uniqueness one of a kind f i n g e r p r i n t

16 denver crime lab introduction lighting depth lobby south plaza electrical depth photovoltaic array construction breadth structural breadth conclusion qualitative criteria relaxation quantitative criteria lighting power density illuminance levels safety TaskE h (lux)E v (lux)Avg:Min Transition – Plaza 625:1 Space Base Allowance (W) Allowance (W/sf) Square Footage Total Allowance (W) South Plaza 1300 0.25500 2400 Space Lighting Zone Allowance (LM/sf) South PlazaLZ47.5 model lighting ordinance

17 introduction lighting depth lobby south plaza electrical depth photovoltaic array construction breadth structural breadth conclusion denver crime lab site plan

18 introduction lighting depth lobby south plaza electrical depth photovoltaic array construction breadth structural breadth conclusion denver crime lab renderings plan view site

19 denver crime lab introduction lighting depth lobby south plaza electrical depth photovoltaic array construction breadth structural breadth conclusion quantitative data Illuminance average | 15 lux average/minimum | 21:1 total watts | 1848 W total site lumens | 18,552 lumens/sf | 3.37 elumtools calculation

20 e l e c t r i c a l d e p t h denver crime lab introduction lighting depth lobby south plaza electrical depth photovoltaic array construction breadth structural breadth conclusion

21 denver crime lab introduction lighting depth lobby south plaza electrical depth photovoltaic array construction breadth structural breadth conclusion system advisor model (sam) modules ManufacturerSunPower Nominal Efficiency19.19% Maximum Power414.8 Wdc Number of Cells128 Length7'-0" Width3'-3" Number of Panels240 ManufacturerSatcon Technology Corp. CEC Weighted Efficiency96.24% Maximum Power (DC)104 kWdc Maximum Power (AC)100 kWac Nominal AC voltage480 V Number of Inverters1 inverter

22 denver crime lab introduction lighting depth lobby south plaza electrical depth photovoltaic array construction breadth structural breadth conclusion module layout solar angles penthouse analysis summary Annual Energy Production160,128 kWh Performance ratio0.86 Electricity Cost without system $92,605 Electricity Cost with system$77,440 Initial Cost$646,431 Payback Period50 + Years Number of Panels240 total savings | $15,165

23 c o n s t r u c t i o n b r e a d t h denver crime lab introduction lighting depth lobby south plaza electrical depth photovoltaic array construction breadth structural breadth conclusion

24 denver crime lab introduction lighting depth lobby south plaza electrical depth photovoltaic array construction breadth structural breadth conclusion cost analysis RS MEANS 2015 COST DATA ITEMCREWQUANTITY 2015 BARE COSTS MATERIALLABORTOTAL INCLUDING OVERHEAD & PROFIT ALT. ENERGY SOURCE, SUNPOWER PHOTOVOLTAIC MODULE, 415 WATT, 73 VOLTS 2240 1,785.00 109.00 454,560.00 522,744.00 SATCON CORP. DC TO AC INVERTER, 480 V, 100 KW 11 41,688.00219.00 41,907.00 48,193.05 PV COMPONENTS, COMBINER BOX, NEMA 3R ENCLOSURE 11191.00109.00 300.00 345.00 FUSE, 15 A FOR COMBINER BOX14018.7510.95 1,188.00 1,366.20 PV RACK SYSTEM, ROOF, NON- PENETRATING BALLAST, 1 PANEL 1240895.0023.50 220,440.00 253,506.00 total cost | $826,154.25 schedule ITEMCREW DAILY OUTPUT LABOR HOURS QTY.HOURSDAYS ALT. ENERGY SOURCE, SUNPOWER PHOTOVOLTAIC MODULE, 415 WATT, 73 VOLTS 28124012015.00 SATCON CORP. DC TO AC INVERTER, 480 V, 100 KW 124140.50 PV COMPONENTS, COMBINER BOX, NEMA 3R ENCLOSURE 142120.25 FUSE, 15 A FOR COMBINER BOX 1400.24081.00 PV RACK SYSTEM, ROOF, NON- PENETRATING BALLAST, 1 PANEL 130.50.52524012615.75 schedule duration | 1 month

25 s t r u c t u r a l b r e a d t h denver crime lab introduction lighting depth lobby south plaza electrical depth photovoltaic array construction breadth structural breadth conclusion

26 denver crime lab introduction lighting depth lobby south plaza electrical depth photovoltaic array construction breadth structural breadth conclusion roof analysis deck type composite | 2VLI20 roof | 1.5B20 module layout

27 live minimum live load | 30 psf dead rigid insulation | 2 psf superimposed dead load | 10 psf composite deck self-weight | 1.97 psf roof deck self-weight | 2.14 psf module weight | 56 lbs denver crime lab introduction lighting depth lobby south plaza electrical depth photovoltaic array construction breadth structural breadth conclusion loads calculations composite deck roof deck snow load | 20 psf

28 denver crime lab introduction lighting depth lobby south plaza electrical depth photovoltaic array construction breadth structural breadth conclusion lightingelectrical constructionstructural c o n c l u s i o n

29 t h a n k y o u a special thanks: Mom & Dad SmithgroupJJR Denver Police Department Shawn Good AE Faculty & Staff Friends and Colleagues Nicolas Cage denver crime lab introduction lighting depth lobby south plaza electrical depth photovoltaic array construction breadth structural breadth conclusion

30 support | lobby

31

32 support | plaza

33

34 support | structural

35 denver crime lab 5am6am7am8am9am10am11am12pm1pm2pm3pm4pm5pm6pm Jan100 66.626241.428430.981926.154824.344124.006925.426231.47743.325666.0323100 Feb100 38.666223.297617.133914.354513.180512.690913.621417.10825.468643.10173.5851100 Mar1009.157114.283532.246891.496881.170570.8323610.9789990.9233882.544057.1934417.043157.1892100 Apr100000000000.5979344.1965711.193929.4424100 May100000000000.1959793.219618.3356421.2989100 Jun100000000000.0184032.415656.3519915.5866100 Jul100000000000.0079142.288216.5403515.3936100 Aug100000000000.2161823.301299.2426321.5792100 Sept100000000001.484565.8334815.110460.0621100 Oct10036.433518.661812.26129.639298.4237.853188.199119.0604914.073623.546747.9667100 Nov100 45.317330.697524.261421.575420.66920.704923.476630.959845.263173.2618100 Dec100 65.418543.080133.36729.034527.261427.322329.946137.698252.293579.0083100 shading loss support | electrical

36 denver crime lab energy analysis annual kWh reduction | 10,000 kWh annual savings | $600.00 support | construction

37 citations IECC 2012 The Lighting Handbook, 10 th edition Vulcraft Manual Revit 2015 RS Means Green Building 2015 images Double Helix. Web. Http://www.Ummo-sciences.Org/en/a037.Htm Figure 2. 2000. Centers for disease control and prevention. By chang gung. Web. M. 1931. By fritz lang. Web. Photograph of author. 2012. Rotterdam. Ciencia hoje. Web.