TEAM II Cooling Tower Analysis By: Cortez Rankin & D. Caruthers
2
Objectives Components of Cooling Tower Air Outlet Velocities and Flow Rates Air Inlet Velocities and Flow Rates Water Inlet and Outlet Data Comparison of Data @ Different Water Inlet Flow Rates
3
Water Cooling Tower
4
Balances Assuming Steady State Operation [IN = OUT] Overall Mass Balance M AO + M WO = M AI + M WI Overall Energy Balance h AO M AO + h WO M WO = h AI M AI + h WI M WI AO=Air Outlet AI=Air Inlet WO=Water OutletWI=Water Inlet
5
Portable Cooling Tower
6
Air Inlet
7
Air Outlet and Water Inlet
8
Psychrometric Chart
9
Air Inlet Data for Water Inlet Flow Rate = 5.1 (l/min) Velocity = 12.2 m/s Wet Bulb Temp. = 18 °C Dry Bulb Temp. = 25.5 °C Area = 0.038 m 2 Relative Humidity = 48% Volumetric Flow Rate= 0.464 m 3 /s
10
Air Inlet Data for Water Inlet Flow Rate = 10.1 (l/min) Velocity = 12.0 m/s Wet Bulb Temp. = 17 °C Dry Bulb Temp. = 25 °C Area = 0.038 m 2 Relative Humidity = 45% Volumetric Flow Rate= 0.456 m 3 /s
11
Air Inlet Data for Water Inlet Flow Rate = 40.3 (l/min) Velocity = 8.0 m/s Wet Bulb Temp. = 19 °C Dry Bulb Temp. = 27.5 °C Area = 0.038 m 2 Relative Humidity = 45% Volumetric Flow Rate= 0.304 m 3 /s
12
Outlet Velocity as a Function of Radius for Water Inlet Flow Rate = 5.1 (l/min)
13
Outlet Velocity as a Function of Radius for Water Inlet Flow Rate = 10.1 (l/min)
14
Outlet Velocity as a Function of Radius for Water Inlet Flow Rate = 40.3 (l/min)
15
Calculate Outlet Air Velocity
16
Formulas Volumetric Flow Rate = (Area)(Velocity) Mass Flow Rate = (Density)(Volumetric Flow Rate)
17
Outlet Air for Water Inlet Flow Rate = 5.1 (l/min ) Area = 0.312 m 2 Volumetric Flow Rate= 1.7 m 3 /s Temp. Dry Bulb= 21 °C= Wet Bulb Temp. Enthalpy = 79 kJ/kg Dry Air
18
Outlet Air for Water Inlet Flow Rate = 10.1 (l/min ) Area = 0.312 m 2 Volumetric Flow Rate= 1.6 m 3 /s Temp. Dry Bulb= 23 °C= Wet Bulb Temp. Enthalpy = 86 kJ/kg Dry Air
19
Outlet Air for Water Inlet Flow Rate = 40.3 (l/min ) Area = 0.312 m 2 Volumetric Flow Rate= 1.0 m 3 /s Temp. Dry Bulb= 31°C= Wet Bulb Temp. Enthalpy = 123 kJ/kg Dry Air
20
Water Data for Water Inlet Flow Rate = 5.1 (l/min ) Inlet Temp.= 52.5 o C Outlet Temp.= 27.7 o C Temp. Change= 24.8 o C Mass Flow Rate= 0.085 kg/s Tons of Cooling= 2.5
21
Water Data for Water Inlet Flow Rate = 10.1 (l/min ) Inlet Temp.= 56.3 o C Outlet Temp.= 31 o C Temp. Change= 25.3 o C Mass Flow Rate= 0.168 kg/s Tons of Cooling= 5.1
22
Water Data for Water Inlet Flow Rate = 40.3 (l/min ) Inlet Temp.= 52 o C Outlet Temp.= 30.4 o C Temp. Change= 21.6 o C Mass Flow Rate= 0.671 kg/s Tons of Cooling= 17
23
Admin Tower Schematic
24
Admin Cooling Tower Front (West) Inlet Dry Bulb Temp = 18 o C Wet Bulb Temp = 12 o C Area = 4.6 m 2 Air Speed = 1.4 m/s Volumetric Flow rate = 6.1 m 3 /s Density of Area = 1.2 kg/m 3 Mass flow rate = 7.3 kg/s
25
Admin Cooling Tower Front (West) Inlet Team 3 Dry Bulb Temp = 33 o C Wet Bulb Temp = 24.5 o C Area = 4.6 m 2 Air Speed = 1.6 m/s Volumetric flow rate = 7.6 m 3 /s Density of Area = 1.1 kg/m 3 Mass flow rate = 8.3 kg/s