Presentation is loading. Please wait.

Presentation is loading. Please wait.

EVD4 - The Smart eVolution Primary distribution circuit-breaker with integrated protection, control and sensors © ABB Group 15. April 2017 | Slide 1 1.

Similar presentations


Presentation on theme: "EVD4 - The Smart eVolution Primary distribution circuit-breaker with integrated protection, control and sensors © ABB Group 15. April 2017 | Slide 1 1."— Presentation transcript:

1 eVD4 - The Smart eVolution Primary distribution circuit-breaker with integrated protection, control and sensors © ABB Group 15. April 2017 | Slide 1 1

2 eVD4: The Smart eVolution Complete integration in a single device
HMI (panel interface) Current and voltage sensor in each pole Measuring Protection and control Communication Equipped with Relion® technology: protection and control unit RBX615 with IEC61850 and Goose 2

3 eVD4: The Smart eVolution Medium voltage vacuum circuit-breaker
Innovation and a sound foundation of proven technology: Since 1987, over 550,000 VD4 circuit breakers have been successfully installed in a wide range of applications, worldwide Based on Relion technology . 3

4 eVD4: The Smart eVolution Reduce time from purchase to commissioning
Standard panel Version with eVD4 4

5 eVD4: The Smart eVolution Versions, specifications, standards
Fixed / Withdrawable for UniGear ZS1 switchgear and PowerCube units Specifications: Up to 17.5 kV rated voltage Up to 2,500 A rated current Up to 40 kA (3 s) breaking capacity Standards: IEC 62271, EMC EN (2000), EN (2007) 5

6 eVD4 - The Smart eVolution Components
© ABB Group 15. April 2017 | Slide 6 6

7 eVD4: The Smart eVolution Sensors
Current sensor Sensor converts primary circuit current and voltage into a signal Rogowski coil measures current Capacitive divider measures voltage Measurements are in class 1: 1/5P Rogowski coil 1/3P capacitive divider Voltage sensor 7

8 eVD4: The Smart eVolution Sensors
Advantages: Absolutely linear voltage and current signals Low potential signal is safer for people and auxiliary equipment Extremely low energy usage Fewer raw materials used Automatic sensor selection, depending on relay configuration 8

9 eVD4: The Smart eVolution RBX615 unit based on Relion® technology
The integrated unit provides protection, control, measuring and monitoring functions for substations. It also protects overhead lines, cable lines and motors. Protection functions adapt to any radial and meshed network, regardless of earthing layout. IEC compliant; supports communication between substation equipment and messaging system (GOOSE) in native mode. Dedicated automatic configuration tool (PCM600) 9

10 eVD4: The Smart eVolution RBX615 unit based on Relion® technology
GOOSE: Generic Object Oriented Substation Event Units based on Relion® technology installed in switchgear communicate with each other and, through a network switch, with the substation’s control system. Communication board: Ethernet, two channels Communication protocols: Native IEC (including GOOSE) TCP/IP Modbus® 10

11 eVD4: The Smart eVolution RBX615 unit based on Relion® technology
Pre-configurations: Feeder 1: Non-directional overcurrent protection and non-directional earth fault protection (current only) Feeder 2: Non-directional overcurrent protection and directional earth fault protection based on measurement of phase voltage values (current and voltage) Feeder 3: Directional overcurrent protection and directional earth fault protection based on measurement of phase voltage values and overvoltage and undervoltage protection (current and voltage) Motor 1: Motor protection with measurement and protection functions based on current (current only) Motor 2: Motor protection with measurement and protection functions based on current and voltage (current and voltage) 11

12 eVD4: The Smart eVolution Human-machine interface (HMI)
HMI allows the integrated unit to be parameterized, and displays the mimic diagram and certain values Large, multi-page double display: Single-line diagram (SLD) page (left) + Standard menu (right) 8 LEDs Power supply: V dc/ac 12

13 eVD4: The Smart eVolution Specific connector for eVD4
Connects auxiliary circuit of the circuit-breaker and integrated unit with auxiliary switchgear circuits Two Ethernet ports transmit digital and communication signals 13

14 eVD4 - The Smart eVolution Advantages
© ABB Group 15. April 2017 | Slide 14 14

15 eVD4: The Smart eVolution Performance improvements and integration advantages
Performance improvements by component harmonization and optimization leading to a MV system simplification and to an increase of the overall reliability. The eVD4 offers specific advantages compared with a standard MV solution in all stages of the panel life cycle 15

16 Advantages along the panel life cycle Specification and ordering
Specification and flexibility: No need to define any parameters for the sensors RBX615 pre-configuration can be customized Supply management: A complete MV solution (CB, Relay and Sensor) can be obtained with just one single order and one single reference 16

17 Advantages along the panel life cycle Installation, Less wiring, Flexibility
The eVD4 is a ready to install solution. The components are internally wired. All the wiring is instantaneously connected to the switchgear through the CB plug. Less effort for engineering and wiring: The switchgear is highly standardized Less risk of errors and increased safety and reliability Easier and faster engineering Shorter and reliable connections Flexibility for last minute modification: The integrated solution is more versatile and flexible. 17

18 Advantages along the panel life cycle Installation, Less wiring, Flexibility – Low Voltage Compartment Standard circuit breakers eVD4 18

19 Advantages along the panel life cycle Testing, Maintenance, Spare parts
Easy and complete testing of the whole measurements chain by primary injection: It is possible to test the whole measurement chain by a primary injection in the CB contacts, easily accessible without any modification in the panel. Easy maintenance, reduced Mean Time To Repair (MTTR): Standard accessories with few variances, readily available for easy maintenance. Self-diagnostic functions System quickly repaired in case of failure (no stops in production) Optimization of the spare parts in stock 19

20 Advantages along the panel life cycle
Testing, Maintenance, Spare parts Easy removable integrated protection and control unit: The unit is fixed in a docking unit by means of screws Facilitates easy access and service

21 Advantages along the panel life cycle Retrofit and revamping
Extremely simple and straightforward solution for retrofitting and revamping: Faster and easier revamping process Flexibility thanks to sensors high range of linearity and RBX615 programmability No need to act on CTs and VTs as they come with the eVD4 Reduced effort for wiring and retesting 21

22 Advantages along the panel life cycle Switchgear simplification and easy operation
Specification Ordering Easy to install Less effort for engineering and wiring Less effort for Factory Acceptance Test (FAT) while increasing safety and reliability Flexibility and easier last minute modifications Extremely simple and straight forward solution for retrofitting and revamping Easy maintenance and reduced Mean Time To Repair (MTTR) Optimization of the spare parts in stock 22

23 eVD4 - The Smart eVolution More than a product
© ABB Group 15. April 2017 | Slide 23 23

24 eVD4: The Smart eVolution Not only a product: Training
Our specialized team helps you get the most out of the integrated circuit breaker: eVD4 Level 1 (Basic): circuit-breaker and basic maintenance Level 2 (Advanced): advanced maintenance Level 3 (Specialist): service activities Integrated protection and control unit (RBX615) Programming control and protection functions (communication, GOOSE, etc.) 24

25 eVD4: The Smart eVolution Not only a product: Customer support
Complete set of documentation and marketing material: All the information you may need on the eVD4 documentation A specific eVD4 support line is available Technical drawings and electrical diagrams available in electronic version 25

26 eVD4 - The Smart eVolution What is coming next
© ABB Group 15. April 2017 | Slide 26 26

27 eVD4: The Smart eVolution Integrated protection and control unit RBX615
New Features for the release 2.0: RS485 CommCard and Modbus RTU Optical Ethernet COM card HMI function keys Automatic relay configuration recovery by the HMI (a backup of the application will be stored in the HMI) Automatic parameterization of the CB condition monitoring function for an effective diagnostic of the CB. eVD4 used with RIO600 to have flexibility in the number of I/Os 27

28 © ABB Group 15. April 2017 | Slide 28 28

29 eVD4 - The Smart eVolution Protection Functions
© ABB Group 15. April 2017 | Slide 29 29

30 eVD4: The Smart eVolution Protection Functions
30

31 eVD4: The Smart eVolution Protection Functions
31

32 eVD4: The Smart eVolution Protection Functions
32

33 eVD4 - The Smart eVolution Digital I/Os
© ABB Group 15. April 2017 | Slide 33 33

34 eVD4: The Smart eVolution Digital Inputs
34

35 eVD4: The Smart eVolution Digital Outputs
35

36


Download ppt "EVD4 - The Smart eVolution Primary distribution circuit-breaker with integrated protection, control and sensors © ABB Group 15. April 2017 | Slide 1 1."