1 OSHA Region IV Electrical Outreach General Industry Photos 29 CFR 1910 Regulations

2 General Industry Photos Standard – 1910.254(d)(9)(iii) Description – Welding lead cable splice were not insulated. All splices and metal parts of cables and parts must be guarded.

3

4 General Industry Photos Standard – 1910.303(b)(1) Description – Building wiring systems were not properly installed. Wiring draped over building surfaces.

5

6 General Industry Photos Standard –1910.303(b)(2) Description – Equipment not installed IAW listing requirements.

7

8 General Industry Photos Standard – 1910.303(g)(1)(iii) Description – Access to circuit breaker panels blocked.

9

10 General Industry Photos Standard –1910.303(g)(2)(i) Description – Live parts exposed.

11

12 General Industry Photos Standard –1910.303(g)(2)(i) Description – The receptacle was not properly installed in the junction box which exposed energized parts.

13

14 General Industry Photos Standard – 1910.303(g)(2)(i) Description – Broken electrical receptacle exposing energized parts.

15

16 General Industry Photos Standard – 1910.303(g)(2)(i) Description – Live parts of 480 VAC electrical system exposed. All live parts are required to be guarded.

17

18 General Industry Photos Standard – 1910.303(g)(2)(i) Description – Front cover removed from circuit breaker panel. Live parts exposed.

19

20 General Industry Photos Standard – 1910.304(f)(5)(v) Description – Portable light with metal guard which is required to be grounded.

21

22 General Industry Photos Standard – 1910.304(f)(5)(v) Description – The ground pin was removed from the electric plug.

23

24 General Industry Photos Standard – 1910.305(a)(2)(iii)(G) Description – Electrical wiring was not protected from damage. Lying across road where cranes and other vehicular traffic could pass over the wiring.

25

26 General Industry Photos Standard –1910.305(b)(2) Description – The faceplate was removed from the receptacle exposing the energized parts.

27

28 General Industry Photos Standard – 1910.305(e)(1) Description – Electrical systems were not designed for wet and damp locations

29

30 General Industry Photos Standard –1910.305(g)(2)(iii) Description – The electrical plug did not have adequate strain relief which causes stress on the contacts.

31

32 General Industry Photos Standard – 1910.305(j)(1)(iv) Description – Electric cords and cables lying in water.

33

34 General Industry Photos Standard –1910.305(j)(1)(iv) Description – The receptacle which was approved for wet and damp locations was damaged.

35

36 General Industry Photos Standard – 1910.307(b)(1) Description – Electrical wiring was not approved for hazardous locations. Paint spray area.

37

38 General Industry Photos Description – Electrical wiring and systems were not installed IAW NEC.