Download presentation
Presentation is loading. Please wait.
Published byBeryl Robyn Sullivan Modified over 9 years ago
1
Frankfurt (Germany), 6-9 June 2011 New challenges in relay testing More complex impedance relay characteristic More complex differential relay characteristic No more than 8 words per line Increased number of functions to test New IEDs require a more accurate simulation of the electrical phenomena Author Name – Country – Session ….. – Paper ID Advanced Distance Relay Modeling and Testing
2
Frankfurt (Germany), 6-9 June 2011 Distance relay modeling Unlike old relays, new impedance characteristics are more complex The test engineer must deeply know all relay features The new Toshiba GRZ100 has a very challenging impedance characteristic
3
Frankfurt (Germany), 6-9 June 2011 The relay characteristic is not just a series of lines and arcs It is the intersection of different comparators A characteristic like thisIs the result of an intersection
4
Frankfurt (Germany), 6-9 June 2011 In RIO format, that shape is defined as LINE 7.212389, 0.7926472, 75 ARC 2.588202, 9.659244, 10, 32.45674, 56.51973 LINE 8.1047, 18, 180 ARC 2.588191, 9.659257, 10, 123.4804, 165 LINE -7.071067, 12.24745, -60 LINE 0, 0, -10 ARC 2.58819, 9.659258, 10, 265, 297.5433 It is evident it is not something that can be easily done by hand.
5
Frankfurt (Germany), 6-9 June 2011 The importance of a library... For this reason, several relay test set manufacturers offer a library The purpose is to automatically define that sequence of arcs and lines which depends on the extension of the circular characteristic And until now, nothing new
6
Frankfurt (Germany), 6-9 June 2011 New ways to define the characteristics The characteristic is always defined as a result of the intersection of different comparator. The result is a series of line and arcs And it represents just one single characteristic... But what if we use two characteristics to represent one ?
7
Frankfurt (Germany), 6-9 June 2011 Use the same (almost) method of the relays... As we already said... So that we can say, if that is zone 1 Zone 1 = Z1 MHO ∩ Z1 QUAD A characteristic like thisIs the result of an intersection of 2 characteristics This MHO And this poligonal
8
Frankfurt (Germany), 6-9 June 2011 So that if the draw two simple char 1. Zone 11: MHO 2. Zone 12: Poligonal The nominal char can simply been calculated as Znom = Min (Zquad, Zmho) The testing software must simply evaluate 2 impedance values and take the minimum
9
Frankfurt (Germany), 6-9 June 2011 In the same way... A Characteristic like the SEL321 will be union of 2 shapes + = In this case: Zone 1 = Z1 MHO U Z1 QUAD and... Znom = Max (Zquad, Zmho)
10
Frankfurt (Germany), 6-9 June 2011 This is very useful in many cases ... Like in the general fault criteria and the General fault criteriaLoad encroachment
11
Frankfurt (Germany), 6-9 June 2011 Conclusion for part 1 This approach will enhance the productiveness of the technicians But it will change the method of exporting the impedance relay nominal characteristic formats like the actual RIO would be insufficient In fact, although it makes possible to define whatever number of zones, it is not giving information whether a single zone is the combination of more shapes.
12
Frankfurt (Germany), 6-9 June 2011 Getting close to a real fault simulation Modern protective relays implement special algorithms to enhance the relay operating time in zone 1. A trip time below 1 cycle is required for EEHA lines. To work properly, the currents seen by the relay must have a smooth change from pre-fault to fault Good simulationBad simulation
13
Frankfurt (Germany), 6-9 June 2011 The DC offset It is not easy to have this simulation at any time It requires the software or hardware to evaluate this equation at every transition Where I 1 = RMS value of the fault current I 0 = instantaneous value of the current just before the fault = Time constant t = Time in seconds, fault occurs at t=0
14
Frankfurt (Germany), 6-9 June 2011 This can be done with Comtrade files ? It is a strategy to perform a single shot test, but... A total of 6 channels With fault duration of 1.2 s sampled at 1 kHz 2 bytes per sample Requires a file of 720 kB to be uploaded With a 10 Mbps or 100 Mbps this can be uploaded very quickly, therefore it might not be a problem
15
Frankfurt (Germany), 6-9 June 2011 But what about developing faults ? A developing fault is a sequence of states where every state depends on what happened in the previous state Due to this, a Comtrade has the limitation that the exact time of transition between states is not certain The exact time of transition determines the DC offset of the currents in the following state
16
Frankfurt (Germany), 6-9 June 2011 The DC offset calculated on the fly Due to this, the DC offset must be evaluated by the hardware itself The firmware of the equipment must be able to elaborate, at high speed, this formula Since the sampling rate of the genaration must be kept relatively high, 10 to 20 kHz, for all current involved in the test
17
Frankfurt (Germany), 6-9 June 2011 Failing to do that, a simulation like the following would become impossible A simulation like thisWill appear like this
18
Frankfurt (Germany), 6-9 June 2011 Conclusion for part 2 Nowaday, testing a relay is not simply a characteristic check Smarter relays require smarter test equipments Smarter test equipment require high speed dedicated processors We have answers to all testing problems may arise in the field.
19
Frankfurt (Germany), 6-9 June 2011 Thanks very much for your attention Mauro Borrielli Doble engineering company Client support engineer Email: mauro.borrielli@doble.nomauro.borrielli@doble.no Web: www.doble.comwww.doble.com
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.