Sound Transmission Class for Masonry Walls

Similar presentations


Presentation on theme: "Sound Transmission Class for Masonry Walls"— Presentation transcript:

1 Sound Transmission Class for Masonry Walls

2 Standard Method for Determining the Sound Transmission Class Rating for Masonry Walls (TMS 0302)

3 TMS 0302 1.0 Scope 2.0 Referenced Standards 3.0 Notations
4.0 Definitions 5.0 Materials 6.0 Construction 7.0 Quality Assurance 8.0 Sound Transmission Class (STC) Rating

4 TMS SCOPE Minimum requirements for STC Field or laboratory standard test methods, or Calculation procedure

5 Sound Transmission Class, STC
TMS DEFINITIONS Sound Transmission Class, STC Single number rating – ASTM E413

6 TMS MASONRY UNITS Shall comply with the following ASTM standards: C34, C55, C56, C62, C73, C90, C126, C129, C212, C216, C652, or C744

7 TMS MORTAR Shall comply with ASTM C270

8 TMS GROUT Shall comply with ASTM C476

9 TMS CONSTRUCTION Shall conform to the requirements: General building code Standard

10 TMS 0302 6.1 PLACING MORTAR AND MASONRY UNITS
Hollow units – face shell mortared head and bed joints Solid units – full mortared head and bed joints

11 TMS 0302 6.2.1 SEALING OPENINGS AND JOINTS
Completely seal through-wall openings. Prior to sealing fill gaps with: Foam Cellulose fiber Glass fiber Ceramic fiber Mineral wool

12 TMS 0302 6.2.2 SEALING OPENINGS AND JOINTS
Completely seal partial-wall penetration openings and inserts.

13 TMS 0302 6.2.3 SEALING OPENINGS AND JOINTS
Seal the following w/elastomeric joint sealants (ASTM C920): Control joints Expansion joints Top of walls and roof Roof assemblies

14 TMS 0302 6.2.3 SEALING OPENINGS AND JOINTS
Fill joint space behind sealant with: Mortar Grout Foam Cellulose fiber Glass fiber Mineral wool

15 TMS 0302 (Commentary) FIG. 6.2.1 ACOUSTICAL LEAKS

16 TMS 0302 (Commentary) FIG. 6.2.2 SEALING AROUND PENETRATIONS AND FIXTURES

17 TMS 0302 8.0 SOUND TRANSMISSION CLASS RATING
Determine in accordance with: 8.1 Laboratory testing – ASTM E 90 8.2 Field testing – ASTM E413 8.3 Calculation

18 TMS 0302 8.3 CALCULATION For walls greater than 3 inches
STC = 0.18W (Eq.1) W = Wall Weight, psf

19 TMS 0302 (Commentary)

20 TMS 0302 (Commentary) FIG 8.3-1 WALL WEIGHT VS. STC

21 TMS 0302 TABLE 8.3-1

22 TMS 0302 (Commentary) TABLE 8
TMS 0302 (Commentary) TABLE – CALCULATED STC RATINGS FOR CONCRETE MASONRY WALLS

23 Given: W = wall weight = 41 psf STC = 0.18W + 40 STC = 0.18(41) + 40
EXAMPLE Given: W = wall weight = 41 psf STC = 0.18W + 40 STC = 0.18(41) + 40 STC = 47.4

24 NCMA TEK 13-2

25 NCMA TEK 13-2