Fire Sprinkler Earthquake Protection – Sway Bracing
2
Abstract Earthquake sway bracing for fire sprinklers will become normative in the EN12845 Annex Building structures are protected against earthquakes and so should the life safety system of fire sprinklers
3
Abstract Fire sprinkler protection provided thru:
Joint flexibility Proper clearances Sway Bracing Sway bracing consists of: Lateral Longitudinal 4Way
4
Abstract Brace design is based on the amount of sprinkler pipe weight within a zone of influence (ZOI) for a given horizontal seismic load (“g” force) Requires calculations and submittals to AHJ’s showing brace meets design loads
5
Abstract Brace assembly strength is limited to the load capacity of the weakest component Requires 3rd party load testing & certification
6
Today’s Presentation Importance of bracing fire sprinklers
Brace assembly components General rules for brace placement
7
Importance of Bracing Fire Sprinklers
8
FM Global - Understanding the Hazard
“Lack of Earthquake Bracing on Sprinkler System”
9
10 Year Period (FM Global)
561 earthquakes worldwide $315 million (USD) in damages facilities $560,000 (USD) average loss 50% of average loss is due to sprinkler system failure
10
How Damage Occurs Building movement is different than the fire sprinkler pipe Unbraced fire sprinklers damage may occur by: Hitting walls, suspended ceilings or other building systems Fittings break due to twisting Couplings can separate or leak during excessive bending, rotation or movement
11
Additional Concerns Protecting against loss from fire or water leakage is a critical towards recovery from an earthquake Time for water leak discharge to fill a 14 ft x 14 ft (4.3m x 4.3m) room to depth of 1 foot (30cm) based on 50 psi (3.4 bar):
12
Ways to Avoid Sprinkler Damage
Bracing Flexibility Clearance Other Considerations Brace suspended ceilings Weak brace and/or hanger attachments Anchoring of equipment, tanks & racks
13
Costs to Brace 3 – 4% if installed with the sprinkler system
Retrofit costs vary widely from an estimated $100 - $500 USD per brace location
14
Importance of Sprinkler Bracing - Summary
Critical after earthquake protection against: Water leaks Fires Decreases loss of: Property Function / use of facilities Increases life safety
15
Brace Assembly Components
16
Sway Brace Components Structure Attachment Brace Brace Clamp
17
Structural Attachments
CSBUNIV – Universal Structural
18
Structural Attachments
CSBBARJ – I-Beam Attachment
19
Structural Attachments
CSBIB – Adjustable I-Beam Attachment
20
Structural Attachments
CSBMA – Multi Attachment
21
Brace Clamps – Lateral Only
CSBQIKCL – Quick Grip Jr CSBQG – Quick Grip
22
Brace Clamps – Lateral & Longitudinal
CSBEZU and CSBSTU Universal Brace Clamp
23
General Rules For Brace Placement
24
Lateral Bracing
25
Lateral Bracing What: Where: Feed and cross mains (any size)
Branch and other piping > 2 ½” (65mm) diameter Where: 40 ft o.c. (12m) maximum spacing On the last length of pipe at the end of a main Within 6 ft (1.8m) of the end of the pipe
26
Lateral Bracing
27
Lateral Bracing Can act as longitudinal brace if installed within 2 ft (0.6m) of piping braced longitudinally Note that Pipe A Diameter > Pipe B Diameter
28
Longitudinal Bracing
29
Longitudinal Bracing What: Where: Feed and cross mains (any size)
Branches > 2 ½” (65mm) diameter NFPA 13 Not Required FM DS 2-8 Required if longer than 40 ft (12.2m) Where: 80 ft (24.2m) o.c. maximum spacing Within 40 ft (12.2m) of the end of the pipe or change in direction
30
Longitudinal Bracing
31
Longitudinal Bracing Can act as a lateral brace if installed within 2 ft (0.6m) of piping braced laterally
32
Riser Bracing Riser tops exceeding 3 ft (0.9m) in length
Maximum Spacing = 25 ft (7.6m) o.c.
33
Thank You Any Questions??