Download presentation
Presentation is loading. Please wait.
Published byNancy French Modified over 9 years ago
2
Arthur Miller, CMS, RCT HVACR Training Consultant www.kam-associates.com info@kam-associates.com
3
OUTLINE 1.Air Flow Terminology 2.Classification of Duct Systems 3.Duct Design Methods 4.Fans 5.Ducts 6.Air Flow & Issues with Design of Ducts 7.Filters 8.Conclusion(s) & Solution(s)
4
A ’PRACTICAL APPROACH’ ALONG WITH SOME THEORY
9
3 ¼ x 12 wall stack
10
Who is Liable? A.The contractor – from design to installation to service B.The filter manufacturer C.The building owner D.Nobody
11
AIR FLOW TERMINOLOGY
12
CFM Volume or Quantity of air measured in Ft 3 /min
13
FPM Velocity of the air measured in Ft/min
14
STATIC Resistance to the air flow measured in inches of water column (“w.c.)
15
Classification of Duct Systems 1.Low Pressure System - up to 2” w.c. 2.Medium Pressure System - up to 6” w.c. 3.High Pressure System - up to 10” w.c.
16
Duct Design Methods 1.Velocity Method 2.Static Regain Method 3.Equal Friction Method
17
Velocity Method 1.Select velocity for main and branch ducts. 2.Determine duct sizes. 3.Determine frictional pressure drops. 4.Select a fan.
18
Static Regain Method 1.Select velocity for main ducts. 2.Velocities are selected so the static pressure at each take-off offsets the pressure loss of the preceding section of ductwork. 3.Select a fan.
19
Equal Friction Method 1.Selection of friction loss. 2.Volume of air is known. 3.Duct is sized based on 1 and 2 above. 4.Select a fan or fan is selected.
20
FANS The ‘HEART’ of the air delivery system
21
Relationship between STATIC and CFM in respect to a FAN
22
Are they A.a direct relationship B.an indirect relationship C.neither
23
STATIC CFM
24
STATIC CFM
25
two configurations of fans
26
1. AXIAL 2. CENTRIFUGAL
27
First, the Axial Fans
28
Definition? What makes an axial fan an axial fan?
29
ANSWER Discharge Air Flow PARALLEL to shaft of motor/fan (NO change in direction)
30
TYPES 1.tubeaxial 2.vaneaxial 3.propeller
31
TUBEAXIAL 1.operates at pressures up to 16” wc 2.wheel turns faster than propeller fan 3.efficiency up to 65%
32
VANEAXIAL 1.operates at pressures up to 20” wc 2.uses guide vanes to improve efficiency and pressure 3.most energy efficient fan
33
PROPELLER 1.operates at low speeds 2.handles large volumes of air at low pressure and at free delivery 3.efficiency is usually less than 50%
34
Performance of PROPELLOR Fans
35
PROPELLOR FAN What is the LOADING component on a PROPELLOR fan? A.CFM B.FPM C.STATIC
36
STATIC
37
This ‘LOAD’ is then imposed on the motor. How will the motor respond?
38
STATIC AMPS
39
STATIC AMPS
40
APPLICATION(S)
41
(1)The condenser on an air conditioner is very dirty. What will happen to the: fan delivery in cfm? fan motor amp. draw?
42
Fan delivery in cfm Increases Decreases Remains the same
43
Fan delivery in cfm Increases Decreases Remains the same
44
Fan motor amp. draw Increases Decreases Remains the same
45
Fan motor amp. draw Increases Decreases Remains the same
46
(2)What about a filter on an ice machine condenser? What will happen to the: fan delivery in cfm? fan motor amp. draw?
47
Fan delivery in cfm Increases Decreases Remains the same
48
Fan delivery in cfm Increases Decreases Remains the same
49
Fan motor amp. draw Increases Decreases Remains the same
50
Fan motor amp. draw Increases Decreases Remains the same
51
(3)Consider a window fan.Is ductwork connected to the fan? 1. YES 2. NO
52
(3)Consider a window fan.Is ductwork connected to the fan? 1. YES 2. NO
53
Now, the Centrifugal Fan
54
? Definition? What makes a centrifugal fan a centrifugal fan?
55
ANSWER Discharge Air Flow PERPENDICULAR to shaft of motor/fan
56
Types of Centrifugal Wheels 1.Backward Inclined (BI) 2.Air Foil Wheels (AF) 3.Forward Curve Wheels (FC) 4.Radial Blade Wheel
57
Backward Inclined (BI)
58
1.used with high pressure systems 2.high flow 3.high efficiency 4.noisy Backward Inclined (BI)
59
Air Foil Wheels (AF)
60
1.used with high pressure systems 2.high flow 3.highest efficiency 4.noisy Air Foil Wheels (AF)
61
Forward Curve Wheels (FC)
62
1.used with medium pressure systems 2.high flow 3.best for moving large volumes against low static 4.quiet Forward Curve Wheels (FC)
63
Radial Blade Wheel
64
1.used with high pressure systems 2.medium flow 3.best for moving air against high static and contaminated airstreams Radial Blade Wheel
65
Performance of CENTRIFUGAL Fans
66
CENTRIFUGAL FAN What is the LOADING component on a CENTRIFUGAL fan? A.CFM B.FPM C.STATIC
67
CFM
68
This ‘LOAD’ is then imposed on the motor. How will the motor respond?
69
CFM AMPS
70
CFM AMPS
71
MOVIE TIME
73
APPLICATION(S)
74
How would you answer the following questions regarding CENTRIFUGAL fans?
75
(1)An addition has been added to a building and the duct system has been added onto include this addition. What will be the: A.fan delivery in cfm? B.fan motor amp. draw?
76
Fan delivery in cfm Increases Decreases Remains the same
77
Fan delivery in cfm Increases Decreases Remains the same
78
Fan motor amp. draw Increases Decreases Remains the same
79
Fan motor amp. draw Increases Decreases Remains the same
80
(2) As the air filter gets more contaminated, what will be the: A.fan delivery in cfm? B.fan motor amp. draw?
81
Fan delivery in cfm Increases Decreases Remains the same
82
Fan delivery in cfm Increases Decreases Remains the same
83
Fan motor amp. draw Increases Decreases Remains the same
84
Fan motor amp. draw Increases Decreases Remains the same
85
(3)You remove a supply air panel on a ‘hot’ day just to cool you off. What will be the: A.fan delivery in cfm? B.fan motor amp. draw?
86
Fan delivery in cfm Increases Decreases Remains the same
87
Fan delivery in cfm Increases Decreases Remains the same
88
Fan motor amp. draw Increases Decreases Remains the same
89
Fan motor amp. draw Increases Decreases Remains the same
90
‘CENTRIFUGAL’ FAN PERFORMANCE
91
Fan Performance depends on (1)CFM (2)Outlet Velocity (3)Static Pressure (4)RPM (5)Brake Horsepower
92
Determining Fan CFMs (1)Using a Fan Curve (2)Using a Fan Chart (3)Using a Fan Law (4)Using Instruments
93
(1) Using a Fan Curve
96
Relationship between STATIC and CFM in respect to a fan
97
STATIC CFM
98
STATIC CFM
99
Relationship between STATIC and CFM in respect to the duct system
100
STATICCFM
101
STATIC CFM
105
1 HP 3 HP 5 HP New Operating Point Original Operating Point
106
(2) Using a Fan Chart
109
PSC Motor
110
ECM Motor
111
And now, the new kid on the block. Dec Star Movie
117
Using a Fan Law 1.six fan laws 2.HVACR is affected by one of them
118
The physics of air flow dynamics dictates the following: CFM – varies as the fan speed Static – varies as the SQUARE of the speed HP – varies as the CUBE of the speed
119
APPLICATION If we increase the cfm’s by 20%, what will be required of the motor speed(rpm)? + 20%
120
If we increase the cfm’s by 20%, what will happen to the static in the system? + 40%
121
If we increase the cfm’s by 20%, what will happen to the horsepower required from the motor? + 80%
122
Using Instruments 1.Anemometer 2.Velometer 3.Manometer with Pitot Tube 4.Balometer
123
So why all the fuss about fans ?
124
Because they must deliver a volume of air that satisfies two requirements:
125
a.Equipment Efficiency b.Customer Satisfaction
126
AIR FLOW
127
So how much CFM can you ‘shovel’ into a duct?
128
That takes us to the DUCT CALCULATOR
129
‘Rule of Thumb’ Design Static Pressures.10 (.08) for SUPPLY AIR duct.08 (.06) for RETURN AIR duct.08 (.06) for HEAT PUMP SUPPLY duct.06 (.04) for HEAT PUMP RETURN duct
131
Furnace Fan External Static Pressure.5”w.c. for the furnace fan, then subtract any external components:
132
ACCA Manual D Component Static Pressure 1.Air conditioner coil =.25”w.c. 2.Filters =.10”w.c. 3.Electric heaters =.10”w.c. to.20”w.c. 4.Humidifiers =.10”w.c. 5.Supply Outlets =.03”w.c. 6.Return Inlets =.03”w.c. 7.Dampers =.03”w.c.
133
Example #1 Furnace fan =.50”w.c. less AC coil =-.25”w.c. less air filter =-.10”w.c. less supply registers =-.03”w.c. less return grilles = -.03”w.c. less dampers = -.03”w.c. left for duct system =.06”w.c.
134
Example #2 Furnace fan =.50”w.c. less AC coil =-.00”w.c. less air filter =-.10”w.c. less supply registers =-.03”w.c. less return grilles = -.03”w.c. less dampers = -.03”w.c. left for duct system =.31”w.c.
135
Designing the Duct System Length of duct - measured Fittings - Equivalent Length tables Velocity Factor - Equivalent Length tables
136
Supply and Return Plenums
137
Take-off fittings
139
Velocity Factor EL Values Fitting012345 or more 354555657080 203035404550 65758595100110
140
Velocity Factor EL Values Fitting012345 or more 354555657080 203035404550 65758595100110
141
CONCLUSION The equivalent length(EL) of the duct system has a direct relationship to the STATIC
142
FILTERS
143
Filters in relation to the SYSTEM
144
STUDY ASHRAE Published October 2012 by John Proctor, P.E. Member ASHRAE
145
California Energy Commission field research Two year old homes Most common replacement filter used is a 1 in. pleated filter
146
Air Conditioning Contractors of America’s Manual D assumes pressure drop through a filter to be approx. 0.10 in. w.c.
147
Field installations showed PD far in excess of 0.10 in. w.c.
148
Static pressures for 34 split AC/furnaces
149
Metric Filter PD Return P S Total ESP Mean: in. w.c. 0.282 - 0.417 0.887 Range: in. w.c. 0.275 – 0.792 - 0.143 – - 0.928 0.533 – 1.21 Static pressures for 34 split AC/furnaces
150
Metric Filter PD Return P S Total ESP Mean: in. w.c. 0.282 - 0.417 0.887 Range: in. w.c. 0.275 – 0.792 - 0.143 – - 0.928 0.533 – 1.21 Static pressures for 34 split AC/furnaces
151
Metric Filter PD Return P S Total ESP Mean: in. w.c. 0.282 - 0.417 0.887 Range: in. w.c. 0.275 – 0.792 - 0.143 – - 0.928 0.533 – 1.21 Static pressures for 34 split AC/furnaces
152
Metric Filter PD Return P S Total ESP Mean: in. w.c. 0.282 - 0.417 0.887 Range: in. w.c. 0.275 – 0.792 - 0.143 – - 0.928 0.533 – 1.21 Static pressures for 34 split AC/furnaces
153
Research results of PD for 53 ducted systems.
154
Filter face area required for 0.05”w.c. PD at 400 cfm/ton for one manufacturer’s line of filters 16 x 25 = 400 in 2
155
Filter face area required for 0.05”w.c. PD at 400 cfm/ton for one manufacturer’s line of filters
156
The following two charts are tests performed by Kevin O’Neill. HVAC Service Manager Carolina Clg. & Plbg. Surfside Beach, SC
161
CONCLUSION every system has air flow issues
162
CONCLUSION Unfortunately there will always be those who: 1. will not keep up with technology. 2. have always done it this way. 3. don’t need to know that. 4. will do it the least expensive way.
163
SOLUTIONS All designers of air flow systems need to check the manufacturer’s specs. of equipment before designing a system.
164
SOLUTIONS Filters may be a point of interest for poor performance of equipment and comfort.
165
SOLUTIONS The consumer is getting smarter about our industry and making demands on us.
166
SOLUTIONS Professionalism has to be promoted inside and outside the industry.
167
SOLUTIONS Continuing Education
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.