1 Capital City Fire/Rescue Fire Marshal’s Office

2 Sprinkler System Plans (Submit 3 sets of plans) Fire Suppression Systems Review apparatus and emergency access Ensure project meets Fire & Life safety requirements

3 2009 IFC Adopted by CBJ 2012 IFC To be adopted by State Fire Marshal 2015 CBJ + ALASKA STATE FIRE MARSHAL Amendments TITLE 19 Referenced Standard

4 Fire Apparatus Roads Minimum width of 20 feet Dead-End Fire Apparatus Access Roads Requirements: 150’ or less No turnaround required 151’ -500’ 120’ hammerhead, 60’ “Y”, or 96’ diameter cul-de-sac

5 Options available for fire apparatus turnaround

6 Minimum Required Fire-Flow (gpm) depends upon Construction Type & Square Footage Hydrant Location, Distribution and Spacing depend upon Fire-Flow Requirement (gpm) Example: A 4,000 sq.ft., Type V-B building has a Fire-Flow of 2,000 gpm. A 2,000 gpm Fire-Flow requires a minimum of 2 hydrants, spaced no more then 450, with a 225 ’maximum distance on road frontage to a hydrant to a hydrant

7 NFPA 13R requirements provide for a level of protection that allows occupants to escape a building in the event of a fire. NFPA 13 provides protection to not only get people out to safety, but also to control or extinguish the fire – saving the building and its contents.

8 Sprinkler systems with 20 or more heads are required to be monitored by a fire alarm.

9 Knox Box required for any Structure that has a suppression or fire alarm system Knox-Vault meets both shunt trip requirement AND Knox Box requirement for new construction.

10 FDC Any Fire Department Connection shall be marked with FDC sign FIRE LANE shall be marked with signage indicating “NO PARKING – FIRE LANE”

11 Fire Department Connections shall be protected with approved locking caps