RBF AND SVM NEURAL NETWORKS FOR POWER QUALITY DISTURBANCES ANALYSIS Przemysław Janik, Tadeusz Łobos Wroclaw University of Technology Peter Schegner Dresden University of Technology
2
2 Contents Increased Interest in Power Quality RBF and SVM Neural Networks Space Phasor Basic Disturbances Simulation of Voltage Sags Conclusion
3
3 Interest in Power Quality Deregulation of the electric energy market Growing need for standardization Equipment has become more sensitive Equipment causes voltage disturbances Power quality can be measured
4
4 Interconnections
5
5 Space division by classical BP algorithm and RBF network Back Propagation AlgorithmRBF Neural Network
6
6 Radial Basis Function
7
7 Radial Basis Function RBF Neural Network Formulation of the Classification Problem X+, X- classes xinput vector radial function
8
8 SVM Neural Networks Support Vector Machines Formulation of the Classification Problem
9
9 Learning of SVM networks Hyperplane Equation Finding the Minimum
10
10 Dividing hyperplane and separation margin Separation Margin Support Vectors
11
11 SVM characteristics linearly not separable data sets can be transformed into high dimensional space to be separable (Cover’s Theorem) Avoiding of local minima (quadratic programming) Learning complexity doesn't depend on data set dimension (support vectors) SVM network structure complexity depends on separation margin (to be chosen)
12
12 Space Phasor (SP)
13
13 Basic Disturbances Outages (Duration and Frequency) Sags Swells Harmonics Flicker (Voltage Fluctuation) Oscillatory transients Frequency variation Symmetry
14
14 Parametric equations of basic disturbances Oscillatory Transient Flicker Harmonics Sudden Swell Sudden Sag Pure Sinusoid EquationEvent
15
15 Parameters variation Signals number In each class: 50 Totally:300 EventParameters variation Pure SinusoidAll parameters constant Sudden Sagduration 0-9 T, amplitude 0.3-0.8 pu Sudden Swellduration 0-8 T, amplitude 0.3-0.7 pu Harmonicsorder 3,5,7, amplitude 0-0.9 pu Flickerfrequency 0.1-0.2 pu, amplitude 0.1-0.2 pu Oscillatory Transient time const. 0.008-0.04 s, period 0.5-0.125 pu
16
16 Voltage sags Sags deepness 0.4 Sags duration 0.032 s 00.020.040.060.080.1 -0.5 0 0.5 1 time [s] U [p.u.] -1.5-0.500.511.5 -1.5 -0.5 0 0.5 1 1.5 real part imaginary part
17
17 Oscillations Time constant 0.0176 s Oscillations period 0.0053 s 0.020.040.060.080.1 -1.5 -0.5 0 0.5 1 1.5 2 time [s] U [p.u.] -2012 -1.5 -0.5 0 0.5 1 1.5 real part imaginary part
18
18 Flicker Flicker amplitude 0.12 Frequency 8 Hz 00.050.10.15 -1.5 -0.5 0 0.5 1 1.5 time [s] U [p.u] -1.5-0.500.511.5 -1.5 -0.5 0 0.5 1 1.5 real part Imaginary part
19
19 Classification results of SVM
20
20 Classification results of RBF 0.975 1.0 0.975 Classification results of SVM
21
21 Sags originating in faults
22
22 Voltage sags 00.020.040.060.080.1 -1.5 -0.5 0 0.5 1 1.5 x 10 4 time [s] U [V]
23
23 Conclusion and future prospects Automated PQ assessment needed SVM based classifier appropriate for automated PQ disturbances recognition Network models for wide parameter changes Research work do be done with real signal