1 Greg Nolan Mark Pelton Mike Bannister Presented By
2
29 years in Co-op property management Over 300 REAC inspections performed Regional Maintenance Supervisor REAC Inspector training Over 75 inspections in the 90’s Registered Cooperative Manager MAHC trainer for 10 years 2
3
60 REAC inspections Performed 9 years as a Regional Property Manager MAHC trainer for 9 years Certified Apartment Property Supervisor Registered Cooperative Manager 3
4
12 years as a Property Maintenance Supervisor Assisted in over 12 REAC inspection Improved REAC scores from 60’s to 90’s Awarded Maintenance Supervisor of the Year by Kirkpatrick Management Co. Turned property around from non performing to performing and cash flowing 4
5
How to schedule, prepare & conduct Scoring Deficiency Items The report How to appeal-instructions 5
6
6 WHAT IS REAC?
7
Acronym for R eal E state A ssessment C enter 7 *HUD’s way of assessing Safe, Decent & affordable housing What is the purpose of a REAC? To give oversight on the physical condition of subsidized properties.
8
Reverse auction-Mortgage Inspection Agreed upon day of inspection-who can schedule-one person in the company Period of Performance Rescheduling Inspection/Delaying Inspection Site is undergoing Rehab-any type Natural Disaster-Tornado/flood/fire 8
9
9 PREPARING FOR REAC
10
When to Start After last REAC 3 months before scheduled or anticipated REAC date. 10
11
Documents Needed Measurement of walkway by square feet, parking lots & roadways by sq ft. Property Map & Rent Roll Notice of Inspection Show Lead Based Paint Inspection Report & 5 member files showing LBP Disclosure form Occupancy Rate 85% and above 11
12
12 # of Units: 87 # of Vacants: 13 74 Step 1: Subtract Number of Vacants from the number of units. *74 is total number of OCCUPIED UNITS Step 2: Divide # Occupied units by Total # of Units 74 ÷ 87 = 85.057471% - Occupation Calculation
13
Know your property Schedule unit inspections Inspect, Repair, Highlight Schedule exterior inspections Assess scope of work How many work orders What work will be done by staff, contractors, or members. Cost of performing work: (concrete patching, drywall repairs) What was your last score? Have you completed unit inspections since the last REAC inspection Did you fix items noted in last REAC inspection report? 13
14
14 REAC SCORES
15
100-903 years 89-802 years 79-601 year 59-31Failing, not necessarily referred to enforcement center 30 & belowComplete failure-automatically referred to enforcement 15
16
The DEC take action against owners that do not live up their responsibility of providing safe, clean and sanitary housing DEC Actions Include Abatement of federal subsidies Civil money penalties Foreclosure on properties Referral to U.S. Attorney’s Office 16
17
Level 1 Deficiency – Lowest amount of points Level 2 Deficiency – Higher amount of points Level 3 Deficiency – Even higher amount Exigent Health and Safety Deficiency - Highest 17
18
18 CONDUCTING THE INSPECTION
19
Relationship with inspector 2 people to perform inspection with inspector Understand REAC Protocol Maintain good relationship with inspector Talk about common interest Diversion Tactics Have a copy of the compilation bulletin with you Ask inspector to show you the definition of the deficiency Carry a maintenance package with you 19
20
Maintenance package Light bulb 9V batteries Screwdriver and pliers Switch plates and outlet covers Breaker blanks Paperclip 20
21
21 SITE DEFICIENCIES
22
If it’s there, it must function as it is designed to function. Fencing – Perimeter and building 3 to 4 Deficiencies Retaining walls Damaged or leaning 22
23
Grounds ◦ Overgrown/penetrating vegetation ◦ Erosion/Rutting ◦ Ponding Site Drainage Parking lots ◦ Cracks ◦ Ponding ◦ Potholes/loose material ◦ Settlement heaving 23
24
5/17/2011 Play Areas Damaged play area Broken Equipment/Benches Walkways /steps Cracks/settlement/ heaving Spalling Broken or missing handrail 4 or more steps Refuse disposal Damaged enclosure Inadequate storage 24
25
Graffitti Level 1 – 1 place Level 2 – 2 to 5 places Level 3 – 6 or more Litter – Excess Have a groundsman picking up trash always in sight of the insp. Mailboxes/Project Signs. Sign damaged and cannot be read Mailbox damaged or cannot lock 25
26
26 EXTERIOR
27
If it’s there, it must function as it is designed to function. Fire Escapes – Missing components or blocked Foundation Cracks/gaps Spalling/exposed rebar Lighting Bulb or fixture broken/missing 27
28
Roofs Shingles Vents gutters soffitts Walls cracks/holes peeling paint Caulking chimney 28 Windows ◦ Broken ◦ Sills ◦ Bars ◦ Paint & Screens Doors ◦ Hardware & frame ◦ Surface & screen ◦ Caulk
29
29 SYSTEM HITS
30
If it’s there, it must function as it is designed to function Water Leaking spigots Misaligned flu Missing T&P valves Fire Protection Sprinkler head Fire extinguisher Disposable Rechargeable Pull stations HVAC System Fuel leaks Misaligned flu 30
31
Sanitary System Broken pipes Clean out covers Elevators Not operable 31 Emergency power ◦ Lights don’t work Electrical system ◦ Missing breakers ◦ Blocked ◦ Frayed Wiring ◦ Cover missing
32
32 UNITS
33
If it’s there, it must function as it is designed to function. Blocked Egress -doors & windows-Biggest Inside Hit Bathroom- faucets, tubs, drains, exhaust fans, toilets Doors Surface & Frame Hardware Floors Carpet or tile % is bad Kitchen Plumbing & Cabinets Refrig. & Exhaust fan 33
34
Windows Hardware & Sill Seal, lockability, broken glass Stairs Treads & Railing Patio/porch/balcony Laundry area Dryer vent Washer pipes and drain 34
35
35 Lighting ◦ Must work – carry bulb Electrical ◦ Outlets ◦ Covers ◦ Switches
36
36 COMMON AREAS
37
Maintenance Garage Office Clubhouse or Community Room Exercise Room Pool & Playground If an area has utilities it is inspectable 37
38
38 Exigent Health & Safety
39
Electrical Hazards Emergency/Fire Exits Air Quality Flammable Materials- Gas lines, propane, charcoal fluid Garbage Debris 39
40
Hazards-Tripping, Sharp Edges Infestation Misaligned Flu in hot water heater or furnace Will not enter a unit present with bed bugs 40
41
Smoke detectors that are inoperable or missing will be noted on the REAC report as a EH&S violation that has to be mitigated within 24 hours of inspection, but, it is NOT a scoreable item. 41
42
Cable trip hazards are non scoreable. 42
43
43 APPEALING A SCORE
44
Technical Review- A technical review may be requested if during the inspection an objectively material error occurred that if corrected would result in an improvement of the properties overall score. Building data errors Unit count errors Non existent deficiency errors Received within 30 days 44
45
Database Adjustment A request for database adjustment initiates a review of the results of a physical inspection. A database adjustment may be requested for circumstances affecting the inspected property that are out of the ordinary, reflect an inconsistency with ownership or are allowed by city state code. Received with 45 days 45
46
46 REAC REFERENCES
47
www.hud.gov/offices/reac www.hud.gov/offices/reac Technical Assistance Center-1800-245-4860 DCD 2.3a Public Version User Guide Compilation Bulletin REAC Class in Washington, DC Questions/Comments 47
48
48
49
49
50
What Category does a leaking water spigot fall into? a. Unit b. Site c. Systems d. Exterior 50
51
Screens are one of the major things to fix before a REAC inspection. True False 51
52
Broken glass found on the property is an exterior Deficiency True False 52
53
Foundation cracks are a relatively small hit on an inspection True False 53
54
A Blocked egress is the largest hit you can take inside of a unit True False 54
55
You have 48 hours to fix all Exigent Health and safety violations True False 55
56
A broken splash block falls into what category a. Unit b. Exterior c. Systems d. Site 56
57
Which of these is not an exigent health and safety violation a. Open breaker port b. Misaligned Water heater flu c. Missing outlet cover d. Massive hole in Bedroom wall 57
58
The deficiency “erosion” is only found by large rutting areas or large areas of soil being washed away? True False 58
59
There are 3 areas you can be cited for a deficiency on a Unit window True False 59
60
Playground benches are not inspectable. True False 60
61
Playground mulch or associated material is not inspectable. True False 61
62
All Breaker boxes must have doors True False 62
63
What is the occupancy % value that HUD is looking for to keep from inspecting vacant units? a. 84% b. 92% c. 77% d. 85% 63
64
Project signage must be readable from at least 20 ft away or it is deficient True False 64
65
Graffiti, Level 3 must have at least 4 areas of occurrence. True False 65
66
If you remove a broken swing from the playground area, then you cannot be cited for it True False 66
67
All fire extinguisher must be tagged by a certified fire protection company True False 67
68
If a retaining wall is damaged but is not a safety risk then there is no deficiency True False 68
69
Trip Hazards only applies to concrete sidewalks True False 69
70
An exterior GFI is a large electrical deficiency True False 70
71
If a bed is blocking 1 of two windows in a bedroom, it is still a blocked egress True False 71
72
If you remove an A/C from a window and the window will not stay open by itself, it is considered a blocked egress. True False 72
73
It is not possible to receive a deficiency in a breaker box where all of the breakers and/or blanks are present True False 73
74
What is the distance according to HUD that a discharge tube on a water heater can be from the floor. a. 12 inches b. 24 inches c. 20 inches d. 18 inches 74
75
Fire pull stations can be inspected by the property True False 75
76
On an exterior wall, a crack or gap that is more than 3/8 inches wide, 1/8 inch deep or 6 inches long is still a relatively small hit in terms of points. True False 76
77
Garbage inside of a unit is not a deficiency True False 77
78
A lamp in front of a bedroom window constitutes a blocked egress True False 78
79
GFI’s that deliver voltage but do not test are still considered a deficiency True False 79