Presentation is loading. Please wait.

Presentation is loading. Please wait.

Low-Expansion Foam System Design

Similar presentations


Presentation on theme: "Low-Expansion Foam System Design"— Presentation transcript:

1 Low-Expansion Foam System Design
Unit 4 Low-Expansion Foam System Design

2 Standard for Low Expansion Foam
NFPA 11 Standard for Low Expansion Foam

3 Flammable or Combustible???
Which one is safer? Flammable or Combustible???

4 Flammable Liquids Flammable liquid is defined as a liquid that has a flash point below 100ºF and having a vapor pressure not exceeding 40 psi What is flash point? Lower Flammable Limit What is vapor pressure? Closed container, vapor-air mixture above the liquid

5 Combustible Liquids Combustible liquid is defined as a liquid that has a flash point at or above 100ºF

6 Low-Expansion Foam “Low-expansion foam systems are used when a blanket of foam is needed to float on the horizontal surface of a flammable or combustible liquid.” Limited vertical surface protection Use when Coating and O2 Displacement are the preferred method of extinguishment

7 Low-Expansion Foam (cont.)
Coating Separates the fuel from the flame Blocks admission of air to the combustion process (i.e. oxygen dilution/separation of the fire) Cools the surface of the fuel

8 Low-Expansion Foam (cont.)
Low-Expansion foam is an appropriate substitute for water when water is heavier than the Flammable/Combustible liquid being protected. Specific gravity

9 Expansion Ratio

10 Expansion Ratio Low Expansion Foam Up to 20:1 Typically 8:1
Medium Expansion Foam 20:1 to 200:1 Typically 100:1 High Expansion Foam 200:1 to 1000:1 Typically 500:1

11 Expansion Ratio (cont.)
The expansion ratio of foam is computed by measuring the volume of the foam produced after water and air are added and comparing that volume to the original volume of foam concentrate used Low-Expansion Foam = up to 20:1 of the hazard

12 The Components of Foam

13 Components of Foam Air Water Foam Concentrate
Contained within Foam bubbles Water Delivered at a specified density in GPM/SQ.FT Foam Concentrate Injected into the water stream at a specific percentage

14 Components of Foam (cont.)
Foam concentrate is usually stored in drums or barrels 1st - the Foam Concentrate is mixed with water to make a Foam Solution 2nd - the Foam Solution flows through the piping system to the hazard location 3rd - the Foam Solution is mixed with air (disch. devices) at the specified rate to make FOAM “It’s like blowing bubbles”

15 Types of Foam

16 Types of Foam Protein Foam Fluoroprotein Foam (FFFP)
Aqueous Film-Forming Foam (AFFF) Alcohol-resistant Foam Chemical Foam

17 Protein Foam Expansion ratio between 8:1 and 10:1
Protein-based animal additives (hooves, feathers) Hmm, Hmm, Good!… Can be effective on hydrocarbon fires, but absorbs fuel and tends to fail, no film What does hydrocarbon mean? Organic Compounds that contain only carbon and hydrogen (i.e. Natural Gas, Petroleum, Coal, etc)

18 Protein Foam (cont.) Shorter shelf life
More frequent replacement compared to other types of Foam May not maintain “floating” above the fuel

19 Fluoroprotein Foam Protein Foam Contains fluoroprotein additives
Less absorption of fuel Film-Forming fluoroprotein (FFFP) More effective than regular Fluoroprotein Produces a film barrier between the foam and the fuel

20 Protein-based Foams(Summary)
Ranked by Effectiveness Film-Forming Fluoroprotein Foam (FFFP) Fluoroprotein Foam Protein Foam

21 Aqueous Film-Forming Foam (AFFF)
Synthetic Foam Recommended for flammable liquids in storage tanks Thin aqueous film that separates the foam from the fuel Readily available Foam of choice for many applications including Aircraft Hangars protection

22 Alcohol-resistant Foam
Used for the protection of alcohol-based flammable liquid fires Effective because the alcohol in the flammable liquid does not collapse the foam bubbles (water absorption) like other foams Forms a polymeric membrane between the foam and the fuel

23 Chemical Foams Depends on chemical reaction within the Foam Solution to create air bubbles (Foam) Obsolete due to AFFF and FFFP

24 Proportioning Methods

25 Proportioning Methods
Foam Concentrate must be mixed with water by a Foam Proportioner Ensures proper expansion Ratio and proper proportions Example 6% Foam Concentrate 6% Foam Concentrate, 94% Water

26 Types of Proportioners
Venturi /In-Line Proportioner Pressure Proportioner Balanced Pressure Proportioner

27 Venturi /In-Line Proportioner
Water moves past the metering orifice, thus creating negative pressure at the orifice that forces (pulls) Foam Concentrate into the water stream of the Venturi Foam is dependent on metering orifice size, but is typically 1%, 3%, or 6% mix

28 Pressure Proportioner
Draws a portion of incoming water stream into the tank holding the Foam Concentrate This is done in an effort to pressurize the tank where the foam concentrate is stored Collapsible bladder holds the Foam Concentrate Water increases the amount of pressure on the bladder tank, thus forcing foam concentrate out of the bladder and towards the proportioner

29 Balanced Pressure Proportioner
Uses an atmospheric foam concentrate tank Uses a pump to pressurize the concentrate and force it toward the proportioner A proportioner that balances the pumped concentrate pressure to the water supply pressure, mixing the two at the correct ratio

30 Types of Foam Systems

31 Types of Foam Systems Mobile and Portable Apparatus Semi Fixed Systems
Fixed Foam Systems

32 Mobile and Portable Apparatus
Fire Departments Hand (portable) F.D. Truck Wheeled Platform (Mobile) Selection of Foam or Foam Equipment should match the expected flammable or combustible liquid

33 Semi Fixed Systems Permanent Foam makers and outlets
Spaced as needed or required Piped to a connection Located a safe distance from hazard Semi Fixed Piping used in conjunction with mobile or portable foam equipment Mobile or portable foam equipment should be able to serve multiple semi fixed piping installations Detection system, continuously attended central station, on-site fire brigade is recommended

34 Fixed Foam Systems This course is focused on Fixed Foam Systems
Automatic Self-contained No manual intervention Specifically fixed storage tank foam F.P. and fixed aircraft hangar F.P.

35 Storage Tank foam fire protection
Four types of protection systems we will discuss in FET-222 Subsurface injection Surface application Seal protection for floating roof tanks Dike protection

36 Subsurface Injection – Low Expansion Foam Systems

37 Subsurface Injection Foam Systems
Storage tank w/fixed permanent roof Prevents the collection of rainwater above or below flammable/combustible liquid Foam is applied below the surface of the liquid, and floats to the top of the fuel surface

38 Subsurface Injection Foam Systems
#1 Dedicated foam line Piping and nozzles at bottom of tank with nozzles in the liquid, dedicated solely to foam injection Nozzle spacing provides uniform disbursement of foam to surface of the liquid (more gentle and uniform than surface application of foam) Not practical for existing tanks #2 Injection into product (liquid) line Tapped directly into the tank product line Practical for existing tanks

39 Subsurface Injection Foam Systems (cont.)
High back-pressure foam makers required on both types of subsurface injection types

40 Design Methods for Subsurface Injection Foam Systems
Step #1-Calculate fuel surface area The circular area of the exposed fuel at the upper level of the tank Area=(pi)(r)^2 Step #2-Determine application rate (R) and discharge time (T) See Figure 3-8

41 Design Methods for Subsurface Injection Foam Systems (cont.)
Step #3-Calculate minimum foam discharge rate Foam Discharge rate Dgpm=(Area) (Rate) D=foam discharge rate (gpm) A=tank surface area (Step #1) R=application rate (See Figure 3-8)

42 Design Methods for Subsurface Injection Foam Systems (cont.)
Step #4-Calculate foam concentrate quantity Foam Concentrate Quantity Q=(A)(R)(T)(%) Q=primary foam concentrate quantity (gal) A=tank surface area (Step #1) R=application rate (See Figure 3-8) %=concentrate percentage for foam selected 1%(0.01), 3%(0.03), (6%(0.06)

43 Design Methods for Subsurface Injection Foam Systems (cont.)
Step #5-Determine the number of subsurface foam application outlets See Figure 3-9 Step #6-Determine supplementary protection requirements See Figure 3-10 # of addl. hose streams x 50gpm See Figure 3-11 (# of addl. hose streams) x (50gpm) x (Operating Time) x (%)

44 Design Methods for Subsurface Injection Foam Systems (cont.)
Step #7-Determine total discharge rate Dt=D+Ds Step #8-Determine total foam concentrate quantity Qt=Q+Qs Step #9-Hydraulically calculate the system

45 Break

46 Surface Application - Low Expansion Foam Systems

47 Surface Application Low Expansion Foam Systems
Surface application discharge devices are designed to roll a thin blanket of foam over the surface area of the fuel with fixed discharge outlets permanently located above the fuel surface See Figures 3-12, 13A, 13B in textbook There are two types of discharge devices

48 Surface Application Low Expansion Foam Systems (cont.)
Discharge devices Type I Outlet Discharge Devices Designed to deliver foam onto the liquid surface in a very gentle fashion Two types Porous Tubes – tube overcomes diaphragm pressure and drops into tank from the Foam Chamber Foam Trough – Chute securely attached to the inside of the tank, “like pouring concrete” These outlets are designed to extinguish fire with a minimum of Foam-producing materials.

49 Surface Application Low Expansion Foam Systems (cont.)
Discharge devices (cont.) Type I Outlet Discharge Devices Considered obsolete because nearly all currently manufactured foams are suitable for use with Type II discharge outlets

50 Surface Application Low Expansion Foam Systems (cont.)
Discharge devices (cont.) Type II Outlet Discharge device Designed to deliver foam (less gently than Type I Outlets) onto the liquid surface, but to lessen submergence of the foam and agitation of the surface Commonly called Foam Chambers Most Foam Chambers are of a Type II discharge outlet design, since they are normally suitable for use with modern foams

51 Seal Protection for Floating Roof Tanks

52 Seal Protection for Floating Roof Tanks
What is a floating roof? A floating roof floats on the surface of the flammable liquid, rising and falling as the liquid is added to or removed from the tank The floating roof allows no space between the bottom of the roof and the surface of the liquid, no vapor buildup What is seal protection? A system that involves building a dam around the perimeter of a floating roof and filling the seal area with low expansion foam

53 Seal Protection for Floating Roof Tanks (cont.)
What part of the floating tank gets Foam protection? The space between the edge of the floating roof and the perimeter of the tank The (weather) seal that covers this area requires Foam Protection This involves building a “Dam” of Foam around the perimeter of the floating roof and the tank Some cases require Foam Distribution Piping to penetrate the (weather) seal Seal must be able to hold the Foam

54 Seal Protection for Floating Roof Tanks (cont.)
Spacing of Discharge devices Top of Seal protection (foam dam) Foam dam height 12 inches, Outlets-40ft max Foam dam height 24 inches, Outlets-80ft max Protection below Seal (pipe penetration of seal) Mechanical Shoe seal, Outlets-130ft max Tube seal, Outlets-60ft max typically Foam dam required when 6 in or less between top of roof and tube

55 Dike Protection Low Expansion Foam Systems

56 Dike Protection Low Expansion Foam Systems
Containment dike for tank farms will often have a supplemental Low Expansion Foam System The dike area is flooded with Foam that will float on top of any flammable liquid that may have been spilled within the containment area See Figure 3-19, Plan view

57 Dike Protection Low Expansion Foam Systems (cont.)
A dike protection system may also be recommended as supplemental protection fixed cone roof (FCR) floating roof tank (FRT) dike area Systems can be portable or mobile under certain guidelines

58 Dike Protection Low Expansion Foam Systems (cont.)
Design Procedure Calculate dike area Note: If a tank is installed with its bottom mounted to the floor of the dike, then the surface area of the tank may be deducted from the total dike area Determine application rate and discharge times per NFPA 11 Calculate foam discharge rate and concentrate quantity Determine the number of foam discharge devices required

59 Dike Protection Low Expansion Foam Systems (cont.)
Design Methodology Step #1 Calculate dike area Step #2 Determine application rate(outlets & monitors) Determine discharge times(outlets & monitors)

60 Dike Protection Low Expansion Foam Systems (cont.)
Step #3 Calculate foam discharge rate Calculate concentrate quantity Step #4 Determine # of foam discharge devices required N=(2L+2W)/30 See page 11-19, NFPA 11

61 Low Expansion Foam Systems for Aircraft Hangars

62 Low Expansion Foam Systems for Aircraft Hangars
Aircraft that are stored or serviced in an aircraft hangar contain large amounts of flammable fuel Servicing the aircraft offers numerous opportunities for the spilled fuel to ignite

63 Low Expansion Foam Systems for Aircraft Hangars (cont.)
NFPA 409 Standard on Aircraft Hangars Low expansion foam systems not only smother flammable liquid pool fires on the floor, but effectively coat the aircraft skin with an effective exposure protection barrier.

64 Low Expansion Foam Systems for Aircraft Hangars (cont.)
Hangars are classified by three groups Group I, Group II and Group III Aircraft hangar fire protection design can consist of low expansion foam systems Ceiling protection (coats skin) Aspirated foam water nozzles (Air) vs. Non-aspirated sprinklers Underwing protection (WOM) Water Oscillating monitors Supplementary Hose protection

65 Truck Loading Rack Protection

66 Truck Loading Rack Protection
NFPA 11- Standard for Low Expansion Foam NFPA 16- Standard for the Installation of Deluge Foam-Water Sprinkler and Foam-Water Spray Systems NFPA 16A- Standard for the Installation of Closed-Head Foam-Water Sprinkler Systems The point where flammable and combustible liquids are pumped from storage tanks to a truck See Figure 3-25, Page 69

67 Hazards Associated with Truck Loading Racks
Most dangerous portion of the manufacture of a flammable or combustible liquid Pumping the liquid involves Pressurization of the hose line that transmits the liquid Pump could fail Hose could burst or become dislodged from the connection to the truck

68 Hazards Associated with Truck Loading Racks (cont.)
Numerous other ignition sources: Smoking Electrostatic charges Truck Battery

69 Fire Protection Strategy for Truck Loading Racks
Roof protection Foam-water sprinklers or Foam-water spray nozzles at the roof of the truck loading rack. Typically, at a maximum of 100 sq.ft.(10’ x 10’) i.e. Extra Hazard Goal of Roof Protection To provide complete protection of the drainage area The drainage area is the curbed area designed contain spilled flammable or combustible liquids as it flows towards floor drains. Note: Drainage area may not always coincide with the Roof area. The hazard area is always the drainage area, not the roof area.

70 Fire Protection Strategy for Truck Loading Racks
See Figure 3-28 Additional nozzles are aimed directly at the point of connection of the hose to the truck Additional nozzles are aimed beneath the truck to enable the sweeping of liquid from beneath the truck See Figure 3-29

71 Summary Use Expansion ratio – Low Expansion Components of Foam
Protection of Flammable or Combustible liquids (Two-dimensional) Expansion ratio – Low Expansion Up to 20:1 Components of Foam Foam concentrate, Water, Air Types of Foam Protein, Fluoroprotein, AFFF, Alcohol-resistant, and Chemical

72 Summary (cont.) Applications Subsurface injection Surface injection
Seal protection Dike protection Aircraft Hangars Truck loading racks

73 Questions???


Download ppt "Low-Expansion Foam System Design"

Similar presentations


Ads by Google