Acoustical Presentation to the Rocky Mountain ASHRAE Chapter April 16, 2010
2
Discussion Topics Acoustics Overview Frequency Ranges of Mechanical Noise Design Criteria for Typical Spaces Mechanical Noise Control : Areas of Interest Sound Transmission Paths Typical Ductborne Mitigation Methods Typical Duct Breakout Mitigation Methods Typical Structure-borne Noise and Vibration Mitigation Methods Mechanical Design affecting Sound Isolation LEED for Schools
3
Acoustics - A Brief Overview 1. Sound Isolation 2. Noise Control 3. Vibration Control 4. Interior Acoustics 1 234
4
Acoustics 101 Frequency is the rate of repetition of a periodic event. Most sound sources, except pure tones, contain energy ever a wide range of frequencies. For measurement and analysis of sound, the frequency range is divided into sections labeled as octave bands
5
Acoustics 101 Decibel (dB): Measure on logarithmic scale of the magnitude of sound pressure, sound power, or sound intensity level with respect to a standard reference value. L = 20 log (P rms /P ref ) P ref = 20µPa Human Hearing Threshold of Audibility: 0 dB Threshold of Pain: 120 dB Ear cannot differentiate less than 1 dB of change Due to log scale, dB does not add algebraically 1 Vacuum = 90 dB 2 Vacuums ≠ 180 dB 2 Vacuums = 93 dB
6
Acoustics 101
7
Definitions of Terms: Sound Power vs Sound Pressure
8
Definitions of Terms: dBA A-Weighted Sound Levels (dBA) dBA does not completely represent human perception of noise. dBA is used primarily in environmental noise studies and LEED for Schools Requirements.
9
Definitions of Terms: NC Noise Criteria Level (NC) Industry Standard Does not address frequencies below 63 Hz Does not provide sound quality assessment.
10
Definitions of Terms: RC Room Criteria (RC) Probable industry standard for future Addressed frequencies below 16 and 31.5 Hz Provides sound quality assessment. N, R, H, RV Excerpted from Chapter 7, “Sound and Vibration,” of the 1993 ASHRAE Fundamentals Handbook
11
Comparison of dBA, NC, RC NC 36 RC 18 (R) 39 dBA
12
Perception of Sound Decrease of 3 dB represents a halving of sound energy but is a just noticeable difference. Decrease of 10 dB represents a halving of perceived sound levels Decrease of 20 dB represents ¼ of the perceived sound levels Picture from Bell Telephone Laboratories
13
Frequency Ranges of Mechanical Noise Frequency (Hz)Perceptible SoundPossible Reason for Mechanical Noise 0.8 to 31.5ThrobTurbulent Airflow and Fan Instability 31.5 to 125 HzRumbleTurbulent Airflow and Poor Vibration Isolation 125 to 500 HzRoarFan Noise, Turbulent Airflow, VAV Boxes 125 to 1000 HzHum & BuzzPoor Vibration Isolation, Fan Powered VAV Boxes 500 to 2000 HzWhine and WhirrPumps and Chillers 1000 to 8000 HzHiss and WhistleGrilles, Diffusers, Water Valves
14
Design Criteria for Typical Spaces SpaceNC LevelRC (N) Level Recording Studios; Concert Halls15 Studios20 to 2520 Auditorium; Sanctuary2520 to 25 Tele/Videoconferencing; Distance Learning Classrooms25 to 30 Conference Rooms; Classrooms30 to 3525 to 30 Private Offices; Residences3530 to 35 Lobbies, Corridors, Computer Classrooms; Retail4035 to 45 Laboratories; Toilets4540 to 50 Kitchens, Laundry Rooms, Computer Equipment Rooms5045 to 55
15
Mechanical Noise Control : Areas of Interest Equipment Selections Type of Fans, Variable vs Constant, Diffusers/Grilles Noise Data for Equipment Selections AHU’s, RTU’s, VAV Boxes, Cooling Towers, Fan Coil Units, etc… Ductwork layouts Overhead Ducted, Displacement, Under Floor Distribution Ducted vs. Plenum Return Airflow Velocities Plumbing noise Vibration Isolation
16
Sound Transmission Paths Excerpted from Chapter 7, “Sound and Vibration,” of the 2003 ASHRAE Fundamentals Handbook
17
Sound Transmission Paths Excerpted from Chapter 7, “Sound and Vibration,” of the 2003 ASHRAE Fundamentals Handbook
18
Sound Transmission Paths Excerpted from Chapter 7, “Sound and Vibration,” of the 2003 ASHRAE Fundamentals Handbook
19
Sound Transmission Paths Excerpted from Chapter 7, “Sound and Vibration,” of the 2003 ASHRAE Fundamentals Handbook
20
Sound Transmission Paths Excerpted from Chapter 7, “Sound and Vibration,” of the 2003 ASHRAE Fundamentals Handbook
21
Sound Transmission Paths Excerpted from Chapter 7, “Sound and Vibration,” of the 2003 ASHRAE Fundamentals Handbook
22
Typical Ductborne Mitigation Methods Internal Ductliner Attenuates Mid to High Frequencies Distance of ductwork from mechanical equipment Sound Attenuators Most effective at attenuating Mid to High Frequencies Increases Static Pressure Drop Lined Plenum Most effective method for attenuating low frequencies Can be incorporated into AHU and RTU Casing
23
Typical Ductborne Mitigation Methods Double Wall Ductwork Utilized when internally lined ductwork is not allowed. Hospitals, Laboratories Diffuser/Grille Selection Diffusers/grilles should be selected 5 NC points below room criteria. Flex duct connection Airflow velocity Ductwork Airflow velocity Number of elbows and junctions
24
Terminal Units FAN-POWERED, SERIES FLOW, VAV Integral Sound Attenuators Manufacturer NC Ratings CONSTANT OR VARIABLE AIR VOLUME
25
Good Design Practices Fan Discharge Configurations Inlet Configuration Excerpted from Chapter 7, “Sound and Vibration,” of the 2003 ASHRAE Fundamentals Handbook
26
Typical Duct Breakout Mitigation Methods Lagging or Wrapping Attenuates Mid to High Frequencies Utilized primarily for plumbing noise Ductwork Enclosures Most effective at attenuating low frequencies Primarily used for RTU’s Utilized as an extension of Mechanical Room
27
Typical Structure-borne Noise and Vibration Mitigation Methods Concrete Inertia Bases Pumps/Large Fans Spring Isolators Pumps Rotating Equipment Above Grade Chillers/Cooling Towers Neoprene Pads On Grade Chillers/Cooling Towers
28
Typical Structure-borne Noise and Vibration Mitigation Methods Rooftop Isolation Curb RTU’s Spring/Neoprene Hangers Ductwork/Piping 30 foot critical distance Flex Connections Double Bellows
29
Mechanical Design affecting Sound Isolation Crosstalk between Spaces Length of ductwork Junctions and Elbows Internal Ductliner Plenum Return Z or U Shaped Internally Line Transfer Ducts Excerpted from No Noise Classroom Acoustics Publication
30
Mechanical Design affecting Sound Isolation Penetrations Full Height Partitions
31
Mechanical Design affecting Environmental Noise Control Most states, counties, cities, and towns have property line noise ordinances. Typical Day/Night level of 55/50 dBA Typical Equipment Culprits Emergency Generators Radiator, Exhaust, Intake Cooling Towers Fans Rooftop Units Alignment of Compressor/Condenser Section
32
Mechanical Design affecting Environmental Noise Control Mitigation Measures Equipment Locations Adjacent Properties Barrier Walls/Screens Materials Height Louvers Type
33
LEED for Schools Acoustics is now a mandatory LEED credit for Schools Prerequisite 3 Background Noise Requirements: Max BNL of 45 dBA OR Achieve an RC (N) Mark II level of 37 EQ Credit 9: Enhanced Acoustical Performance Background Noise Requirements Max BNL of 40 dBA (1 point) or 35 dBA (2 points) 2: Achieve an RC (N) Mark II level of 32 (1 point) or 27 (2 points)
34
Thanks for Attending Any Questions???? Additional Resources ASHRAE Application Handbook Chapter 47 Architectural Acoustics: David Egan
35
Case Studies Ritz Carlton Denver Boardroom and Conference Areas NC 45+ due to breakout noise (125 Hz) NC 35 Criteria Remedial Measures: Incorporated ductwork enclosure around high pressure running over spaces. NC 34 after implementation of remedial measures
36
Case Studies UCDHSC Research 1 Facility Vibration Issues in NMR and Crystallography Growth Chambers Acoustical testing: Issues at 32 Hz Short circuited spring isolators in AHU fans: Still bolted down for shipping
37
Case Studies