Download presentation
Presentation is loading. Please wait.
Published byLee Booth Modified over 9 years ago
1
1 New Products – Type 2213C006 For usage in fire fighting systems New design, similar to type 46 Small coil with only 18W Compact design No bonnet „Negative-Seat“ – the piston is positioned headfirst Pressure range 1-150 bar
2
Applications Fire fighting system Application: fire fighting with a water mist (fog) instead of a sprinkler system
3
Applications Extinguishing system droplet diameter [mm] Reaction surface [m²/l water] Sprinkler > 1 < 2 Fine spray system 0.120 Water mist system 0.01200 Fire fighting system
4
Applications RTL Television Studio Fire fighting system
5
Applications Requirements to the valve: Pressure: 120bar Leakage: 0% Manual operation G5/4“ to G2“ Mounting in any position High pressure design Fire fighting system
6
Applications Solution: Type: 2/040-27-0601-.242 1-150bar; G6/4; orifice 40,0 mm pilot operated; piston design; NC-non energised closed body material : stainless steel 1.4305 (AISI 303) Internals : stainless steel 1.4104 (AISI 430F) Seal : PTFE / NBR Mounting : actuator in any position Fire fighting system