Download presentation
Presentation is loading. Please wait.
Published byAleesha Burke Modified over 9 years ago
1
1 ASPIRATING SYSTEMS TRAINING e-series
2
2 Overview e-series model range ASD Software NetTracer Detector Monitor PipeTracer
3
3 Pico
4
4 The Pico provides the earliest warning to a potential fire condition within localised areas or where space is limited. Air is drawn from the protected area through a 25mm o.d sampling channel. The Pico continually monitors the samples from areas up to 850m2
5
5 The aspirator has a static pressure of 800Pa providing superior detection times in high air low environments The Pico employs a very high sensitivity smoke detector, with a range of 0.005% to 20% obscuration/metre with four alarm levels. This wide dynamic range allows early warning detection and the ability to trigger suppression systems.
6
6 FT1
7
7 Single channel large bore aspirated early warning smoke detection system Uses a high-sensitivity laser smoke detector combined with a high static pressure centrifugal blower to achieve the earliest warning to a fire condition The large bore pipes are normally 20mm / 25mm o.d. and are sited so that sampling holes along their length provide wide area detection coverage The system has four input pipes with individual flow monitoring, each of which can be up to 100metres in length This unit also comes with a display
8
8 FT4
9
9 Four channel large bore aspirated early warning smoke detection system The system monitors all four input pipes simultaneously and when a trace level of smoke is detected the system raises an initial alert and then performs a rapid scan of each pipe to locate the source of the incident
10
10 FT6
11
11 FT6 Six channel aspirated early warning smoke detection system The system monitors all six input pipes simultaneously and when a trace level of smoke is detected the system raises an initial alert and then performs a rapid scan of each pipe to locate the source of the incident
12
12 FT6 Enviro
13
13 RSU Enviro option Enviro. offers an integrated fire, security and environmental monitoring system in a single package Sensor inputs monitor changes in room temperature and humidity, and provide flood detection Gas detection is integrated for toxic hazards or to supplement the early warning smoke detection where a known emission such as CO is present
14
14 FT15
15
15 FT15 High performance rotary pump enables 50m pipe runs using microbore tubing 15 different sectors can be simultaneously monitored Small-bore pipes enable concealed installation
16
16 ASD
17
17 ASD - High Performance Aspirator The ASD allows the use of simple point detectors within an aspirated system The system incorporates two analogue addressable point detectors providing the ability for failsafe redundancy or mixed detection strategies The ASD utilises a high performance aspirator and flow monitoring circuit
18
18 The flow level is displayed on a 10 element bargraph with adjustments for high and low flow thresholds Flow failure is reported to the central panel as a device fault on the primary detector The ASD incorporates an in-line air filter to remove dust particles from the air sample
19
19 Filter is housed in a removable transparent cartridge enabling rapid inspection and maintenance The ASD provides closed loop sampling whereby the exhausted air can be completely returned to the sampled area making it particularly suitable for prison cells, hospitals and duct sampling
20
20 Software WinTracer Detector Monitor PipeTracer NetTracer
21
21 WinTracer WinTracer software provides a central monitoring service for smoke and gas detection systems
22
22 Central monitoring, calibration and control of all functions. Fully Accessible anywhere across the globe Graphical interface enables fast review of the situation, improving reaction times It has barcharts/spreadsheets of current data
23
23 Front panel representations of the attached units Data is logged to disk for future requirements and can be displayed in trend graphs If an alarm occurs, the user is notified clearly with site maps and sound sequences, along with user definable action and hazard lists
24
24 Detector Monitor The Detector Monitor (DetMon) software allows the detector to be programmed from a PC Displays current smoke levels and diagnostics for the Laser Smoke Detector
25
25 Download/display of rolling data log stored with SRAM inside the Laser Smoke Detector Displays show current smoke & flow levels, along with the detector status With this software, the engineer can inspect, diagnose and tune the Laser Smoke Detector to suit the environment of each site
26
26 The Main Screen showing Diagnostics, Numerical Values, Bar Graph and Strip Chart
27
27 PipeTracer Calculates system response times Models wide-bore systems Straightforward interface All factors taken into account Setting initial parameters
28
28 Details on holes, bends, segments and risers is entered
29
29 Graphical representations of the system are shown
30
30 Performance is given for each pipe and the entire system All data is shown in spreadsheet form The entered data can then be altered to minimise response time
31
31 NetTracer - WEB based central monitoring software Supports multiple ASDs – multiple observers Utilises IBM Websphere middle layer 3D graphics for stacked multi-storey floor plans Nationwide site at top layer All site hazards, alarms and faults seen at nationwide level Stores logged data and flags exceptions Full access control management integrated