Energy Efficient Fluid Flow
2
Fluid Flow System Fundamentals W motor = W fluid / (Eff motor x Eff drive x Eff pump )
3
Look For “Inside” Opportunities to Max Savings Efficiency losses in distribution and primary energy conversion systems multiply “inside” savings Example: –W elec = W fluid / [Eff pump x Eff drive x Eff motor ] –W elec = 1 kWh / [.70 x.92 x.90 ] = 1.7 kWh
4
Fluid Flow System Fundamentals W fluid = V P total
5
Fluid Flow System Fundamentals W fluid = V P total = V (k V 2) = k V 3 W friction = V P friction = k / D 5
6
Pumping System Savings Opportunities Reduce volume flow rate Reduce required pump head P static P velocity P elevation P headloss Increase pump, drive, motor efficiency W elec = V P total / [Eff pump x Eff drive x Eff motor ]
7
Fluid Flow System Saving Opportunities Reduce Required Pump/Fan P Employ Energy Efficient Flow Control Improve Efficiency of Pumps/Fans
8
Reduce Pump/Fan P
9
Increase Reservoir Level to Reduce Elevation Head
10
Minimize Pipe Friction: Use Bigger Pipes/Ducts Use large diameter pipes: P headloss ~ k / D 5 Doubling pipe diameter reduces friction by 97%
11
Minimize Pipe Friction Use Smooth Pipes/Ducts Use smooth plastic pipes: f steel = 0.021 f plastic = 0.018 Pumping savings from plastic pipe (0.021 – 0.018) / 0.018 = 17%
12
Use Gradual Elbows
14
Employ Energy Efficient Flow Control
15
Inefficient Flow Control By-pass loop (No savings) By-pass damper (No savings) Outlet valve/damper (Small savings) Inlet vanes (Moderate savings)
16
Efficient Flow Control Trim impellor for constant-volume pumps Slow fan for constant-volume fans VFD for variable-volume pumps or fans
17
Inefficient and Efficient Flow Control
18
Cooling Towers
19
Cooling Loop Pumps
20
Worlds Largest Bypass Pipe
21
For Constant Speed Pump Applications: Trim Pump Impellor Look for discharge valve at < 100% open More energy-efficient to downsize the pump by trimming impellor blades than throttle flow
22
Trim Impellor and Open Throttling Valve
23
For Constant Speed Fan Applications: Slow Fan Speed by Changing Pulley Diameter Look for discharge damper at < 100% open More energy-efficient to slow fan than throttle flow
24
For Variable Flow Applications: Install VFD W 2 = W 1 (V 2 /V 1 ) 3 Reducing flow by 50% reduces pumping costs by 87%
25
Variable Speed Pumping on HVAC Chilled Water Loops Replace 3-way Valve with 2-way valve on AHU
26
VFDs on Vent Hoods
27
Need Controls for VFDs on Dust Collection
28
Use VFDs on Cooling Tower Fans
29
Pump Long, Pump Slow Identify intermittent pumping applications More energy to pump at high flow rate for short period than low flow rate longer Example: –Current: Two pumps in parallel for four hours –Recommended: One pump for six hours –Estimated Savings: $500 /yr Reason: W fluid = V DP = k V 3
30
Optimize Efficiency of Pumps/Fans
31
Correct Fan Inlet/Exit Conditions No Yes
32
Refurbish Inefficient Pumps Pump not operated at peak efficiency in middle of operating range
33
Resize Miss-sized Pumps Pump operating at off- design point M Eff = 47% Replace with properly sized pump Estimated savings: $14,000 /yr
34
Fluid Flow Summary Reduce Required Pump/Fan Head –Reduce excess elevation head –Smoother pipes/ducts –Larger diameters –Gradual elbows Employ Energy Efficient Flow Control –Constant speed pumping: trim impellor blade –Constant speed fans: Slow fan –Variable flow: Install VFDs –Pump slow, pump long Improve Efficiency Pumps/Fans –Correct fan inlet/exit conditions –Refurbish inefficient pumps –Resize miss-sized pumps/fans