1 Outline Control structure design (plantwide control) A procedure for control structure design I Top Down Step 1: Degrees of freedom Step 2: Operational.

Similar presentations


Presentation on theme: "1 Outline Control structure design (plantwide control) A procedure for control structure design I Top Down Step 1: Degrees of freedom Step 2: Operational."— Presentation transcript:

1 1 Outline Control structure design (plantwide control) A procedure for control structure design I Top Down Step 1: Degrees of freedom Step 2: Operational objectives (optimal operation) Step 3: What to control ? (self-optimizing control) Step 4: Where set production rate? II Bottom Up Step 5: Regulatory control: What more to control ? Step 6: Supervisory control Step 7: Real-time optimization Case studies

2 2 II. Bottom-up Determine secondary controlled variables and structure (configuration) of control system (pairing) A good control configuration is insensitive to parameter changes Step 5. REGULATORY CONTROL LAYER 5.1Stabilization (including level control) 5.2Local disturbance rejection (inner cascades) What more to control? (secondary variables) Step 6. SUPERVISORY CONTROL LAYER Decentralized or multivariable control (MPC)? Pairing? Step 7. OPTIMIZATION LAYER (RTO)

3 3 Step 5. Regulatory control layer Purpose: “Stabilize” the plant using a simple control configuration (usually: local SISO PID controllers + simple cascades) Enable manual operation (by operators) Main structural issues: What more should we control? (secondary cv’s, y 2, use of extra measurements) Pairing with manipulated variables (mv’s u 2 ) y 1 = c y 2 = ?

4 4 Objectives regulatory control layer 1.Allow for manual operation 2.Simple decentralized (local) PID controllers that can be tuned on-line 3.Take care of “fast” control 4.Track setpoint changes from the layer above 5.Local disturbance rejection 6.Stabilization (mathematical sense) 7.Avoid “drift” (due to disturbances) so system stays in “linear region” –“stabilization” (practical sense) 8.Allow for “slow” control in layer above (supervisory control) 9.Make control problem easy as seen from layer above The key decisions here (to be made by the control engineer) are: 1.Which extra secondary (dynamic) variables y 2 should we control? 2.Propose a (simple) control configuration

5 5 Control configuration elements Control configuration. The restrictions imposed on the overall controller by decomposing it into a set of local controllers (subcontrollers, units, elements, blocks) with predetermined links and with a possibly predetermined design sequence where subcontrollers are designed locally. Some control configuration elements: Cascade controllers Decentralized controllers Feedforward elements Decoupling elements Selectors Split-range control

6 6 Cascade control arises when the output from one controller is the input to another. This is broader than the conventional definition of cascade control which is that the output from one controller is the reference command (setpoint) to another. In addition, in cascade control, it is usually assumed that the inner loop K2 is much faster than the outer loop K1. Feedforward elements link measured disturbances to manipulated inputs. Decoupling elements link one set of manipulated inputs (“measurements”) with another set of manipulated inputs. They are used to improve the performance of decentralized control systems, and are often viewed as feedforward elements (although this is not correct when we view the control system as a whole) where the “measured disturbance” is the manipulated input computed by another decentralized controller.

7 7 Why simplified configurations? Fundamental: Save on modelling effort Other: –easy to understand –easy to tune and retune –insensitive to model uncertainty –possible to design for failure tolerance –fewer links –reduced computation load

8 8 Use of (extra) measurements (y 2 ) as (extra) CVs: Cascade control GK y 2s u2u2 y2y2 y1y1 Key decision: Choice of y 2 (controlled variable) Also important (since we almost always use single loops in the regulatory control layer): Choice of u 2 (“pairing”) Primary CV Secondary CV (control for dynamic reasons)

9 9 Degrees of freedom unchanged No degrees of freedom lost by control of secondary (local) variables as setpoints become y 2s replace inputs u 2 as new degrees of freedom GK y 2s u2u2 y2y2 y1y1 Original DOF New DOF Cascade control:

10 10 Example: Distillation Primary controlled variable: y 1 = c = x D, x B (compositions top, bottom) BUT: Delay in measurement of x + unreliable Regulatory control: For “stabilization” need control of (y 2 ): –Liquid level condenser (M D ) –Liquid level reboiler (M B ) –Pressure (p) –Holdup of light component in column (temperature profile) Unstable (Integrating) + No steady-state effect Variations in p disturb other loops Almost unstable (integrating) TC TsTs T-loop in bottom

11 11 XCXC TC FC ysys y LsLs TsTs L T z XCXC Cascade control distillation With flow loop + T-loop in top

12 12 Hierarchical control: Time scale separation With a “reasonable” time scale separation between the layers (typically by a factor 5 or more in terms of closed-loop response time) we have the following advantages: 1.The stability and performance of the lower (faster) layer (involving y 2 ) is not much influenced by the presence of the upper (slow) layers (involving y 1 ) Reason: The frequency of the “disturbance” from the upper layer is well inside the bandwidth of the lower layers 2.With the lower (faster) layer in place, the stability and performance of the upper (slower) layers do not depend much on the specific controller settings used in the lower layers Reason: The lower layers only effect frequencies outside the bandwidth of the upper layers

13 13 QUIZ: What are the benefits of adding a flow controller (inner cascade)? q z qsqs 1.Counteracts nonlinearity in valve, f(z) With fast flow control we can assume q = q s 2.Eliminates effect of disturbances in p1 and p2 Extra measurement y 2 = q

14 14 Objectives regulatory control layer 1.Allow for manual operation 2.Simple decentralized (local) PID controllers that can be tuned on-line 3.Take care of “fast” control 4.Track setpoint changes from the layer above 5.Local disturbance rejection 6.Stabilization (mathematical sense) 7.Avoid “drift” (due to disturbances) so system stays in “linear region” –“stabilization” (practical sense) 8.Allow for “slow” control in layer above (supervisory control) 9.Make control problem easy as seen from layer above Implications for selection of y 2 : 1.Control of y 2 “stabilizes the plant” 2.y 2 is easy to control (favorable dynamics)

15 15 1. “Control of y 2 stabilizes the plant” A. “Mathematical stabilization” (e.g. reactor): Unstable mode is “quickly” detected (state observability) in the measurement (y 2 ) and is easily affected (state controllability) by the input (u 2 ). Tool for selecting input/output: Pole vectors –y 2 : Want large element in output pole vector: Instability easily detected relative to noise –u 2 : Want large element in input pole vector: Small input usage required for stabilization B. “Practical extended stabilization” (avoid “drift” due to disturbance sensitivity): Intuitive: y 2 located close to important disturbance Maximum gain rule: Controllable range for y 2 is large compared to sum of optimal variation and control error More exact tool: Partial control analysis

16 16 Recall maximum gain rule for selecting primary controlled variables c: Controlled variables c for which their controllable range is large compared to their sum of optimal variation and control error Control variables y 2 for which their controllable range is large compared to their sum of optimal variation and control error controllable range = range y 2 may reach by varying the inputs optimal variation: due to disturbances control error = implementation error n Restated for secondary controlled variables y 2 : Want small Want large

17 17 What should we control (y 2 )? Rule: Maximize the scaled gain General case: Maximize minimum singular value of scaled G Scalar case: |G s | = |G| / span |G|: gain from independent variable (u 2 ) to candidate controlled variable (y 2 ) –IMPORTANT: The gain |G| should be evaluated at the (bandwidth) frequency of the layer above in the control hierarchy! If the layer above is slow: OK with steady-state gain as used for selecting primary controlled variables (y 1 =c) BUT: In general, gain can be very different span (of y 2 ) = optimal variation in y 2 + control error for y 2 –Note optimal variation: This is often the same as the optimal variation used for selecting primary controlled variables (c). –Exception: If we at the “fast” regulatory time scale have some yet unused “slower” inputs (u 1 ) which are constant then we may want find a more suitable optimal variation for the fast time scale.

18 18 Minimize state drift by controlling y 2 Problem in some cases: “optimal variation” for y 2 depends on overall control objectives which may change Therefore: May want to “decouple” tasks of stabilization (y 2 ) and optimal operation (y 1 ) One way of achieving this: Choose y 2 such that “state drift” dw/dd is minimized w = Wx – weighted average of all states d – disturbances Some tools developed: –Optimal measurement combination y 2 =Hy that minimizes state drift (Hori) – see Skogestad and Postlethwaite (Wiley, 2005) p. 418 –Distillation column application: Control average temperature column

19 19 2. “y 2 is easy to control” (controllability) 1.Statics: Want large gain (from u 2 to y 2 ) 2.Main rule: y 2 is easy to measure and located close to available manipulated variable u 2 (“pairing”) 3.Dynamics: Want small effective delay (from u 2 to y 2 ) “effective delay” includes inverse response (RHP-zeros) + high-order lags

20 20 Rules for selecting u 2 (to be paired with y 2 ) 1.Avoid using variable u 2 that may saturate (especially in loops at the bottom of the control hieararchy) Alternatively: Need to use “input resetting” in higher layer (“mid- ranging”) Example: Stabilize reactor with bypass flow (e.g. if bypass may saturate, then reset in higher layer using cooling flow) 2.“Pair close”: The controllability, for example in terms a small effective delay from u 2 to y 2, should be good.

21 21 Cascade control (conventional; with extra measurement) The reference r 2 (= setpoint y s2 ) is an output from another controller General case (“parallel cascade”) Special common case (“series cascade”)

22 22 Series cascade 1.Disturbances arising within the secondary loop (before y 2 ) are corrected by the secondary controller before they can influence the primary variable y 1 2.Phase lag existing in the secondary part of the process (G 2 ) is reduced by the secondary loop. This improves the speed of response of the primary loop. 3.Gain variations in G 2 are overcome within its own loop. Thus, use cascade control (with an extra secondary measurement y 2 ) when: The disturbance d 2 is significant and G 1 has an effective delay The plant G 2 is uncertain (varies) or nonlinear Design / tuning First design K 2 (“fast loop”) to deal with d 2 Then design K 1 to deal with d 1

23 23 Cascade control: y 2 not important in itself, and setpoint (r 2 ) is available for control of y 1 Decentralized control (using sequential design): y 2 important in itself Partial control

24 24 Partial control analysis Primary controlled variable y 1 = c (supervisory control layer) Local control of y 2 using u 2 (regulatory control layer) Setpoint y 2s : new DOF for supervisory control Assumption: Perfect control (K 2 -> 1 ) in “inner” loop Derivation: Set y 2 =y 2s -n 2 (perfect control), eliminate u 2, and solve for y 1

25 25 Partial control: Distillation Supervisory control: Primary controlled variables y 1 = c = (x D x B ) T Regulatory control: Control of y 2 =T using u 2 = L (original DOF) Setpoint y 2s = T s : new DOF for supervisory control u 1 = V

26 26 Limitations of partial control? Cascade control: Closing of secondary loops does not by itself impose new problems –Theorem 10.2 (SP, 2005). The partially controlled system [P 1 P r1 ] from [u 1 r 2 ] to y 1 has no new RHP-zeros that are not present in the open-loop system [G 11 G 12 ] from [u 1 u 2 ] to y 1 provided r 2 is available for control of y 1 K 2 has no RHP-zeros Decentralized control (sequential design): Can introduce limitations. –Avoid pairing on negative RGA for u 2 /y 2 – otherwise P u likely has a RHP- zero

27 27 Selecting measurements and inputs for stabilization: Pole vectors Maximum gain rule is good for integrating (drifting) modes For “fast” unstable modes (e.g. reactor): Pole vectors useful for determining which input (valve) and output (measurement) to use for stabilizing unstable modes Assumes input usage (avoiding saturation) may be a problem Compute pole vectors from eigenvectors of A-matrix

28 28

29 29

30 30 Example: Tennessee Eastman challenge problem

31 31

32 32

33 33

34 34

35 35

36 36

37 37 Decentralized control (single-loop controllers) Use for: Noninteracting process and no change in active constraints +Tuning may be done on-line +No or minimal model requirements +Easy to fix and change -Need to determine pairing -Performance loss compared to multivariable control - Complicated logic required for reconfiguration when active constraints move

38 38 Multivariable control (with explicit constraint handling = MPC) Use for: Interacting process and changes in active constraints +Easy handling of feedforward control +Easy handling of changing constraints no need for logic smooth transition -Requires multivariable dynamic model -Tuning may be difficult -Less transparent -“Everything goes down at the same time”


Download ppt "1 Outline Control structure design (plantwide control) A procedure for control structure design I Top Down Step 1: Degrees of freedom Step 2: Operational."