Name: Osamu TSUBOI Country: Japan Registration No.: Group: B5 Pref. Subject: 1 Question: 7 1 Question 7 Non-harmonic-restraint schemes applied in Japan
2
Name: Osamu TSUBOI Country: Japan Registration No.: Group: B5 Pref. Subject: 1 Question: 7 2 1.A non-harmonic-restraint scheme is selected according to the relay principle. 2.Fault current includes lower harmonic; such as 1000kV, cable transmission. Non-harmonic-restraint schemes applied in Japan Non-harmonic-restraint schemes are applied in the following cases:
3
Name: Osamu TSUBOI Country: Japan Registration No.: Group: B5 Pref. Subject: 1 Question: 7 3 Impedance locus scheme For preventing unwanted operation of distance protection relay In Japan, the distance protection is generally used for a transformer backup protection Reactance X calculated by distance protection: varies during inrush almost fixed during fault (for distance protection)
4
Name: Osamu TSUBOI Country: Japan Registration No.: Group: B5 Pref. Subject: 1 Question: 7 4 Current remains balanced between windings of the parallel tank even during inrush (for 1000kV transformer with parallel winding) Parallel winding current-balance relay scheme Series winding Common winding Tertiary winding 61S 61T 61C 61: Current-balance relay 1000kV 500kV 154kV
5
Name: Osamu TSUBOI Country: Japan Registration No.: Group: B5 Pref. Subject: 1 Question: 7 5 Tertiary voltage restraint scheme Drop in transformer tertiary voltage: small during inrush large during internal fault For preventing unwanted trip-lock by the harmonic restraint (for network with lower harmonic) Differential relay Harmonic restraint Small drop in transformer tertiary voltage & & Trip Trip-lock condition