Protection notice / Copyright noticeFor presentation in EWEC 2010 HVDC Solution for Offshore Wind Park Comprising Turbines Equipped with Full-Range Converters Presenting Author - Ranjan Sharma
2
Prepared for EWEC 2010 Ranjan Sharma Siemens Wind Power A/S Page 2 Why High Voltage Direct Transmission (HVDC) ? Future offshore wind-farms Longer transmission distance Higher installed power capacity The amount of charging current associated with HVAC cable increases with distance, resulting in Reduced active power transmission capacity Added losses Reactive power compensation becomes necessary (refer Fig. 1) Gernerally compensated from the two ends of the transmission cable Placing the compensation units between the cable sections in the offshore is not feasible economically Fig. 1 Transmission capacity of HVAC cable with distance It is sometimes a challange finding a strong grid in the close proximity of nearby on-land transmission system A VSC can operate in all four quadrant – absorve or release both active and reactive power, which helps to connect to a weaker grid
3
Prepared for EWEC 2010 Ranjan Sharma Siemens Wind Power A/S Page 3 Description of the System Under Consideration Individual wind turbines in a wind-farm has a configuration as in Fig. 2. Wind Turbine rating – 3.6MVA Generator – Induction generator Power electronics – back-to-back full-range converter The wind-farm collection network is a medium voltage AC grid – 33kV The offshore platform consists of a AC-DC conversion unit (Voltage source converter) The DC power transmission is via sea cables – 200kV Fig. 2 Structure of the wind turbine Fig. 3 Structure of the transmission system The DC-AC conversion unit connects the wind-farm to the on-land transmission system
4
Prepared for EWEC 2010 Ranjan Sharma Siemens Wind Power A/S Page 4 Principle of Operation Under normal operating conditions, the following control strategy is implemented: Wind-farm side VSC operates with fixed AC voltage and frequency Controlled to act as an infinite voltage source Condition is similar to if the wind-farm is connected to the HVAC system No major changes are required in the wind turbine control Grid-side VSC controls DC voltage and the reactive power Total active power generated from the wind farm is thus transfered to the grid. Fig. 3 Structure of the transmission system Fig. 4 Block diagram of converter control
5
Prepared for EWEC 2010 Ranjan Sharma Siemens Wind Power A/S Page 5 Principle of Operation Fig. 3 Structure of the transmission system Fig. 5 Without fault control Fig. 6 With fault-ride-through Fault in the super grid Options Direct fast communication between the converters Use of DC chopper Use the DC voltage rise to detect fault and control the wind farm side AV voltage
6
Prepared for EWEC 2010 Ranjan Sharma Siemens Wind Power A/S Page 6 Principle of Operation The fault-ride-through mode of the turbines can be directly utilized to control the power balance The effect of the grid side fault (or power imbalance) is the increase in DC side voltage Upon the detection of overvoltage in the DC transmission The grid side VSC is set to support the grid with reactive current and limit the active current The VSC at the wind-farm side is set to actively control the DC voltage by reducing the AC voltage Fig. 7 Control sequence of the wind farm side converter During fault in the super grid The upper and the lower DC voltage threshold are defined When the upper threshold level is exceeded, the grid-side converter is set to control the DC voltage To avoide any possible conflict, the grid side VSC releases its DC control during fault
7
Prepared for EWEC 2010 Ranjan Sharma Siemens Wind Power A/S Page 7 Principle of Operation The reduced AC voltage (in the collection network) will activate the fault-ride through mode on the individual wind turbines, hereby reducing power output Once the fault is cleared, the grid side VSC starts delevering power to the grid, causing the DC voltage to drop When the DC voltage crosses the lower threshold value, the operation of the system shall revert to normal Fig. 8 Conditions at the grid side converter
8
Prepared for EWEC 2010 Ranjan Sharma Siemens Wind Power A/S Page 8 Summary The grid conditions are thus reflected at the wind-farm collector network From the wind turbine prospective, the situation is similar as with the HVAC transmission system No major modificaitons required in the structure of the wind turbine Turbines in a wind-farm can still have individual speed control Wind velocity seen by all the wind turbines in a wind-farm may not be same due to the large area that a wind-farm has to cover The proposed control strategy provides flexibility to connect different generator converter topologies to the same VSC platform offshore
9
Prepared for EWEC 2010 Ranjan Sharma Siemens Wind Power A/S Page 9 References: As provided in the published paper: ’ HVDC solution for offshore wind park comprising turbines equipped with full- range converters’ Thankyou for your attention!!!