Fire protection – Combustible Shielding in Instrumental Buildings Daniel Rosberg - WSP AB Dan Madsen – Grontmij AB Fredrik Jörud – ESS AB
2
2 Planning and Building Act (ESS-0002382) Natural Fire => roof steel members No resistance & pillars 60 minutes
3
Radiation Protection Act (ESS-0001051) “As far as reasonable practical, non- combustible materials should be used in installations” “Detect and extinguish quickly those fires that do start” 3
4
General Safety Objectives (ESS-000004) Ionization radiation 4 > 1 mSv to public within a return time of 10 000 years > 20 mSv to public within a return time of 1 000 000 years Demonstrate how to avoid: > 100 mSv to public within a return time of 10 000 000 years
5
Recommendation to limit loss of property (ESS- 0001126) Recommendation to limit loss of property (ESS- 0001126) > 7 M€ => AUT SUPPRESSION > 50 M€ => AUT SUPPRESSION + ANALYSIS
6
Purpose: Evaluate how to handle the combustible shielding to meet requirements 6
7
SUMMARY Install sprinkler in cave Install sprinkler in hall ceiling Allow only redesign of 1 instrument simultaneously OR apply 5 m safety distance Keep HGV on 10 m distance to unprotected fire load Keep field offices/labs on 2 m distance to unprotected fire load 7