Download presentation
Presentation is loading. Please wait.
Published byBrittney Webb Modified over 9 years ago
1
GREDOR - GREDOR - Gestion des Réseaux Electriques de Distribution Ouverts aux Renouvelables Real-time control: the last safety net Journée de présentation GREDOR Thierry Van Cutsem, ULg Moulin de Beez, 29/04/2015
2
Test system with: 75 MV buses 22 DG units (doubly fed induction & small synchronous generators) Distribution networks are expected to host larger amounts of dispersed renewable generation voltage and congestion (thermal overload) problems are expected to occur more often but, hopefully, over limited periods of time Context (1/3) 2
3
Reinforcing the network (“fit-and-forget”) to deal with such temporary problems would be too expensive there is a good opportunity to use Distributed Generation (DG) units as “control means” to remove the security limit violations this is a service for which DG unit operators/owners could be financially compensated see Task 1 of GREDOR Loads with new consumption profiles e.g. electric vehicles, heat pumps, etc. Flexible loads are expected to also provide control means through remote control, complementing smart meters this presentation, however, focuses on DG units only. Context (2/3) 3
4
Automatic control schemes are needed to assist the Distribution System Operator in: correcting voltage and/or congestion emergencies keeping the MV grids within desired operating limits coordinating their actions with transmission system operator Context (3/3) 4
5
Centralized control with system-wide monitoring and model preferred requires a communication infrastructure… …but offers more advanced control capabilities …and communication cost will be much lower than network reinforcement exploit less expensive controls first e.g. reactive power modulation preferred to active power curtailment act in a non discriminatory and transparent manner optimize a system-wide objective with efforts shared by all relevant DG units drive the system from the current (unacceptable) to the desired (secure) operating point do not rely on models which may not be available / accurate especially for loads (sensitivity to voltage not well known !) rely on a simplified model (e.g. infrequently updated) be robust with respect to inaccuracies of this simplified model Desired features of automatic corrective control 5
6
controller Centralized controller: inputs and outputs set-points (updated every ~ 10 s) P, Q (volt. set-point of load tap changer) measurements (refreshed every ~ 10 s) P, Q, V V 6
7
Model Predictive Control computed set-point (sent to DG unit) discrete time predicted output measurement discrete time 7
8
Mode 1 DSO Controller State estimation Network data Real-time measurements MPPT set points static data Non Dispatchable DG units Local controller measurements MPPT : MaximumPower Point Tracking DSO : Distribution System Operator 8
9
DSO Controller State estimation Network data Decision by non-DSO actor Corrective reports Dispatchable DG units Mode 2 Real-time measurements set points static data measurements DSO : Distribution System Operator 9
10
22 DG units controlled controls adjusted every 10 s N c = 3 N p = 3 (larger if LTC actions anticipated) Test system 10
11
Mode 1. Wind increase (t = 20 → 70 s, all 22 wind generators) Congestion corrected by controller 11 Example 1
12
Mode 3.a Decision by non-DSO actor DG units DSO Controller State estimation Network data Corrective reports Real-time measurements set points static data measurements near-future schedule information 12
13
Mode 3.b DG units Controller State estimation Network data Operational planning Corrective reports DSO near-future schedule Real-time measurements set points static data measurements information 13
14
Mode 1 : 9 generators - wind increase (t= 20 → 70 s) Mode 3 : 13 generators - power schedule (t= 150 → 180 s) Overvoltages corrected by controller Example 2 generation schedule 14
15
15 DG unitsControl strategy Capability of anticipating limit violation ? Mode 1 non- dispatchable Normal operating conditions: take no corrective action Emergency conditions: deviate as few as possible from the last normal operating conditions No. Correction is applied after violation is observed Mode 2 dispatched by non-DSO actor Modes 3a & 3b both dispatchable and non- dispatchable Normal operating conditions: control system to follow the schedule Emergency conditions: deviate as few as possible from the schedule Yes. Controls are applied to avoid exceeding the limits Overview of various modes
16
Centralized controller collecting measurements and adjusting set-points of DG units to satisfy operating constraints: currents below limits voltages inside bounds power factor at connection point with transmission system relies on concept of Model Predictive Control moving the operating point progressively from current to desired state compensating for modelling inaccuracies (as a closed-loop control) anticipating the effect of known changes (Modes 3.a & 3.b) uses a simple, infrequently updated sensitivity model takes into account the load tap changer operation as a separate controller or by controlling its voltage set-point constrained optimization problem compatible with real-time operation Summary 16
17
Extensions of formulation treat discrete controls as such in optimization reset DG units at maximum / scheduled power after emergency situation has been corrected and operating conditions improve treat flexible loads and storage devices as additional control variables mitigate high voltage problems in LV grid due to photo-voltaic installations etc. Implementation aspects and further tests Assess practical telecommunication needs Provide more meaningful results with the networks of GREDOR DSO partners Further integration with Task 3 (operational planning) and Task 1 (interactions) etc. Ongoing work in GREDOR 17
Similar presentations
© 2024 SlidePlayer.com. Inc.
All rights reserved.